Performance Test ........... 20 1.2.6 Communications Interface ......1 Maintenance ............20 Installation ..............1 Appendix A EL731 Menu Map ........22 2.1 System Wiring ............1 Appendix B System Parameters & Setup Record ..24 2.1.1 Supply Voltage ..........2 Appendix C EL731 Revision History ......
Page 4
Page iii EL731 AC/DC Sensitive Earth-Leakage Relay Rev. 6-F-032816 This page intentionally left blank.
Outline and details for panel-mounting an EL731 are Earth-leakage current is sensed by one or two EFCT- shown in Fig. 1. Insert the EL731 through the cutout and series core-balance zero-sequence current transformers. slip the panel-mount clamp over the EL731 body. Slide...
Figs. 9, 10 and 11 for current-sensor dimensional DHCP. drawings. If the EL731 is being set up for first time, it is Using shielded twisted-pair cable, connect CT2 to recommended to only have one EL731 connected to the terminals 10 and 11 and connect the shield to terminal 9.
Rev. 6-F-032816 To calibrate, connect an EFCT-series current sensor to The CT LED will flash, during the calibration process, the EL731 and ensure that no CT-primary current is which takes about 30 seconds. present. Apply EL731 supply voltage and navigate to...
AND CT2 IS 20 TO 6,000 HZ. USE ONE OR BOTH TRIP INPUTS TO PROVIDE DESIRED FREQUENCY RESPONSE. SEE SECTION 4. ALARM 4. RELAY CONTACTS SHOWN WITH THE EL731 DE-ENERGIZED. EL731 5. ALTERNATE CT LOCATIONS. 6. IF AN EARTH-FAULT OCCURS IN THE RECTIFIER PORTION OF AN ASD, THIS CONTROL SCENARIO MIGHT BE INSUFFICIENT.
Page 7 EL731 AC/DC Sensitive Earth-Leakage Relay Rev. 6-F-032816 INSERT THE EL731 THROUGH THE OPENING OF THE WEATHERPROOF WINDOW. FRONT-PANEL INSERT ASSEMBLY INTO PANEL AND SECURE WITH DETAILS NOT SHOWN. THE PANEL-MOUNT CLAMP . REFER TO SECTION 2 FOR DETAILS.
The ENTER button is used to select menu items and to of full scale (5 A, depending upon the primary turns choose settings. setting) and as a bar graph. All EL731 settings can be accessed using the EL731 menu system or the optional network communications 3.2.1 M ETERING interface.
The Calibrate menu applies to CT1 (0 to 90 Hz). When detected on CT1 or CT2. CT1 is used, the EL731 must be calibrated after installation. Fail-safe or non-fail-safe mode selection is available. See Section 2.2.
Menu: Setup | System Config | Reset Pwd En Used to enable and change the EL731 reset password (four-character numeric field). When enabled, the reset password must be entered to reset the EL731. The default reset password is 1111. 3.2.3.5.3 M...
Page 14 EL731 AC/DC Sensitive Earth-Leakage Relay Rev. 6-F-032816 68.0 68.0 (2.68) (2.68) 17.0 34.0 (0.67) (1.34) M4 OR 8-32 TAP M5 SCREWS MOUNTING DETAIL 25.0 26.5 (0.98) (1.04) E F C T- 2 6 E A R T H FA U LT C T...
The 90 Hz Low Pass filter selection configures the signal, and its magnitude can be accurately measured EL731 to respond to only the low end of its frequency across a wide frequency range. The EL731 can measure range–20 to 90 Hz.
4.2.3 CT2 3 kHz L ILTER The 3 kHz Low Pass filter selection configures the Continuous ....... 25 A Earth-Fault EL731 to respond to the 20 to 3,000 Hz frequency range. Current 1 second ......400 A Earth-Fault Current 4.2.4 CT2 190 Hz H...
Page 17 EL731 AC/DC Sensitive Earth-Leakage Relay Rev. 6-F-032816 Break: Shipping Weight ....... 0.45 kg (1 lb) dc ......... 50 W Resistive, 150 Vdc ac ......... 2,500 VA (PF=1.0) PTC-Thermistor Input: Cold Resistance ....1,500 maximum at 360 VA (PF=0.4) Subject to maximums of 8 A and 250 V 20C (68°F)
0 No 1 Yes 8. W ARRANTY Communications: The EL731 Earth-Leakage Relay is warranted to be free 0 None from defects in material and workmanship for a period of 1 DeviceNet™ 5 years from the date of purchase. 2 Profibus ®...
To clean the EL731, use a micro-fiber cloth to gently remove dust from the surface. If necessary, spray warm b) Verify proper location of the EFCT current sensors. water on the cloth (avoid excessive moisture). Do not Ensure the cables pass through the current-sensor spray liquids directly on the EL731.
Page 21 EL731 AC/DC Sensitive Earth-Leakage Relay Rev. 6-F-032816 TABLE 4. E ARTH- AULT- ECORD a) FOR 6 - 100 mA TRIP LEVEL ESULTS EFCT-X EFCT-X FROM POWER LOAD SOURCE R1 L EL731 L2/N SE-400 NOTE: 1. R1 MUST BE ≥ 10 OHMS...
{CT1 Current in Milliamperes} CT2 Current {CT2 Current in Milliamperes} Full Current {CT1+CT2 Current in Milliamperes} Internal Temp {EL731 Temperature Measurement in Celsius & Fahrenheit } PTC Status {PTC state} RTD Temperature {RTD Temperature in Celsius & Fahrenheit} Exit {Return to Previous Menu} Messages...