Read Configuration; Fail-Safe; Configure Analog Outputs Range; Multipurpose Command - Macurco RD-24 Installation & Operation Manual

Modbus remote driver
Table of Contents

Advertisement

TM
Macurco
Macurco RD-24 Manual

6.1 Read Configuration

Device configuration is indicated by 2 bytes.
bit
bit
bit
bit
15
14
13
12
Module # 4
0000 = relays
0001 = analog outputs
0010 = analog inputs
0011 to 1110 - future
1111 = No exp. board

6.2 Fail-safe

Device fail safe configuration uses 4 bytes.
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4
Fail safe timer value 30 to 3600 (seconds)
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4
Analog Output value when in fail safe condition: (mA x 100)

6.3 Configure Analog Outputs Range

Expansion Board #4
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8
DAC2
DAC1
x
rng
x
rng
rng: '0' – 4 to 20 mA (2 to 10V), '1' 0 to 20mA (0 to 10V)

6.4 Multipurpose command

Multipurpose command uses 2 bytes, and can be used on the following situations:
Control all relays of a remote driver (RD-24) device.
Control all analog outputs of remote drivers with same value.
Control remote drivers with analog outputs and relays with same output values for relays and same output
values for analog outputs.
Command to prevent a failsafe timeout when there is no change in the state of the outputs.
REV – 1.0.0
bit
bit
bit9 bit8
11
10
Module #3
0000 = relays
0000 = relays
0001 = analog outputs
0001 = analog outputs
0010 = analog inputs
0010 = analog inputs
0011 to 1110 - future
0011 to 1110 - future
1111 = No exp. board
1111 = No exp. board
0 = 0mA
2000 = 20.00mA
Expansion Board #3
DAC2
DAC1
x
rng
x
rng
[34-8708-4770-1]
bit
bit6 bit5 bit4
7
Module #2
0=OFF
Expansion Board #2
bit7
bit6 bit5 bit4
DAC2
DAC1
x
rng
x
rng
bit
bit2 bit1 bit0
3
Module #1
0000 = relays
0001 = analog outputs
0010 = analog inputs
0011 to 1110 - future
1111 = No exp. board
bit3
bit2
bit1 bit0
state
Active
x
x
0=NO
1=ON
1=YES
bit3
bit2
bit1 bit0
x
x
x
x
Expansion Board #1
bit3
bit2 bit1 bit0
DAC2
DAC1
x
rng
x
rng
17 |
P a g e

Advertisement

Table of Contents
loading

Related Products for Macurco RD-24

Table of Contents