Sicame Nortroll Dragon LineTroll 110Em User Manual

Sicame Nortroll Dragon LineTroll 110Em User Manual

Remote indicator system - ris

Advertisement

Quick Links

LineTroll
LineTroll
Remote Indicator System - RIS
User Manual
110Eµ
110Eµr
"Dragon"
LINETROLL 110E /110Eµr User Guide May 2014
Page 1 of 16

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Nortroll Dragon LineTroll 110Em and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sicame Nortroll Dragon LineTroll 110Em

  • Page 1  LineTroll 110Eµ  LineTroll 110Eµr Remote Indicator System - RIS “Dragon” User Manual LINETROLL 110E /110Eµr User Guide May 2014 Page 1 of 16...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS LINETROLL 110E/110EµR OVERVIEW ..............3 FUNCTIONAL DESCRIPTION ..................3 2.1. Sensors ......................... 4 2.2. Activation criteria....................... 4 2.3. Indication........................4 2.4. Reset criteria ....................... 4 2.5. Battery lifetime / maintenance .................. 5 2.6. Low battery warning ....................5 2.7.
  • Page 3: Linetroll 110E/110Eµr Overview

    LINETROLL 110Er provides fast fault 1. LINETROLL 110E/110Eµr location enabling reduction in outage times. This represents enhanced service to OVERVIEW the customers thereby improving the utilities image. LINETROLL 110E (110E) is a line mounted fault indicator for local Another important aspect of using fault indication.
  • Page 4: Sensors

    2.1. Sensors In order to avoid activating the indicator due to the magnetising inrush current of the line, it's di/dt sensor is blocked for 5 The magnetic field generated by the line sec. upon re-energising of the line. While current induces a signal in the indicator the blocking time elapses, the line current pickup coil.
  • Page 5: Battery Lifetime / Maintenance

    energised and can in turn reset the indicator after 30 seconds of continuously energised line 2) Automatic reset by internal timer. This timer can be set to: 2, 6, 12 or 24 hours The indicator can also be reset manually at any time by use of a magnet, or by use of the mounting and testing tool KBN-4.
  • Page 6: Application

    fault current has to be taken into 3. APPLICATION account. The application of LINETROLL 110Eµ • On conductors of 5-36 mm diameter. usually requires a previous line survey so that the best use of it may be obtained. For the best economic benefit it is recom- with special emphasis on: mended that the indicators are used: •...
  • Page 7: Application Notes

    4. APPLICATION NOTES The aim of this section is to describe how the LINETROLL 110E indicator behaves in different service situations and network events. 4.1. Energising a healthy line As the magnetising inrush current of a line Figure 6: Delayed reset of flashing. can be very high, the indicator is provided with a 5 seconds blocking which prevents 4.2.
  • Page 8: Transient Fault

    4.3. Transient fault 4.5. Multiple faults Multiple faults sometimes occur. Defective Transient fault cleared within the last network components may burn or break automatic reclosing, will be detected by the due to the electro-dynamic force of the green LED. The LED will flash for 24 fault current and cause a second fault.
  • Page 9: Capacitive Discharges

    4.6. Capacitive discharges To estimate the capacitive discharge current at any line point, you have to calculate the contribution from all the The LINETROLL-110Er indicator is not overhead lines and underground cables directional, it therefore detects current lengths only beyond that point. without discriminating its direction.
  • Page 10: Programming

    4.7. PROGRAMMING 4.7.2. Threshold sensing Switch # Threshold level The indicator has two options for programming; 1. Local by manipulating the 250 A microswitches on the PCB. 500 A 750 A Table 2: Threshold setting 4.7.3. Timer reset Sw # Timer reset 2 hours 6 hours...
  • Page 11: Programming Of Radio Addresses

    5.2. Reset battery monitoring 4.7.6. Programming of radio addresses All indicators in the same location must be When the battery is replaced with a new given a unique ID’s by rotating the address battery the battery monitoring must be selector. reset according to the following procedure It is recommened to give indicators on the for respectively Eµr / (Eµ):...
  • Page 12: Technical Specifications

    7. TECHNICAL SPECIFICATIONS Current consumption: Non-activated: LT-110Eµ: 100µA Nominal voltage : 6-132 kV LT-110Eµr w/RF active: 120uA Starting criteria : Active (flashing) perm/trans: 4.0/0,3 mA. • Line energised for at least 5 Battery: 3.6 V 16,5Ah type KBB-11 seconds followed by a stepped Recommended battery replacement approx.
  • Page 13: Dimensions

    DIMENSIONS Fix the indicator to the hot-stick and raise/lift it to the line as shown 158 mm in fig 14. Pull the stick downwards and against the line, until the line is in correct position, see fig 15. Release the grip-all stick. Figure LINETROLL 110Eµ/110Eµr physical dimensions.
  • Page 14 Battery can be tested by placing a magnet on the yellow spot marked: RESET. After 2 sec the indicator will respond by flashing the LED’s, see § 10. Flashing sequences -Test/Reset. During the last few months of the battery’s life, an yellow LED with a low flashing frequency (1/10 Hz) will indicate that less than 20% of capacity remains and that Figure 17: Opening/ closing the LINETROLL...
  • Page 15: Flashing Sequences

    Flashing sequences: Transient fault: Permanent fault: Transient fault followed by a permanent fault Flashing frequency for main flash (red) is 1/3s, 1/10s after 12 hours. For the transient indication (green) the frequency is 1/5s (1/10s after 12 hours). LINETROLL 110E /110Eµr User Guide May 2014 Page 15 of 16...
  • Page 16 Test & Reset The magnet must be kept at the yellow reset spot for minimum 2 sec to activate test or reset. Manual with magnet RESET Test sequence Manual with magnet Test sequence TEST-sequence: All 5 LED’s rotate 2 times f=1/10s Status indication After a Reset or connection of battery, the indicator will start a 3 min Status Indication,...

This manual is also suitable for:

Nortroll dragon linetroll 110emr

Table of Contents