Summary of Contents for airinspace Wall-i Pilot

  • Page 1 Intelligent electronic pressure control and management system USER MANUAL EMC European Directive 2014/30/EU...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS SECTION 1 - General information Safety instructions Regulatory standard Normative standards Classification Description of the device 1.5.1 Overview 1.5.1.1 Wall-i PILOT 1.5.1.2 Sensor Box 1.5.2 Markings and Warnings Functional description of the device 1.6.1 Intended use 1.6.2 Physical characteristics Packaging –...
  • Page 3: Section 1 - General Information

    Option: Particle Counter – CP31101 Note: The user manual is available on the USB key supplied with the administrative documents or ® by airinspace personnel if they are in charge of putting the device into service. English (United Kingdom)_Notice d'utilisationCP31000_Wall-i PILOT_ed01_22-janvier-2021...
  • Page 4: Safety Instructions

    IMPORTANT: BEFORE CARRYING OUT ANY WORK ON AN ELECTRICAL COMPONENT, SWITCH OFF THE EQUIPMENT BY DISCONNECTING THE VCC POWER CONNECTOR airinspace ® ORK ON ELECTRICAL CIRCUIT COMPONENTS IS STRICTLY RESERVED FOR MAINTENANCE STAFF OR DULY TRAINED PERSONNEL English (United Kingdom)_Notice d'utilisationCP31000_Wall-i PILOT_ed01_22-janvier-2021...
  • Page 5: Regulatory Standard

    REGULATORY STANDARD Wall-i Pilot is CE-marked under European regulations: European Electromagnetic Compatibility Directive 2014/30/EU NORMATIVE STANDARDS EN 61326-1 (2013). Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements EN 61000-3-2 (2006 + A1(2009) + A2(2009): Electromagnetic compatibility (EMC) - Part 3- 2: limits - Limits for harmonic current emissions (equipment input current ≤...
  • Page 6: Description Of The Device

    DESCRIPTION OF THE DEVICE 1.5.1 OVERVIEW 1.5.1.1 Wall-i PILOT 1 7-inch screen 2 USB Data logger connector 3 Air decontamination unit system RJ45 connector 4 Sensor box RJ45 connector 5 ModBUS RJ45 connector (HVAC) 6 100-240VCC power connector 7 Control card...
  • Page 7: 1.5.1.2 Sensor Box

    1.5.1.2 Sensor Box Internal pressure tap Wall-i Pilot RJ45 connector Particle counter connector (optional) Pressure transducer Temperature and relative humidity sensor 1.5.2 MARKINGS AND WARNINGS Label Description Position Product On the left side of the box Electrical characteristics At the bottom of the box Electrical characteristics At the bottom of the box...
  • Page 8: Functional Description Of The Device

    < 0.05 mg/m Note: The information contained in this table is for information only. For any information on ® measurements and tolerance intervals, please contact airinspace at the address provided at the end of this document. English (United Kingdom)_Notice d'utilisationCP31000_Wall-i PILOT_ed01_22-janvier-2021...
  • Page 9: Packaging - Acceptance

    PACKAGING – ACCEPTANCE Wall-i Pilot is supplied and installed with a sensor box. Carefully examine the equipment delivered when installing the components. In the event of any anomaly, please contact the manufacturer or distributor, providing the serial number and date of purchase TRANSPORT Before transporting, protect the unit from shocks and scratches, keep and use the original packaging.
  • Page 10: Section 2 - Installation

