Energy storage system (ess) 12kw / 15kw hybrid inverter / lfp 14.3kwh - 42.9kwh battery (36 pages)
Summary of Contents for Lion Energy SANCTUARY 99990814
Page 1
SANCTUARY INSTALLATION GUIDE Sanctuary 12K Energy Storage System (ESS) ™ 8kW AC / 12kW PV Hybrid Inverter / Charger and 13.5kWh - 40.5kWh Lithium Iron Phosphate Battery Installation Guide Updated 6/15/23...
Page 2
SANCTUARY INSTALLATION GUIDE READ THIS INSTALLATION GUIDE IN ITS ENTIRETY BEFORE OPERATING THE UNIT. This unit provides safe, silent, and renewable electric power. It is very important to carefully read this Installation Guide before using the product. Keep this guide for future reference. Carefully read and comply with all safety directives.
Sanctuary system(s) to be placed in parallel home, the correct sizing of the Sanctuary is (please contact Lion Energy for more details). key for the system to function properly. Before sizing, you must review the Sanctuary technical Note that the Sanctuary is only sold with both specifications.
SANCTUARY INSTALLATION GUIDE Inverter Overview High Voltage DC Switch Power Gen Signal Start 12V DC Power Supply Remote location for Rapid Shutdown Switch Shutdown Connection WiFi Control Comm Comm Module Port A Port B CT 2 CT 1 Coms Invert Ether Coms Coms...
SANCTUARY INSTALLATION GUIDE Inverter Parts and Components 1 Per Inverter 1 Per Inverter Inverter Standoff Inverter Bracket Set Wall Mount 1 Per Inverter 1 Per Inverter 12K Inverter (#50170168) Inverter Wall mount CT Pair Bracket Set (#50170168) 2 Per Inverter 1 Per Inverter 1 Per Inverter 1 Per Inverter...
Page 7
SANCTUARY INSTALLATION GUIDE Battery Parts and Components 1 Per Battery 1 Per Battery Freestanding Wire Box Battery Bracket (#90000504) 1 Per Battery 4 Per Battery 13.5kWh Battery Sanctuary Energy (#50170132) Wire Box Cover Wire Box Housing Bolts Storage System (#90000506) (#90000518) 1 Per Battery 1 Per Battery...
SANCTUARY INSTALLATION GUIDE Installation Location Before installing the Lion Sanctuary System (inverter/charger and battery), consider the following when choosing a location for installation: • Install the Sanctuary System in a climate controlled location, regulated temperature between 32º to 86º F. The Sanctuary ESS cannot be installed in a living space. In other words, the Sanctuary ESS needs to be installed in a garage or utility/storage room, not your family room.
SANCTUARY INSTALLATION GUIDE Location Preparation: The Lion Sanctuary ESS battery is designed to be mounted on a wall using a French Cleat system, the inverter is designed to be mounted to the top of the battery and directly to the wall. It is recommended that you install a suitable material such as plywood onto an existing wall for anchoring.
SANCTUARY INSTALLATION GUIDE Mounting Brackets Inverter Wall Mount Step 1: Mount Inverter standoff brackets and Inverter wall mount brackets to the back of the inverter. Inverter Wall Mount Brackets Step 2: Measure a minimum of 30½” from the floor to the top of the battery bracket and secure the battery bracket to the wall.
Page 11
SANCTUARY INSTALLATION GUIDE 32 ⅞” Optional Battery Optional Battery 30 ½” Floor Floor 22 ½” 22 ½” (Yields a recommended 4” spacing between batteries for ease of installation) Minimum battery spacing allowable is 0.5 inches as stated on UL Certificate.
SANCTUARY INSTALLATION GUIDE Low Voltage DC Wiring: 1 Inverter When wiring 1 inverter to 1 battery, first check the voltage of the Battery. It should be between 45-55.6VDC. If it is not, contact LionESS support at (435) 244-3352. Connect the battery cables to the inverter first. Now connect the cables to the battery receptacles last.
