Ups Remote Manitoring And Control; Using Serial Port; Serial Communication Port Connection Cable - Tescom DS300T-HF1 Series User Manual

Dsp controlled ups
Table of Contents

Advertisement

IX. UPS REMOTE MONITORING AND CONTROL
Following external connections are available for DS300T-HF1 Series UPSs.
Communication by serial port connection.
Dry contact (interface board) connections.
Remote monitoring panel.
Using one of above communication options is satisfactory for remote monitoring and control in most of the
systems. But in some systems may use 2 or 3 of above options at the same time. In this case accessories
group produced by Tescom may help to make appropriate solutions.

9.1 Using Serial Port

Two serial communication port is included on DS300T-HF1 Series UPS cabinet (com1 and com2). Both of
them may be used for user communication. But in service status duty of com2 port is changed and set as
service port in Options Menu.
All data of UPS can be accessed by this communication way. All the voltage and current values measured
by UPS, alarms, warning and status messages can be monitored.
Because the communication system is designed in an interactive manner, UPS may get commands from
monitoring and control units. These commands are listed below:
• Switch to BYPASS
• Switch to INVERTER
• SOUND on/off
• Adjust UPS time and date
• Quick BATTERY TEST
• BATTERY TEST until battery low alarm
• CANCEL battery test
• Turn off UPS output voltage immediately (SHUTDOWN)
• Turn off UPS output voltage after delay (WAITING SHUTDOWN)
• Turn off UPS output voltage (SHUTDOWN) and turn on UPS output voltage (WAITING RESTART)
• CANCEL SHUTDOWN
• RENAME UPS
These
commands
OPTİONS/COMMUNICATION OPTIONS menu and if user password is sent from this (com2) port.
Otherwise UPS doesn't perform these commands and only information can be obtained from the ports.
Special softwares are required in order to use the serial communication ports. Some of the commands
above have special functions and they can only be activated and used by operating TMON program groups
on a PC that is serially connected to UPS.
TMON program group includes softwares developed by TESCOM.
Additionally, remote monitoring and control is provided in every kind of operating systems, by using
worldwide known and continuously devoloping software programs. These softwares can be supplied from
TESCOM.

9.2 Serial Communication Port Connection Cable

The maximum length for RS232 communication cable should be 25 meters. For remote panel and UPS
connection the same pin configuration is valid. Connection terminals of RS232 cable is shown below for
com1 and com2 ports:
UPS Side
9 Tx
2 Rx
7 Gnd
5 Gnd
6 Rx
3 Tx
are
evaluated
only
Panel Side
if
REMOTE
CNTRL:
54
ON
option
is
selected
in

Advertisement

Table of Contents
loading

Table of Contents