    SECTION 2 - INSTALLATION ASSEMBLY Assembly of the Wall-i Pilot connected to the sensor box and the air decontamination unit. Wall-i Pilot can be mounted flush with the wall (1) or directly to the wall (2). sensor box is designed to be wall-mounted. Follow the same assembly steps for the Wall-i Pilot if you wish to mount it directly to the wall.
  • Page 11 Using a hammer, insert the two plugs and then tighten the screws, leaving them a few millimetres overhanging. Example of Wall-i Pilot assembly flush with the sensor box: On the sensor box, position the flexible tube on the positive pressure tap , the sensor will automatically detect positive pressure (prevents the spread of incoming contamination) or negative pressure (prevents the spread of outgoing contamination).
  • Page 12 ® Example of assembly with the nozzle under positive pressure: Wall-i Pilot, sensor box airinspace air decontamination unit ® Electrically connect airinspace air decontamination unit to the Wall-i Pilot using a straight RJ45 cable. Position the straight RJ45 cable on the RJ45 connector marked as Air decontamination unit.
  • Page 13 Power the Wall-i Pilot with 100-240Vcc using a live earth neutral power supply terminal block. Connection colour code: Earth (E) Yellow/Green Neutral (N) Blue Live (L) Brown and others Electrically connect the sensor box to the Wall-i Pilot using a straight RJ45 cable. Position the straight RJ45 cable on the RJ45 connector , marked as Sensor box.
  • Page 14: Disposal

    DISPOSAL This product is covered by European Directive 2012/19/EU of 04 July 2012 on waste electrical and electronic equipment (WEEE) and falls within category 6 “Electrical and electronic tools (with the exception of large-scale stationary industrial tools)” as defined in Appendix I to this directive. Disposal of this product and the recovery of the resultant waste must respect regulations arising from the application of the European directive by the different member states, as well as any local regulations that complement it.
  • Page 15: Use Of User Interface

    USE OF USER INTERFACE Wall-i Pilot is equipped with a simple, user-friendly interface. The user interface consists of a 7-inch colour touchscreen. Light signals Green: the pressure is consistent with the setpoint (+/-1 Pa). Orange: the pressure is different from the setpoint (+/-1Pa), the PLC regulates the ventilation setpoint to return to the pressure setpoint.
  • Page 16: Start-Up/Shutdown

    Wall-i Pilot via a straight RJ45 cable. ® Check the electrical connection of the airinspace air decontamination unit to the Wall-i Pilot via a straight RJ45 cable. (See Section 2 Installation Assembly) ® Check the electrical connection of the airinspace air decontamination unit to the ~ 230 V;...
  • Page 17: Settings Display

    SETTINGS DISPLAY The room’s regulation settings are displayed from the maintenance screen by pressing the maintenance button The maintenance screen displays: The pressure setpoint Alarm delay (factory setting 2 min, maximum value 10 min). Low pressure alarm threshold (factory setting 10Pa) High pressure alarm threshold (factory setting 20Pa) Flow alarm threshold (factory setting 300m Flow warning threshold...
  • Page 18: Changing The Settings

    CHANGING THE SETTINGS The configuration menu can be accessed by pressing the maintenance button from the main screen, then the Password button Access to this menu is protected by a definable User password, by default 1234. Note: don't forget to confirm password entry by pressing ENTER. The modification screen appears, making it possible to change the following variables: Language: Choice of language Settings: Access settings...
  • Page 19: Pressure And Flow Alarm Thresholds

    2.6.1 PRESSURE AND FLOW ALARM THRESHOLDS Pressure and alarm setpoints can be accessed by pressing the settings button of the configuration menu. This screen allows you to view and change the following variables: Pressure setpoint Pressure alarm delay (factory setting 2 min, maximum value 10 min). Low pressure alarm threshold (factory setting 10Pa) High pressure alarm threshold (factory setting 20Pa) Flow alarm threshold (factory setting 300m...
  • Page 20: Pressure Regulation Settings

    2.6.3 AIR DECONTAMINATION UNIT VARIABLES ® In settings , this page allows you to view and change the following airinspace air decontamination unit variables: o Fan setpoint (display only) o Air decontamination unit’s filter pressure (display only) o Sensors (door, filters, pre-filter)
  • Page 21: Software Update, Date, Hour And Minute

