Honeywell 5817CBXT Quick Start Manual page 2

Wireless commercial transmitter

Advertisement

5817CBXt
WireLess CommerCiAL TrAnsmiTTer
Switch
Setting
On
Off
Notes: a. In order for the control panel to enroll the transmitter, the DIP switches must be Set to OFF-ON-ON-OFF (see Diagram 2).
b. The auxiliary loops are not affected by the DIP switch settings.
Wiring Connections
Connect the loop wiring to the unit's terminals before installing the battery (see Diagram 2).
Notes: a. Primary loop 1 is a supervised loop and must have an end-of-line (EOL) resistor (470K ohms, supplied) placed across the sensor.
Additionally, for primary loop 1, a contact device may not be installed more than 20 feet from the transmitter.
b. If loop 2 is not going to be used, the magnet is not necessary.
c. If loop 3 is not going to be used, no connection is needed across its terminals. For UL household burglary and fire installations, the loop 3
contact device (if used) may not be more than 3 feet from the transmitter.
spEcIfIcaTIONs:
• Dimensions:
- 1-9/16" W x 3-1/2" H x 1-3/16" D
(40mm x 89mm x 30mm)
- Battery 3v Lithium
(see BATTerY insTALLATion
AnD rePLACemenT).
• UL Listings:
- Commercial Fire
- Household Fire
- Household Burg
- Commercial Burg UL 365, UL 609,
• Battery Type:
- Cr123 Lithium
Figure 1. Mounting Plate
NOTE: For UL commercial and household fire installations, only one initiating device may be connected to this transmitter. For UL commercial burglary
installations, multiple initiating devices may be used as long as the devices all service the same function such as door/window contacts, motion or
glassbreak detectors. All initiating devices must be located within the same room. no more than one wire per terminal may be connected. Use only
14-22AWG wire.
ORDERING
5817CBXt
Wireless Commercial Transmitter
automation and control solutions
Figure 3. 5817CBXT Transmitter, Top Cover Removed
Honeywell Security Products Americas
2 Corporate Center Dr. Suite 100
P.o. Box 9040
melville, nY 11747
1.800.467.5875
www.honeywell.com
Repeating transmission (every 4 sec.) upon primary loop fault use high priority alarm, such as fire.
Single transmission per primary loop change-of-state.
Figure 1. Mounting Plate
UL 864
UL 985
UL 1023
UL 1076, UL 1610
Primary Loop Options Table
DIP Switch Position
1
Figure 2. Case Back
Figure 3. 5817CBXT Transmitter, Top Cover Removed
L/5817CBXTD/D
october 2014
© 2014 Honeywell International Inc.
Figure 1. Mounting Plate
Figure 2. Case Back
Figure 3. 5817CBXT Transmitter, Top Cover Removed