Download Print this page

Mackwell XYVEX WALL Mounting Instructions

Advertisement

Quick Links

3. Punch out the hole for mains supply wires and two rope mounting holes on top of the mounting base. Connect the
mains supply wires to the terminal, and connect the battery onto the PCBA.
Choose maintained or non-maintained mode by connecting or removing the jumper cap.
* Wire"L""N" to terminal block
DALI wiring
Maintained (default)
Non-Maintained
Jumper cable removed
Jumper cable connected
L: Live
SL: Switched Live
N: Neutral
4. Insert the rope into the mounting hole and secure with nuts.
Put the front cover back.
1. Instruction for Automatic test function
Once the unit is powered up, a self-diagnostics test will be
automatically initiated:
• Monitoring battery, lamp, charge status constantly.
Run 3mins function test every month.
Run 3H duration test every year.
Note: All test functions are preset and no need field adjustment.
2. Dual Colour LED Status Indicator Meaning
Green indicator solid on: Ready/ Normal Operation
Red indicator flashes:
Require service
Status indication for DALI Versions
System status is indicated by a bi-colour LED and by a DALI status flag.
LED indication
Status
System OK
Permanent green
Fast flashing green
Function test underway
(0.1 sec. on - 0.1 sec. off)
Slow flashing green
Duration test
(1 sec. on – 1 sec. off)
Red LED on
Load failure
Slow flashing red
Battery failure
(1 sec. on - 1 sec. off)
Fast flashing red
Charging failure
(0.1 sec. on - 0.1 sec. off)
Double pulsing green
Inhibit mode
Binary transmission of
Address identification
address via green/red LED
Green and red off
Emergency mode
Cable Size & Strip Length
0.75 - 2.5mm²
(0.75-1.5mm² for DALI)
Solid conductor or
7 stranded wire ends
Battery
wire 2 x DALI signal
PCBA
wires to terminal on PCB
jumper cap
5. Finish installation. Switch on.
One flash, 4s pause
Battery disconnected
Two flashes, 4s pause
Low battery voltage
••
Three flashes, 4s pause
Charge board fault
•••
Four flashes, 4s pause
AC/DC transfer fault
••••
Five flashes, 4s pause
LED lamp fault
•••••
Note: When the fault is recovered, press the test button for 2s, the red flashing
indicator will turn green. The fault is cleared, and the unit is back to normal.
3. Button Test
Press test button once
run a 30s duration test
Press test button twice within 2s
run a 3mins duration test
Press test button 3 times within 2s
run a 30mins duration test
Press test button 4 times within 2s
run a 1H or 3H duration test
Comments
Open circuit / Short circuit / LED failure
Battery failed the duration test or function test/
Battery is defect / Incorrect battery voltage
Incorrect charging current
Switching into inhibit mode via controller
Provides the DALI short address of the fitting via binary
code. Red=1, Green=0. Example: 000011= SA3
Battery operation (Emergency mode)
XYVEX WALL
IP40

Advertisement

loading

Summary of Contents for Mackwell XYVEX WALL

  • Page 1 Jumper cable removed Jumper cable connected L: Live SL: Switched Live N: Neutral XYVEX WALL 4. Insert the rope into the mounting hole and secure with nuts. 5. Finish installation. Switch on. Put the front cover back. IP40 1. Instruction for Automatic test function...
  • Page 2 Normal Operation: The green LED indicator stays on when connected to mains supply. The indicator will turn 1. Cut out size: L300-315mm x W160-175mm. Four 2. Pry off the front cover and get access to the off when the mains supply fails, or when the internal charger malfunctions, or when the luminaire is in test mode. springs for fixing the luminaire onto the ceiling.