Advertisement

Service Literature
The EL072XP (6 ton / 21.1 kW), EL090XP (7.5 ton / 26.4
kW), and EL120XP (10 ton / 35.2 kW) heat pump units
are designed for HFC-410A, light commercial applica-
tions, with a remotely located blower-coil unit or a fur-
nace with an add-on evaporator coil. ELXP model units
are equipped with one dual speed scroll compressor. The
ELXP heat pumps match with the ELXA blower-coil units.
ELXP units are all three-phase.
This manual is divided into sections which discuss the ma-
jor components, refrigerant system, charging procedure,
maintenance and operation sequence.
Information in this manual is intended for qualified service
technicians only. All specifications are subject to change.
Procedures in this manual are presented as recommen-
dations only and do not supersede or replace local or
state codes.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
WARNING
Electric shock hazard! - Disconnect all power
supplies before servicing.
Replace all parts and panels before
operating.
Failure to do so can result in death or
electrical shock.
WARNING
To prevent serious injury or death:
1. Lock-out/tag-out before performing maintenance.
2. If system power is required (e.g., smoke detector
maintenance), disable power to blower, remove fan
belt where applicable, and ensure all controllers
and thermostats are set to the "OFF" position before
performing maintenance.
3. Always keep hands, hair, clothing, jewelry, tools, etc.
away from moving parts.
UNIT INFORMATION
100068
March 25, 2023
ELXP SERIES HEAT PUMP UNITS
Page 1

Table of Contents

Model Identification.........................................................2
Specifications ................................................................3
Unit Plumbing Parts Arrangement .................................5
I-UNIT COMPONENTS ..................................................6
A-Control Box Components ...........................................6
II- REFRIGERANT SYSTEM .........................................8
A- Lineset ......................................................................8
B-Service Valves ...........................................................9
III-START-UP ................................................................10
IV-CHARGING ............................................................. 11
A-Leak Testing ............................................................. 11
B-Evacuating the System ............................................12
C- Refrigerant Charge ..................................................13
V- SEQUENCE OF OPERATION ................................13
VI- MAINTENANCE ......................................................14
TION .............................................................................15
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
ELXP
7.5 & 10 TON

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ELXP Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Allied ELXP Series

  • Page 1: Table Of Contents

    100068 7.5 & 10 TON March 25, 2023 ELXP SERIES HEAT PUMP UNITS The EL072XP (6 ton / 21.1 kW), EL090XP (7.5 ton / 26.4 kW), and EL120XP (10 ton / 35.2 kW) heat pump units are designed for HFC-410A, light commercial applica- tions, with a remotely located blower-coil unit or a fur- nace with an add-on evaporator coil.
  • Page 2: Model Identification

    Model Identification EL 120 X P S S T 1 Y Brand/Family Voltage Y = 208/230V-3 phase-60Hz G = 460V-3 phase-60Hz J = 575V-3 phase-60Hz Nominal Cooling Capacity − Tons 072 = 6 Tons 090 = 7.5 Tons 120 = 10 Tons Minor Design Sequence 1 = 1st Revision Refrigerant Type...
  • Page 3: Specifications

    Specifications General Model No. EL072XPSST EL090XPSST EL120XPSST Data Nominal Tonnage Connections Liquid line - in. (o.d) (sweat) Vapor line - in. (o.d) 1-1/8 1-1/8 1-1/8 Refrigerant Factory Charge R-410A holding charge (2 lbs. per circuit) (R-410A) No. of Circuits Field charge (25 ft. line set) 22 lbs.
  • Page 4 OPTIONS / ACCESSORIE S Item Catalog EL072XPSST EL120XPSST EL090XPSST CABINET Combined Coil/Hail Guards 13T30 13T32 Corrosion Protection Factory CONTROLS 17A08 BACnet Module ® BACnet Sensor with Display 97W23 ® BACnet Sensor without Display 97W24 ® 16F26 Low Ambient Control (0°F) ELECTRICAL 74M70 Service...
  • Page 5: Unit Plumbing Parts Arrangement

    Unit Plumbing Parts Arrangement EL072XP/EL090XP EL120XP Page 5...
  • Page 6: I-Unit Components

    NOTE – 208 volt units are field wired with the red wire WARNING connected to control transformer. 230 volt units are factory wired with the orange wire connected to control transform- Electrostatic discharge can affect er primary. electronic components. Take care 2 - Condenser Fan Capacitors C1 and C2 during unit installation and service to protect the unit’s electronic controls.
  • Page 7 NOTE – Defrost control part number is listed near the P1 PRESSURE SWITCH CIRCUITS timing pins. Units with defrost control 100269-07 have a The defrost control includes two pressure switch circuits. factory default setting of 90 minutes. The factory-installed high pressure switch (S4) wires are connected to the board’s HI PS terminals (figure 3).
  • Page 8: Ii- Refrigerant System

    1 - Compressor 2 - Two Stage Compressor Solenoid (L34) Resistance Check All units use scroll compressors. Resistance check: Measure the resistance from the end Compressor consists of two involute spiral scrolls matched of one molded plug lead to either of the two female con- together to generate a series of crescent shaped gas nectors in the plug.
  • Page 9: B-Service Valves

    Refer to table 2 for field-fabricated refrigerant line sizes for Manifold gauge sets used with HFC-410A refrigerant sys- runs up to 50 linear feet (15 m). tems must be capable of handling the higher system oper- ating pressures. The gauges should be rated for use with TABLE 2.
  • Page 10: Iii-Start-Up

    Service (Ball) Valve 3 - When testing is completed, replace service port cap and tighten as follows: Some units are equipped with a full service ball valve, as shown in figure 8. One service port that contains a valve • With Torque Wrench: Finger tighten and then tight- core is present in this valve.
  • Page 11: Iv-Charging

    IMPORTANT WARNING If unit is equipped with a crankcase heater and the Fire, Explosion and Personal Safety hazard. outdoor ambient air is 50ºF (10ºC) or below, it should Failure to follow this warning could result in be energized 24 hours before unit start-up to prevent damage, personal injury or death.
  • Page 12: B-Evacuating The System

    MANIFOLD Connect an HFC-410A manifold gauge set high pressure hose to the GAUGE SET suction valve service port. With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. After the line set has been connected to both the indoor and outdoor units, check the line set connections and indoor unit for leaks.
  • Page 13: C- Refrigerant Charge

    NOTE - Remove cores from service valves if not already done. MANIFOLD GAUGE SET MICRON GAUGE A34000 1/4 SAE TEE WITH SWIVEL COUPLER TO LIQUID LINE SERVICE VALVE OUTDOOR UNIT TO SUCTION SERVICE VALVE RECOMMEND MINIMUM 3/8” HOSE Connect low side of manifold gauge set with 1/4 SAE in-line tee to suction line service valve Connect high side of manifold gauge set to liquid line service valve Connect micron gauge available connector on the 1/4 SAE in-line tee.
  • Page 14: Vi- Maintenance

    DEFROST MODE (occurs during Heating Call) OUTDOOR UNIT Defrost Initiation 1 - Clean and inspect the condensor coil (may be flushed with a water hose). Ensure power is off During heating operation, if outdoor coil temperature falls before cleaning. below S6, S9 (120 only) defrost switch setpoint, the de- frost thermostat closes.
  • Page 15: Vii- Wiring Diagram And Sequence Of Operation

    VII- WIRING DIAGRAM AND SEQUENCE OF OPERATION Page 15...

This manual is also suitable for:

El072xpEl090xpEl120xpEl072xpsstEl090xpsstEl120xpsst

Table of Contents