Page 13
SANCTUARY INSTALLATION GUIDE Step 4 Step 1 Busbars Step 2 Step 3 Battery Voltage When connecting multiple batteries, check voltage on each battery first. Batteries must be within 0.5V in order to connect in parallel.
Page 14
SANCTUARY INSTALLATION GUIDE Low Voltage DC Wiring: Multiple Inverter (3 Inverters, 6 Batteries) Battery Voltage Step 1: Mount busbars directly below each inverter. Connect busbars to each other. Recommended to add 225A T-Fuse to positive cable between busbars. (cables and T-Fuses not When connecting multiple provided).
SANCTUARY INSTALLATION GUIDE High Voltage DC Wiring The Sanctuary Inverter has 4 MPPT’s that are capable of 3kW of solar each, for a total of 12kW’s. The minimum allowable voltage is 150VDC. The maximum allowable voltage is 500VOC. The max PV ISC is 13ADC per MPPT.
Page 17
SANCTUARY INSTALLATION GUIDE PV Connection It is important for system safety and efficient operation to use the appropriate cables for the PV module connections. To reduce risk of injury, use the recommended cable size given in the table below. The Sanctuary system accepts up to 10 AWG wire for PV connection. PV Module Wire Connection Verify correct polarity of all wire connections for the PV modules and PV input connectors.
SANCTUARY INSTALLATION GUIDE Rapid Shutdown The Sanctuary inverter has a built in 12 Volt DC power supply for a rapid shutdown (RS) transmitter. The RS ransmitter is polarity sensitive. The 12 Volt supply is located as highlighted below:...
SANCTUARY INSTALLATION GUIDE Remote Shutdown Switch If you are installing a remote shutdown switch, remove the black wire on the 12 volt circuit board on the inverter. Next, mate this wire and run one wire out to the remote shutdown switch. Then on the other side of the switch, run one wire back and connect it into the contact where the black wire used to be on the circuit board.
SANCTUARY INSTALLATION GUIDE AC Wiring: 1 Inverter For grid-tied installation, the Sanctuary is capable of up to a 90 Amp grid-supplied pass-through. The grid input power must come from an appropriately sized circuit breaker. The maximum wire size the inverter terminals can accept is 2 AWG copper. Inverter to cover Essential Loads Install two breakers into the Main Panel.
Page 21
SANCTUARY INSTALLATION GUIDE AC Wiring: Multiple Inverter For a Grid-Tied installation, the Sanctuary is capable of up to a 90 Amp grid-supplied pass-through. The grid input power must come from an appropriately sized circuit breaker. The maximum wire size the inverter terminals can accept is 2 AWG copper. 3 Inverters to cover whole home backup Between the Meter and the existing Main Panel, install a combiner panel with 4 breakers.
SANCTUARY INSTALLATION GUIDE CT Installation Using the provided CT’s, clamp the CT loops in front of the main service panel with the arrow on the CT pointed away from the Sanctuary ESS towards the grid. Arrows on the CT sensors must point away from the main panel and towards the grid power source...
SANCTUARY INSTALLATION GUIDE Generator Wiring : 1 Inverter The Sanctuary ESS is compatible with 240V split phase home backup generators. The Sanctuary can function with both a manual or an auto start feature. It can accept up to 8kW of input power through the Gen input to cover loads and to charge batteries.
Page 24
SANCTUARY INSTALLATION GUIDE Generator Wiring: Multiple Inverter L1 L2 PHASING It is of vital importance that the grid input and load output phases on multiple breakers match. Crossing phases WILL cause a catastrophic failure on the equipment See continuity testing on page 25 The Sanctuary ESS is compatible with 240V 2 Wire Auto Start...
Page 25
SANCTUARY INSTALLATION GUIDE Continuity Testing: Single Inverter When installing a multiple inverter Sanctuary, it is essential to not cross phases. This means, Line 1 needs to remain Line 1 on Grid Input and Load Output for all Inverters. Line 2 needs to remain Line 2 on Grid Input and Load Output for all Inverters.
