Return Material Authorization (RMA) Warranty Service Advanced Replacements Overview Installation Before You Begin Placement Network Connections Testing Troubleshooting Specifications Electrical Operating Environment Index Glossary VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 2...
Any changes or modifications not expressly approved by VES Fire Detection Systems could void the user's authority to operate this equipment under the rules and regulations of the FCC.
INTRODUCTION Technical Support For technical support, contact VES at 800.274.9514 or e-mail techsupport@ves-network.com. VES technical support is available Monday through Friday, 9:00 AM to 6:00 PM, EST. For technical support, contact Shield at +44 1708 377731 or e-mail elv@shieldglobal.com. Shield technical support is available Monday through Friday, 8:00 AM to 5:00 PM.
Products returned using the advanced replacement process must be received within 30 days of the RMA issue date. VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 5...
Overview OVERVIEW The L@titude Network Module (S723) provides supervised, enhanced high-speed communication for networking up to a maximum of 127 fire control panels. The network provided by this module can support combinations of L@titude Fire Alarm Control Panels and L@titude Vision Annunciators.
Installation INSTALLATION This section explains the installation procedure for the L@titude Network Module (S723). Notify the monitoring center and location security that the L@titude Fire Alarm Control Panel will be temporarily out of service. Remove the module from its packaging and check its contents.
2. Connect the 40 conductor connector of the Network Module to the 40 conductor connector of the LCD Main Processor Board as shown. VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 8...
Control Panel's Main Back Board after installing the Network Module. The following figure illustrates the typical network connections of a 3 panel, Class X network: VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 9...
Page 10
Field wiring must be connected in order for the Network Module to operate properly. A singular panel installation must be wired as shown. VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 10...
Yellow Full duplex (on) half duplex (off) LED 10 Ethernet Speed 10MHz (off), 100MHz (on) LED 12 Communication Green Communication present when flashing VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 11...
This event indicates that the link impedance measurement has detected an Partial Open Circuit Trouble impedance above the normally expected range. VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 12...
L@titude Fire Alarm Control Panel: 24V DC Operating Environment Dry indoor use only. Temperature Range F (-5 C) - 120 F (49 Relative Humidity Up to 95%, non-condensing VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 13...
Class A 3 Class X 6, 9 Heartbeat 11 LCD Main Processor Board 7 Network 4, 6-7, 12-13 Terminals 9 Trouble 6, 10 VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 14...
DIP Switch A group of two-position electrical contacts mounted in a Dual Inline Package (DIP), typically used to set address or function information. VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 15...
Page 16
Supervision Monitoring the integrity of a circuit or device to detect a fault condition that would prevent nor- mal operation. VES Fire Detection Systems Version 1.05 | May 2019 | MAN-1436VES L@titude Network Module (S723) Information Guide Page 16...
Need help?
Do you have a question about the S723 and is the answer not in the manual?
Questions and answers