1. Owner's manual
1.1 Turning the system On or Off
Press the [On/Off] button to turn the
system on - The word "ON" will
appear on display.
Press again to turn the system off
- the word "OFF" will appear on
display.
1.2 Adjusting the set-point temperature
Press the
or
button – the set-
point temperature will appear on
display.
Press again to adjust the set-point.
1.3 Selecting system mode
Press the [Mode] button to select between:
Fan only
Auto mode
Notes:
- The
or
icons will flash on display on demand for
cooling or heating.
- The mode selection may be limited or disabled when
connected to some types of controllers
Unit ON
Unit OFF
Heating
Cooling
+972-3-9626462
Tel
+972-3-9626620
Fax
www.meitavtec.com
1.4 Selecting fan speed
Press the [Fan] button to select between fan speeds:
Auto
Low
speed
speed
Note:
- The fan speed selection may be limited or disabled when
connected to some types of controllers
1.5 Auto fan selection (fan on demand)
Press and hold the [Fan] button for to
turn Auto fan ON or OFF.
When ON, the fan will run on demand for cooling or
heating,
When OFF, the fan will run continuously.
Notes:
- Auto fan cannot be selected in Fan only mode.
- The auto speed selection may be limited or disabled
when connected to some types of controllers
1.6 Errors and alarms
F8 – Communication error between the main board and the
panel.
Note: F8 will appear on the first activation of the unit and will
automatically disappear after a few seconds.
If the indication remain on display, check the wiring
between the unit and the main board and the panel.
F8/F5 flashing alternately – wrong communication protocol.
In order to change the protocol. Press and hold the [Fan]
and [Mode] buttons simultaneously for 10 seconds until
"P00" appears on display.
Using the [+] and [-] buttons switch between "0" and "1".
Press the [On/Off] button to exit settings mode and
resetting the unit.
Medium
High
speed
speed

Advertisement

loading
Need help?

Need help?

Do you have a question about the ALT/X500 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for meitav-tec ALT/X500

  • Page 1 1.4 Selecting fan speed Room Panel Press the [Fan] button to select between fan speeds: ALT/X500 Owner’s manual & Technician settings Auto Medium High speed speed speed speed Note: - The fan speed selection may be limited or disabled when connected to some types of controllers 1.5 Auto fan selection (fan on demand)
  • Page 2 2. Installation instructions 4. Technician settings The ALT/X500 room panel is designed for wall mounting in the Entering technician settings Press the [On/Off] and [Mode] buttons simultaneously for room to be controlled. 10 sec. It should be located where the occupant can easily read the Press the [Mode] button to proceed to the next parameter.