Operating Instructions
PSF-EX approval according to
Directive 2014/34/EU (ATEX)
Version 26/07/2023
Art. No.: 8035498
©2023 PS Automation GmbH
The operating instructions in other languages can be found at the following QR codes:
Please note to scan the QR codes within an Ex-atmosphere only with a suitable end device!
French
Italian
German
Or follow the Link:
www.ps-automation.com/downloads
Subject to change!

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSF-EX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for PS Automation PSF-EX

  • Page 1 Operating Instructions PSF-EX approval according to Directive 2014/34/EU (ATEX) Version 26/07/2023 Art. No.: 8035498 ©2023 PS Automation GmbH The operating instructions in other languages can be found at the following QR codes: Please note to scan the QR codes within an Ex-atmosphere only with a suitable end device!
  • Page 2: Table Of Contents

    Content 1. Product description ............................... 3 2. Applicable standards ..............................3 3. Key figures ..................................4 3.1 Type code ................................5 4. Symbols used and safety ............................... 5 5. Intended use ................................. 6 5.1 Special conditions ..............................7 6. Storage ..................................7 7.
  • Page 3: Product Description

    Conduit entries are available in the lower section of the housing for inserting the electrical cables. The construction, as well as the interaction of the individual components and the housing regarding their suitability for use in hazardous areas, are tested by PS Automation GmbH and confirmed by the identification with the type label.
  • Page 4: Key Figures

    3. Key figures Device category II 2GD EU Type Examination Certificate TPS 22 ATEX 110398 0002 X Ex marking Ex db eb IIC T6 Gb Ex db eb IIC T4 Gb or rather Ex tb IIIC T80 °C Db Ex tb IIIC T100 °C Db Size (electrical section) approx.
  • Page 5: Type Code

    General dangers in case of non-observance of the safety instructions The PSF-Ex actuators are built according to the latest state of the art and are operationally safe. Nevertheless, hazards can arise from the actuators if they are not used by trained or at least instructed personnel and/or are used improperly or for purposes other than those for which they are intended.
  • Page 6: Intended Use

    5. Intended use  The type PSF-EX actuator is a fixed installed device for use in Ex zone 1, 2, 21 or 22. The type PSF-EX actuator is not suitable for use in Zone 0 and Zone 20.
  • Page 7: Special Conditions

     Assembly/disassembly, operating and maintenance work may only be carried out by suitable skilled personnel familiar with the work. All generally applicable legal regulations and other binding guidelines for work safety, accident prevention and environmental protection must be complied with. ...
  • Page 8 Installation  The conductor must be connected carefully at the terminal points so that the individual wires are not damaged. The maximum connection data on the type plate and the applicable documents must be taken into consideration.  The device must be integrated into a suitable earthing or equipotential bonding system before commissioning, a connection part (4 mm²) is available for this purpose on the underside of the actuator.
  • Page 9: Manual Override And Setting Of The Dip Switches

    8. Manual override and setting of the DIP switches 8.1 Setting the actuators during commissioning (hood open) When commissioning the actuators, the hood must be opened. The hood may only be opened in non-hazardous areas and only in a dry environment (see chapter 10 for instructions). To actuate the actuator during setting work (valve assembly and end position setting), an electrical manual override by means of a push button is available (for operation, see chapter 12.3).
  • Page 10: Setting The Actuators During Operation (Hood Closed)

    8.2 Setting the actuators during operation (hood closed) To actuate the actuator during setting work in potentially explosive atmospheres (end position setting), an electrical manual override by means of a push button is provided in the hood (for conditions see chapter 12.3). To reach the manual override, the screw plugs must be opened.
  • Page 11: Valve Mounting

    9. Valve mounting Spring-loaded clamp with coupling pin Pillar Coupling Locking nut Valve stem 1 mm Bracket Pillar nut Figure 5: Valve mounting 9.1 Spring Extend (SE) valve mounting Starting position: Valve stem retracted 1. Fit the drive onto the bracket. 2.
  • Page 12: Opening And Closing The Hood

    10. Opening and closing the hood The hood may only be opened in non-hazardous areas and only in a dry environment. Take appropriate ESD handling precautions before opening the housing:  Earth the actuator.  Touch earthed housing parts before opening the hood. Opening: Hexagon socket screw...
  • Page 13: Electric Supply

    Unused entries must be closed by suitable blanking elements. As the PSF-Ex electrical actuators do not have an internal electrical disconnect device available, a switch or circuit breaker must be provided in the building installation. This must be located in the vicinity of the device, easily accessible to the operator and must be identified as a disconnect device for the device.
  • Page 14: Connection Diagram

    11.2 Connection diagram Figure 7 shows the electrical connection for standard drives. The wiring diagram in the actuator is binding for the connection. For the connection of optional accessories, please refer to the respective operating instructions. Figure 7: Electrical connection Figure 8: Connection for potential equalisation The protective earth line is connected at the point marked on the actuator.
  • Page 15: Display And Functions

    12. Display and functions 12.1 DIP switches Function Signal Set value Position feedback Voltage Current function Control via set value Control via binary inputs Extend valve stem with increasing set value Retract valve stem with increasing set value Closing with force / opening with force Closing with force / opening with stroke Closing with force / opening with 20 mm stroke...
  • Page 16: Operating Direction

    12.2 Operating direction SE = Spring Extend: Actuator stem extends, valve stem retracts SR = Spring Retract: Actuator stem retracts, valve stem extends SE = Spring Extend: Actuator stem extends, valve stem retracts SR = Spring Retract: Actuator stem retracts, valve stem extends Figure 9: Operating direction 12.3 Operating buttons Function...
  • Page 17: Status Display

    12.4 Status display Green LED Red LED Actuator not calibrated Flashes rapidly Normal operation / actuator moves Normal operation / actuator stationary Manual mode active Flashes alternately Flashes alternately Manual mode: Valve stem is Flashes extended Manual mode: Valve stem is Flashes retracted Automatic commissioning running...
  • Page 18: Manual Commissioning (See Also Chapter 12.3)

    12.6 Manual commissioning (see also chapter 12.3)  Check that the gland between the valve and the actuator is secure.  To activate the individual calibration, press button B1 > at least 7 seconds.  The actuator can be moved manually with buttons B1 and B2 until the desired open-end position of the valve is reached.
  • Page 19: Operation

    13. Operation The operator of an electrical system in a potentially explosive environment must keep the equipment in proper condition, operate it properly, monitor it and carry out maintenance and repair work. See also IEC/EN 60079- 17/IEC/EN 60079-19. During operation, all internal parameters, such as the required motor torque and the current position, as well as the operating states of the actuator are continuously monitored.
  • Page 20: Valve Curve

    13.2 Valve curve Switch position S2-10 can be used to select the relationship between the set value and the actuator position. Two curves are available. With the linear valve curve, the actuator position in % corresponds to the set value in %. The "Quick Opening Curve"...
  • Page 21: Maintenance And Servicing

    15. Maintenance and servicing The actuators are maintenance-free under the operating conditions specified in the data sheet. The gearboxes are lubricated for life and do not require relubrication. Attention! During maintenance and servicing, the actuator must not be operated electrically. Personnel carrying out work and maintenance and servicing must be skilled and familiar with the work.
  • Page 22: Annex

    17. Annex 17.1 Accessories Optional accessories are available for the actuators. Technical data can be found in the corresponding data sheets.
  • Page 23: Original Declaration Of Incorporation For Incomplete Machines And Eu Declaration Of Conformity

    17.2 Original declaration of incorporation for incomplete machines and EU declaration of conformity...