COBALT Pro
Wall Sensor
Standard Operations
USER MODE
The normal state of the valve. The valve is in user mode when it detects that its cover is on, or if it has been in maintenance mode
for more than 30 minutes. Auto activations are only available in user mode.
ACTIVATION
Auto-Activation
The valve will automatically flush based on IR detection. The IR sensor has 3 LEDs, a red, green, and blue to indicate detection
and activation status.
When no object is detected no LED indication will display.
After 5-7 seconds of detecting an object, the valve will be considered "locked on" and a green LED will blink in 5-second intervals
up to 30 seconds.
When an object exits from lock-on the valve will Auto-Activate.
Manual Activation
There are two manual activation buttons on the plate. The left button performs a reduced flush, while the right button performs
a standard flush.
Sentinel Activation
The valve can automatically activate 24 hours after the last activation, by default Sentinel Activation is off. To toggle Sentinel
Activation on and off hold down the Activate button in the interface box (not the Manual Activation buttons) for 5 seconds. The
green LED in the IR sensor window will blink 3 times to indicate it has been turned on, or the red LED will blink 3 times to indicate
it has been turned off.
Activation Refusal
When an activation is attempted but the valve is unable to activate, a red LED will flash. This can be caused by obstructions
or being temporarily disabled. Valves are automatically temporarilyy disabled for 3 seconds after activation.
TruFLUSH
®
Pro devices use TruTOUCH®, an algorithm based on water pressure to optimize flush volumes.
DEFAULT SETTINGS
Range
Exit Time
Water Savings
Base Volume
Redetect Time
I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com
One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents
101822 / 101675 / 101929 / 101674
Urinal
25"
1 second
0%
0.25gpf
1 second
Water Closet
43"
3 seconds
0%
1.1gpf
15 seconds
Rev 081123
page 1

Advertisement

loading

Summary of Contents for I-CON COBALT Pro 101822

  • Page 1 1 second 15 seconds page 1 I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com Rev 081123 One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents...
  • Page 2 After 5 seconds profile mode will end, and the LEDs will clear. page 2 I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com Rev 081123 One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents...
  • Page 3 Adjusts the maximum range used to detect a user. The range can be adjusted from 6-54 inches. page 3 I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com Rev 081123 One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents...
  • Page 4 Adjusts the amount of time a user must be out of range before another user can be detected. The range can be adjusted from 0-60 seconds. page 4 I-CON Systems, Inc., for product support call 1-866-730-7192 or visit us online at support.i-con.com Rev 081123 One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents...

This manual is also suitable for:

Cobalt pro 101675Cobalt pro 101929Cobalt pro 101674