MAIN FEATURES
High efficiency
Ultra compact size
Active PFC for optimal efficiency
Overload 150%
Up to 60°C operating temperature with no
derating
Constant current or Hiccup mode limitation,
user settable
Wide range of output voltage
Easy parallelable for power increase
All models available as version PH
Models with suffix P - internal ORing diode
Models with suffix H - enhanced transient
overvoltage protection (> 6 kV)
READ THIS CAREFULLY BEFORE
INSTALLATION!
Before operating, read this document
thoroughly and retain it for future reference.
Non-respect of these instructions may reduce
performances and safety of the devices and
cause danger for people and property.
The products must be installed, operated,
serviced and maintained by qualified
personnel in compliance with applicable
standards and regulations.
Do not open the device, it does not contain
replaceable components, the tripping of the
internal fuse (if included) is caused by an
internal failure.
Do not repair or modify the device, if
malfunction or failure should occur during
operation, send unit to the factory for
inspection.
No responsibility is assumed by Bel for any
consequences deriving from the use of this
material.
CAUTION
RISK OF BURNS, EXPLOSION, FIRE,
ELECTRICAL SHOCK, PERSONAL INJURY.
Never carry out work on live parts! Danger of
fatal injury!
The product's enclosure may be hot, allow
time for cooling product before touching it.
Do not allow liquids or foreign objects to enter
into the products.
To avoid sparks, do not connect or
disconnect the device before having
previously turned-off input power and wait for
internal capacitors discharge (minimum 1
minute).
LDC480-24
INPUT:
OUTPUT:
LDC480-24P
INPUT:
OUTPUT:
LDC480-24H
INPUT:
OUTPUT:
LDC480-24PH
INPUT:
OUTPUT:
INPUT:
LDC480-36
OUTPUT:
LDC480-36P
INPUT:
OUTPUT:
LDC480-36H
INPUT:
OUTPUT:
LDC480-36PH
INPUT:
OUTPUT:
LDC480-48
INPUT:
OUTPUT:
INPUT:
LDC480-48P
OUTPUT:
LDC480-48H
INPUT:
OUTPUT:
LDC480-48PH
INPUT:
OUTPUT:
INPUT:
LDC480-72
OUTPUT:
LDC480-72P
INPUT:
OUTPUT:
LDC480-72H
INPUT:
OUTPUT:
LDC480-72PH
INPUT:
OUTPUT:
VOR DER INSTALLATION BITTE FOLGENDE
SICHERHEITSHINWEISE BEACHTEN!
Lesen Sie dieses Dokument vor der
Inbetriebnahme sorgfältig durch und bewahren Sie
es zum späteren Nachschlagen auf.
Die Nichtbeachtung dieser Anweisungen kann die
Funktion und Sicherheit der Geräte beeinträchtigen
und birgt Gefahren für Personen und Eigentum.
Die Geräte müssen von qualifiziertem Personal
unter Einhaltung der geltenden Normen und
Vorschriften installiert, betrieben, gewartet und
instand gehalten werden.
Öffnen Sie das Gerät nicht, es enthält keine
austauschbaren Komponenten, das Auslösen der
internen Sicherung (falls vorhanden) ist stets auf
tiefergehende Fehler im Schaltkreis zurück zu
führen.
Reparieren oder modifizieren Sie das Gerät nicht.
Sollte während des Betriebs eine Fehlfunktion oder
ein Defekt auftreten, schicken Sie das Gerät zur
Überprüfung ins Werk.
Bel übernimmt keine Haftung für die Folgen, die
sich aus dem Einsatz dieses Gerätes ergeben.
ACHTUNG
GEFAHR VON VERBRENNUNGEN,
EXPLOSIONEN, FEUER, STROMSCHLAG,
PERSONENSCHÄDEN.
Führen Sie niemals Arbeiten an
spannungsführenden Teilen durch! Gefahr von
tödlichen Verletzungen! Das Gehäuse des Gerätes
kann heiß sein, lassen Sie Zeit zum Abkühlen des
Gerätes, bevor Sie es berühren.
Lassen Sie keine Flüssigkeiten oder Fremdkörper
in die Geräte eindringen.
Um Überschläge zu vermeiden, schließen Sie das
Gerät nicht an oder trennen Sie es nicht ohne
vorher die Eingangsspannung abgeschaltet zu
haben, und warten Sie die Entladung der internen
Kondensatoren ab (mindestens 1 Minute).
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 4.9 – 1.7 A
24 VDC, 20 A
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 4.9 – 1.7 A
24 VDC, 20 A + ORing Circuit
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz or 110 - 345 VDC, 4.9 – 1.7 A
24 VDC, 20 A + Increased surge protection
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz or 110 - 345 VDC, 4.9 – 1.7 A
24 VDC, 20 A + ORing Circuit + Increased surge protection
120 – 240 VAC, 5.5 – 1.9 A, 50 - 60 Hz or 110 - 345 VDC, 5.3 – 1.9 A
36 VDC, 14 A
120 – 240 VAC, 5.5 – 1.9 A, 50 - 60 Hz or 110 - 345 VDC, 5.3 – 1.9 A
36 VDC, 14 A + ORing Circuit
120 – 240 VAC, 5.5 – 1.9 A, 50 - 60 Hz or 110 - 345 VDC, 5.3 – 1.9 A
36 VDC, 14 A + Increased surge protection
120 – 240 VAC, 5.5 – 1.9 A, 50 - 60 Hz or 110 - 345 VDC, 5.3 – 1.9 A
36 VDC, 14 A + ORing Circuit + Increased surge protection
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 4.9 – 1.7 A
48 VDC, 10 A
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 4.9 – 1.7 A
48 VDC, 10 A + ORing Circuit
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz or 110 - 345 VDC, 4.9 – 1.7 A
48 VDC, 10 A + Increased surge protection
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz or 110 - 345 VDC, 4.9 – 1.7 A
48 VDC, 10 A + ORing Circuit + Increased surge protection
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 4.9 – 1.7 A
72 VDC, 6.7 A
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 4.9 – 1.7 A
72 VDC, 6.7 A + ORing Circuit
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz or 110 - 345 VDC, 4.9 – 1.7 A
72 VDC, 6.7 A + Increased surge protection
120 – 240 VAC, 4.8 - 2.4 A, 50 - 60 Hz or 110 - 345 VDC, 4.9 – 1.7 A
72 VDC, 6.7 A + ORing Circuit + Increased surge protection
LEGGERE ATTENTAMENTE PRIMA
DELL'INSTALLAZIONE!
Prima dell'installazione, leggere attentamente
questo documento istruzioni e conservarle per
future consultazioni.
L'inosservanza delle presenti istruzioni può
compromettere le caratteristiche e la
sicurezza dell'apparecchio e causare pericolo
per le persone e le cose.
Il prodotto deve essere installato, utilizzato e
riparato da personale qualificato e nel rispetto
delle normative vigenti.
Non aprire il prodotto, esso non contiene
componenti sostituibili, il guasto del fusibile
interno (se previsto) è causato da un guasto
interno.
Non tentare di riparare o modificare il
prodotto, se durante il funzionamento si
verificano guasti o anomalie, inviarlo al
produttore per il controllo.
Bel non si assume nessuna responsabilità per
qualunque conseguenza derivante dall'uso di
questo materiale.
ATTENZIONE
RISCHIO USTIONI, ESPLOSIONE,
INCENDIO, SCOSSA, LESIONI GRAVI.
Non effettuare mai operazioni sulle parti sotto
tensione! Pericolo di lesioni letali!
Il contenitore può scottare, lasciar quindi
raffreddare il dispositivo prima di toccarlo.
Non far entrare liquidi o oggetti estranei nel
dispositivo.
Per evitare scintille, non collegare o scollegare
l'apparecchiatura prima di avere tolto tensione
di ingresso e prima che sia avvenuta la
scarica dei condensatori interni (min. 1
minuto).
A LIRE ATTENTIVEMENT AVANT
L'INSTALLATION!
Lire ces instructions avant l'installation,
conserver ce manuel pour référence future.
Défaut de se conformer à ces instructions
peut affecter les caractéristiques et la sécurité
du dispositif, et causer du danger aux
personnes ou aux biens.
Les produits doivent être installés, exploités
et entretenus par du personnel qualifié et en
conformité avec les règlements.
N'ouvrez pas le produit, il ne contient aucune
pièce réparable, le déclenchement du fusible
interne (le cas échéant) est causé par un
défaut interne.
Ne pas essayer de réparer ou modifier le
produit ; si des défaillances se produisent
pendant le fonctionnement, retourner le
produit au fabricant pour inspection.
Bel n'assume aucune responsabilité des
conséquences éventuelles découlant de
l'utilisation des produits.
AVVERTISSEMENT
RISQUE DE BRULURES, EXPLOSION,
INCENDIE, ELECTROCUTION, DOMMAGE
AUX PERSONNES.
Ne jamais effectuer des opérations sur les
parties sous tension! Danger de mort!
Le boîtier peut produire des brûlures, le
laisser refroidir avant de toucher l'appareil. Ne
faire pas pénétrer des liquides ou des corps
étrangers dans l'appareil.
Pour éviter des étincelles, ne pas connecter
ou déconnecter l'équipement jusqu'à ce que
la tension d'entrée a été supprimée et avant
qu'il n'ait eut lieu la décharge des
condensateurs internes (minimum 1 minute).