    The settings are as follows: Current setpoint Current copy (display) Voltage feedback (display) Current warning threshold Current stop threshold Max current threshold Voltage warning threshold Voltage stop threshold Threshold test delay 2.6.4 SOFTWARE UPDATE, DATE, HOUR AND MINUTE In settings , this page allows you to: View the software version of the Wall-i...
  • Page 22: Adjusting The Temperature, Humidity And Pressure Correction Settings

    Set the transmission speed View the number of data bits Set parity View the number of stop bits Set the unit address 2.6.6 ADJUSTING THE TEMPERATURE, HUMIDITY AND PRESSURE CORRECTION SETTINGS In settings , this page allows you to apply a correction to the temperature, humidity and pressure values.
  • Page 23: Handling Warnings And Alarms

    HANDLING WARNINGS AND ALARMS 2.7.1 DEFINITIONS Warning: a warning message is sent by the management card when a fault, temporary or otherwise, ➢ leads or may lead to a deterioration in the equipment’s nominal operation conditions, without however diminishing its performance significantly. Therefore, the warning helps point out that a maintenance operation is required.
  • Page 24: List Of Alarms And How To Handle Them

    Make sure the transfer filters are in place and check their assembly (no leak) The alarms are auto-reset, which means that there is no need to validate or acknowledge a fault to reset it. ® AIRINSPACE SHALL NOT BE HELD LIABLE FOR THE USE OF FILTERS DIFFERENT FROM THOSE SUPPLIED WITH THE EQUIPMENT...
  • Page 25: Alarm And Warning Log Display

    2.7.4 ALARM AND WARNING LOG DISPLAY In alarm the alert log display is accessible by pressing the alarm and warning log button. Press the icon to save the alarm and warning log to a USB key. Press the button to return to the main screen. English (United Kingdom)_Notice d'utilisationCP31000_Wall-i PILOT_ed01_22-janvier-2021 p.
  • Page 26: Frequency Records Display

    FREQUENCY RECORDS DISPLAY In settings the frequency records of the Wall-i Pilot are displayed from the records screen by pressing the records button Press the icon to save the records log to a USB key. Press the button to return to the main menu. English (United Kingdom)_Notice d'utilisationCP31000_Wall-i PILOT_ed01_22-janvier-2021 p.
  • Page 27: Section 3 - Regulation Operation

    SECTION 3 - REGULATION OPERATION FUNCTIONAL DESCRIPTION The operator defines a configurable pressure setpoint. The default value is +15 Pa. Wall-i Pilot controller constantly manages the fan of the air decontamination machine to reach and then maintain a pressure measurement close to the pressure setpoint. Ouverture porte Fermeture porte Opening door...
  • Page 28: Setting An Alarm To A Pressure Value

    SETTING AN ALARM TO A PRESSURE VALUE An alarm on a pressure value can be configured by the user. This alarm is configurable via three settings: - Low pressure alarm threshold - High pressure alarm threshold - Pressure alarm delay If the pressure measured is outside the range defined by “Low pressure alarm threshold”...
  • Page 29: Section 4 - Modbus

    SECTION 4 - MODBUS Wall-i Pilot controller can be connected to a supervision unit via a serial ModBUS link (RJ45 connector) The following exchange table lists the register addresses used: Paramètres Modbus liaison série: 19200 bauds, 8 data bit, parity Even, 1 stop bit Endianness: big-endian (octet de poids fort en premier) Codage: RTU Mode: esclave...
  • Page 30 English (United Kingdom)_Notice d'utilisationCP31000_Wall-i PILOT_ed01_22-janvier-2021 p. 30/32...
  • Page 31 English (United Kingdom)_Notice d'utilisationCP31000_Wall-i PILOT_ed01_22-janvier-2021 p. 31/32...
  • Page 32: Section 5 - Servicing- Maintenance

    MODEL IDENTIFICATION ® or a dealer, please provide the product’s serial number and date of When contacting airinspace purchase. The serial number features on the product label. WARRANTY Contact your local airinspace®...