Installation Configurations
To suit a variety of applications, the hydronic air handler ) is approved for upflow,
downflow and horizontal configurations.
•
The hydronic air handler is for indoor installations only
•
Ensure that electrical components are protected from any contact with water
•
Unit(s) shall not be installed directly on any combustible material other than wood
flooring
•
The hydronic air handler is designed to be used with an air distribution system
(ductwork)
•
Access around the product should be adequate to provide access for servicing
•
The hydronic air handler units are designed to be installed vertically or horizontally on
the floor, units may also be hung from ceiling or a wall. As packaged, the hydronic air
handler is pre-configured for bottom return air inlet application.
SERVICING
24" (610 mm)
12
Minimum Clearance to Combustibles
TOP/PLENUM
zero
SIDE
zero
FRONT
zero
Rinnai Corporation Hydronic Air Handler 101 Training Manual
BACK
zero
SIDE
zero
BOTTOM
zero