Floodlight Range Installation Guide
Zone 1 variant CML13ATEX3007 or IEC Ex CML14.0001 or CML 21UKEX3099
Zone 2 variant CML17ATEX4231 or IEC Ex CML 17.0135 or CML 21UKEX4106
This installation guide provides instructions for installing the RF series of
explosion protected floodlights.
Text in Bold is specific for emergency variants
Overview
Important information
The RF series of explosion protected floodlights are specialist devices, certified for use
in specific operating environments.
The units must be installed in accordance with these instructions, must be correctly
certified for the specific operating environment and must be installed by suitably
qualified personnel.
Emergency floodlights will require the fuse to be reconnected upon installation
and the floodlight subjected to three 24 hour charge/discharge cycles to bring
the battery up to peak capacity.
If you have any queries about the installation or the certification of the unit – please
contact Nemalux for immediate assistance and advice.
MADE IN UK
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
1
Safety Instructions
2
Installation
3
Maintenance
4
Technical Specification
5
Trouble Shooting
SUBJECT TO CHANGE WITHOUT NOTICE
RF Series
rev. A-21
1-12

Advertisement

Table of Contents
loading

Summary of Contents for Nemalux RF Series

  • Page 1 Technical Specification Trouble Shooting Important information The RF series of explosion protected floodlights are specialist devices, certified for use in specific operating environments. The units must be installed in accordance with these instructions, must be correctly certified for the specific operating environment and must be installed by suitably qualified personnel.
  • Page 2: Safety Instructions

    Nemalux document 0010-D-00001 Battery Handling Guide 1.5m Install in a well Do not continually Isolate mains before ventilated area stare at lamp removing cover 2-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 3: Installation

    Mounting RF Unit 1. To meet the requirements of certification a MINIMUM of 2 fixing points must be used, the fixing points must be suitable for the conditions of use. Nemalux recommend using M8 Marine Grade A4 Stainless Steel fixings (not supplied)
  • Page 4 4Nm. The unit can be mounted horizontally or vertically allowing the unit to point up/down or left/right. 4-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 5 Typical wiring diagram – standard luminaires WHITE/RED WHITE/RED Typical wiring diagram – emergency luminaires WHITE/RED WHITE/RED 5-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 6 Live and Neutral together and test between this point and Earth to prevent the risk of damage to the electronic control gear. 6-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 7: Maintenance

    Fitting a new power supply is a reversal of the above procedure. 5. Disposal of packaging, RF unit and old LED assemblies should be carried out in accordance with national regulations. 7-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 8: Technical Specification

    IIIC T82°C Db 110V- V AC or 18-48V AC/18-69V DC IP66 & IP67 Ta = -52°C to +55°C 110V- AC or 18-48V AC/18-69V DC 8-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 9: Troubleshooting

    LED cables to opposite power supply to help identify problem. Max number of fittings allowed per MCB (Based on 230V) MCB Type Rating RF-8 RF-17 9-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 10 & UK Directive SI 2016 No. 1107 (as amended) The RF series luminaire is manufactured by Raytec Ltd. for Nemalux Inc. Raytec Ltd. declares under our sole responsibility that the product(s) listed below conform with the relevant provisions of directive 2014/34/EU of 20th April 2016 and UK Directive SI 2016 No.
  • Page 11 EN 60079-1 : 2014 And also 2014/35/EU - Low Voltage Directive, 2014/30/EU - EMC Directive Signed Name Barry Thompson Position Director Dated Serial number 11-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...
  • Page 12 1018 - 72nd Ave NE | Calgary, AB, Canada T2E 8V9 Toll Free: 1-877-NEMALUX / 1-877-636-2589 P: 1.403.242.7475 F: F: 1.403.243.6190 E: info@nemalux.com W: www.nemalux.com 12-12 MADE IN UK www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 SUBJECT TO CHANGE WITHOUT NOTICE...

This manual is also suitable for:

Cml13atex3007Cml17atex4231

Table of Contents