Items To Check Before Diagnostics; Test Run Mode And View Mode - Samsung AE044MXTPEH Service Manual

Eco heating system
Hide thumbs Also See for AE044MXTPEH:
Table of Contents

Advertisement

4-5 Items to check before diagnostics

4-5-1 Test run mode and view mode

█ Display Option Key
KEY operation
KEY
Press once : Heating test run
K1
Press twice : Defrost test run
Press 3times : Finishing test mode
Press once : Cooling test run
(Heating Only : skip)
K2
Press twice : Output signal test run
Press 3 times : Finishing test mode
K3
Reset
K4
View mode
■ VIEW mode display
Number
Display contents
of press
0
Communication State
1
Order frequency
2
Current frequency
3
Pump output
4
Outdoor air sensor
5
Discharge sensor
6
Eva in sensor (MONO)
7
Inlet water sensor (MONO)
8
Outlet water sensor (MONO)
9
Cond sensor
10
Current
11
Fan RPM
12
Target discharge temperature
13
EEV
14
Protective control
15
IPM temp.
long-1
Main Micom version
long-1 and 1
Inverter Micom version
long-1 and 2
EEPROM version
Samsung Electronics
7-segment display
" " " " "BLANK" "BLANK"
" " " " "BLANK" "BLANK"
-
" " " " "BLANK" "BLANK"
" " " " "BLANK" "BLANK"
7-segment display
-
-
Refer to View mode display
Segment 1
10s digit of Tx
1s digit of Tx
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Year(Dec)
Month(Hex)
Year(Hex)
Month(Hex)
Year(Hex)
Month(Hex)
KEY (K1~K4)
AE090~160JXEDSH
Display
Segment 2
Segment 3
10s digit of Rx
100s digit
10s digit
100s digit
10s digit
100s digit
10s digit
+/-
10s digit
100s digit
10s digit
+/-
10s digit
+/-
10s digit
+/-
10s digit
+/-
10s digit
10s digit
1s digit
1000s digit
100s digit
100s digit
10s digit
1000s digit
100s digit
Protective
control
0 : No protective
control
0 : Cooling
1 : Freezing
1 : Heating
2 : Defrosting
3 : Over-load
4 : Discharge
5 : Total current
+/-
10s digit
Day(two digit)
Day(two digit)
Day(two digit)
ON
1 2 3 4
AE040~060JXEDSH
Units
Segment 4
1s digit of Rx
-
1s digit
Hz
1s digit
Hz
1s digit
%
1s digit
°C
1s digit
°C
1s digit
°C
1s digit
°C
1s digit
°C
1s digit
°C
First decimal
A
10s digit
rpm
1s digit
°C
10s digit
step
Frequency status
0 : Normal
1 : Hold
-
2 : Down
3 : Up_limit
4 : Down_limit
1s digit
°C
Day(One digit)
-
Day(One digit)
-
Day(One digit)
-
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents