Table of Content 1. Introduction ................................3 2. Appearance ................................4 3. Circuit Breaker Specifications ..........................5 4. Main Features ................................7 5. Set up Instruction ..............................7 6. Data Transmission ..............................9 6.1 Default Value of Protection Parameters ......................10 6.2 Example of ReportDataCmd...........................
RP02RH3PNL Wireless 3P+N Miniature Circuit Breaker with Power Meter and Leak Detection RP02RH series is a class C smart Miniature Circuit Breaker with Power Meter based on LoRaWAN open protocol. It can monitor the status of all external circuit breakers in real time. (connect up to 9 poles).
LoRaWAN: LoRaWAN uses LoRa technology to define end-to-end standard specifications to ensure interoperability between devices and gateways from different manufacturers. 2. Appearance RS-485 Interface Indicator Function Key Antenna LoRa/LoRaWAN Radio Module 485 Signal Line External Circuit Breaker Power Module LoRa/LoRaWAN Radio Module RP02RH1PN...
4. Main Features ⚫ Compatible with LoRaWAN ⚫ Support RS485 serial port transparent transmission. ⚫ Circuit breaker attribute value collection. ⚫ Multiple circuit breaker protection. ⚫ Simple operation and setting. 5. Set up Instruction On/Restore to factory setting Power on Power supply of power module Turn on Power supply of power module, the green light flashes once: success...
Page 8
Function Key Function: Restore to factory setting Press and hold for 5 seconds The green indicator flashes for 20 times: success The green indicator remains off: fail The device is in the network: green indicator flashes once and sends a format report Press once 87 + ReceiveData (ReceiveData is the latest received data) format report The device is not in the network: green indicator remains off...
The data transmission cycle of the device shall be subject to the burning configuration. The interval between two reports must be the maximum time. Refer to Netvox LoRaWAN application command documents and command for data analysis reported by the device. http://cmddoc.netvoxcloud.com/cmddoc...
Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version DeviceType– 1 byte – Device Type of Device The DeviceType is listed in Netvox LoRaWAN Application DeviceType doc ReportType – 1 byte –the presentation of the NetvoxPayLoadData,according the DeviceType NetvoxPayLoadData– Fixed bytes (Fixed =8bytes) 6.2.1 1PN/1PNL Report Data...
Page 14
Note: Please refer to the above NetvoxPayLoadData description for the specific reported data. If no related alarm is set, all alarm related information bits are set to 0. #Packet 1:01C9110105000103800000 BreakerRS485Addr=1 BreakerType=3PN BreakerProtectStatusBits=Alarm AlarmStatusBits= A/B/C Phase UnderVol Low voltage alarm),0x380= 11 1000 0000(bit7~bit9=1) Pre_TripStatusBits3PN=NULL #Packet 2:01C9120100000000000000 BreakerRS485Addr=1...
For example, if the RP02RH series is externally connected with two 1PN and one 3PN, the configured ReportMaxTime must be greater than (2 * 1PN reportcount + 1 * 3PN reportcount) * MinTime 6.3.2 Remote Control Circuit Breaker...
It is assumed that the protocol format of the external RS485 device is Transmission frame: 010400100002700E Return frame: 01040440C5D2F2235C Configure device SensorRawCmd Downlink: 0501040010000270E Device return: 8500 (configuration successful) 8501 (configuration failed) Report after 5s: 8701040440C5D2F2235C 7. Application Smart Home Current situation of power consumption ⚫...
Page 19
⚫ Cost reduction: Students’ dormitories realize remote meter reading charges and reduce management costs Intelligent Building Current situation of power consumption ⚫ Complex power environment, high personnel density and poor strain capacity ⚫ Serious waste of electric energy ⚫ Personnel use high-power electrical appliances in violation of regulations, which has great hidden dangers to cause fire ⚫...
Page 20
electrical fire early reduce the occurrence of electrical fire hazards Information communication Current situation of power consumption ⚫ High requirements of power supply continuity ⚫ Difficult regional maintenance and high fault maintenance cost ⚫ Unclear cause of electrical fault ⚫ Failure to supply power in time Coping strategies ⚫...
8. Installation Danger ⚫ There may be danger of electric shock, explosion and electric arc burn. ⚫ When working on this power device, please cut off all power supplies first. ⚫ Violation of these instructions may result in serious personal injury. Note ⚫...
Page 22
1: The 12VDC power module, LoRa/LoRaWAN Radio Module and circuit breaker are arranged in the order shown in the figure above. 2: Clamp the 12VDC power module, LoRa/LoRaWAN Radio Module and circuit breaker back hooks on the guide rail, and then release the clips.
Page 23
4. The wiring diagram of 12VDC power module, LoRa/LoRaWAN Radio Module, circuit breaker and load are as follows: RP02RH1PN ( Power Module + LoRa/LoRaWAN Radio Module + 1PN Circuit Breaker ) RP02RH1PNL ( Power Module + LoRa/LoRaWAN Radio Module + 1PNL Circuit Breaker )
Page 24
RP02RH3PN ( Power Module + LoRa/LoRaWAN Radio Module + 3PN Circuit Breaker ) RP02RH3PNL ( Power Module + LoRa/LoRaWAN Radio Module + 3PNL Circuit Breaker )
Ensure that the device is powered on after the above installation is correct, and the status after power on: 1: The power on indicator of LoRa/LoRaWAN Radio Module flashes once, then the indicator remains off, and the indicator does not respond when pressing the key. 2: The power module indicator is always on after the power module is powered on.
8.3 Dial Switch Status Indicator: Closing indication: The indicator is green. Opening indication: The indicator is red. Status Indicator Fault indication: The indicator is flashing red. Fault to be closed: The indicator is flashing green. Manual state: The indicator is flashing red and green alternately. Dial Switch Dial switch: Operate the manual and automatic state of the control module.
8.5 Combination of Power Modules and Circuit Breakers Because the external circuit breaker will be limited by the power module, the currently provided power module (with an output power of 24W) can be externally connected to a circuit breaker with a maximum of 9 poles. If the circuit breaker with more than 9 poles is connected, it needs to be expanded through the power supply, but the LoRa/LoRaWAN Radio Module device can connect up to 32 circuit breakers.
Page 28
The output power of the power module is 24W, and the combined wiring diagram of the number of circuit breakers that can install the load is as follows: 1. A power module+1PN(L)*2+3PN(L)*1 2. A power supply module + 1PN(L)*4...
3. A power module + 3PN(L)*2 9. Important Maintenance Instruction Kindly pay attention to the following in order to achieve the best maintenance of the product: ⚫ Keep the device dry. Rain, moisture, or any liquid might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.
Need help?
Do you have a question about the RP02RH Series and is the answer not in the manual?