Page 26
SANCTUARY INSTALLATION GUIDE Continuity Testing: Multiple Inverters Essential Loads Panel Parent Inverter Child Inverter WiFi Control WiFi Control Comm Comm Comm Comm Module Module Port A Port B Port A Port B CT 2 CT 1 CT 2 CT 1 Coms Coms Invert...
SANCTUARY INSTALLATION GUIDE Load Output Continuity Testing: L1 After you have turned the load output breakers on, Turn your multimeter on to test Ohms(Ω). Touch the probes together to ensure your multimeter is functioning properly (You should hear an audible ring, if not make sure the probes are plugged in properly and that you have selected the multimeter to ring).
SANCTUARY INSTALLATION GUIDE Parallel Inverter Connection When wiring 2 Parent Child inverters in parallel, using the provided cat5 cable: Connect cat5 cable on Parallel B located on the Parent Inverter to Parallel A on the child Inverter as shown. WiFi Control WiFi Control Comm Comm...
MULTIPLE INVERTER SYSTEM Inverter Communication (Comm) Wiring Step 1: On the Parent Step 1 Inverter, unplug the 6.5” Cat 5 patch cable from WCM inverter Parent Child 1 Child 2 com port. Leave the other end plugged into the Inverter Comm Port.
Port Port Port Parent Battery Child 1 Battery Child 2 Battery You’re now ready to begin the commissioning process. Please make sure you have completed the training and have received a login to the Lion Energy App. Please visit smart.lionenergy.com...
SANCTUARY INSTALLATION GUIDE Fault Information and Processing The table below lists the possible fault codes that might occur if the inverter malfunctions. Error Name Description Solutions Code Occurs when the load Limit load usage to 8kW total (4kW per leg max) Over-Current is drawing too much per inverter.
Page 33
This happens when 1. Try power cycling inverter. Battery Over- A1_5 battery is over the Voltage 2. Contact Lion Energy voltage limit. This happens when 1. Ensure grid input voltage is within range. grid input voltage is A1_6 Grid Low Voltage 2.
Page 34
2. Check wire orientation of BMS cable and Failure communicating with re-wire BMS cable if incorrect (reference the inverter. installation guide) 3. Power cycle the inverter. 1. Power cycle inverter A2_12 *Battery Fault Contact installer. 2. Contact Lion Energy...
Page 35
2. Power cycle the inverter. current rating. 1. Power Cycle the inverter. A2_14 Grid Phase Error Contact installer. 2. Contact Lion Energy 1. Check Solar wiring to ensure correct connections. ARC Fault A2_15 Contact installer. Detected 2. Power Cycle the inverter.
Sanctuary 12kW Energy SANCTUARY INSTALLATION GUIDE Storage Inverter SANCTUARY™ ENERGY STORAGE SYSTEM Model #99990814 – 12K Hybrid Solar Inverter with 13.5kWh Energy Storage Model #99990815 – 12K Hybrid Solar Inverter with 27.0kWh Energy Storage Model #99990816 – 12K Hybrid Solar Inverter with 40.5kWh Energy Storage Model #50170168 Hybrid Solar Grid Support Interactive Inverter PV Input Max PV Input...
3. Installer repairs the unit or if the unit is to be replaced, Lion Energy will ship the unit to the Installer. 4. Installer replaces the unit and ships the replaced unit to Lion Energy for proper recycling.
Page 38
SANCTUARY INSTALLATION GUIDE 735 S. Auto Mall Drive Suite 200 info@lionenergy.com 385.375.8191 American Fork, Utah lionenergy.com Monday - Friday @lionenergy 9:00 AM - 5:00 PM MST 84003...
Need help?
Do you have a question about the SANCTUARY 99990814 and is the answer not in the manual?
Questions and answers