Cassette Grille Installation; Test Run; Test Run Using Outdoor Unit (Pcb); Test Run Using Remote Controller - Fujitsu AIRSTAGE AUXD18GALH Installation Manual

Indoor unit cassette type
Hide thumbs Also See for AIRSTAGE AUXD18GALH:
Table of Contents

Advertisement

• Setting details
Function number
01
Indoor unit address
02
Refrigeration address
For use with a remote controller, set all rotary switches to 0, and refer to "7.1. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
(Example) Function : 31, Setting number : 2
OPERATION
ON
indicator lamp
0.5s
0.5s
(Green)
OFF
ON
TIMER
indicator lamp
0.5s 0.5s
(Orange)
OFF
ON
FILTER
0.5s
0.5s
indicator lamp
(Red)
OFF
En-15
Item
Setting number
00 to 63
00 to 99
Indication pattern
Function number; tens place
(0.5s ON/0.5s OFF)
Function number; ones place
(0.5s ON/0.5s OFF)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
1 cycle 12 sec
0.5s
0.5s 0.5s 0.5s
9 sec
11 sec
10 sec
0.5s
0.5s

8. CASSETTE GRILLE INSTALLATION

• Operate according to the installation Manual CASSETTE GRILLE.
• Be sure to confi rm there is no gap between the cassette grille and main unit after
installing the CASSETTE GRILLE.

9. TEST RUN

9.1. Test run using Outdoor unit (PCB)

• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.

9.2. Test run using Remote Controller

• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicators
fl ash slowly at the same time.

10. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s).
After installation is complete, be sure to check the following check items again.
CHECK ITEMS
Has the indoor unit been installed
correctly?
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been
completed?
Does water drain easily from the indoor
units?
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)?
Is the connection cable the specified
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner
operation by remote control unit or
external device?
After installation is completed, has the
proper operation and handling been
explained to the user?
If not performed correctly
Vibration, noise, indoor unit may
drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn
damage
No operation, heat or burn
damage
Short circuit
No operation, heat or burn
damage
No cooling, No heating
No operation
CHECK
BOX