Advertisement

loading

Summary of Contents for BEL LDC480 Series

  • Page 1 Sollte während des Betriebs eine Fehlfunktion oder verificano guasti o anomalie, inviarlo al produit au fabricant pour inspection. No responsibility is assumed by Bel for any ein Defekt auftreten, schicken Sie das Gerät zur produttore per il controllo. Bel n'assume aucune responsabilité des consequences deriving from the use of this Überprüfung ins Werk.
  • Page 2 When a battery is connected in parallel to the Output for backup purposes; the LDC480 must be set on C.C. mode to avoid battery over-charging (see accessory device). Manufacturer Asia-Pacific Europe, Middle East North America Bel Fuse Inc. +86 755 2988 5888 +353 61 49 8941 +1 866 513 2839 300 Executive Drive, Suite 300 belfuse.com/power-solutions West Orange, NJ 07052 © 2023 Bel Fuse Inc. BCM.00407_AG...
  • Page 3 1 & 2 Manufacturer Asia-Pacific Europe, Middle East North America Bel Fuse Inc. +86 755 2988 5888 +353 61 49 8941 +1 866 513 2839 300 Executive Drive, Suite 300 belfuse.com/power-solutions West Orange, NJ 07052 © 2023 Bel Fuse Inc. BCM.00407_AG...
  • Page 4 NOTES: ▪ Data may change without prior notice in order to improve the product. ▪ Please refer to the latest version of LDC480 Series Datasheet LDC480 Series Installation Instruction on our website: belfuse.com/power-solutions ACCESSORIES ▪ LDX-D20 20 A Active ORing controller ▪...

This manual is also suitable for:

Ldc480-24Ldc480-24pLdc480-24hLdc480-24phLdc480-36Ldc480-36p ... Show all