Operating Instructions Battery-powered signal converter for magnetic-inductive flow meters model FLC-406 Battery-powered signal converter FLC-406...
In order to avoid possible accidents to 1.6 Product identification persons or things caused by incorrect interpretation Each FLC-406 converter supplied by Euromisure has an of the instructions, the user must not proceed with adhesive product lable, on which the following information operations and/or interventions on the converter if there are reported.
MID certification. 2.2 Coupling The maximum diameter of the sensor that can be paired with the FLC-406 is 600 mm. Backup battery life is affected by the 2.6 Battery size of the sensor. The flow meter can be ordered both...
Push buttons 1-4 Sensor coils Status LED Positive pulse output Cable glands for pulse and other I/O Negative pulse output SIM gate Grounding connection Battery pack connection LED Power indicator 12/24 V input WIKA Operating Instructions - Battery-powered signal converter FLC-406...
P2 selects the next value in the sequence: year> month> day> hour> minute. After selecting the last value, a further press of P2 confirms the value and go to the next screen. P1 confirms the current settings and exits. WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Page 8
- Function selection code: each value corresponds to a menu or a parameter set function (see Par. 3.7 'Functions'). For selecting the function code use P4/P3; use P2 to enter the selected code. Pressing P1 returns to the main screen. WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Some basic information on cellular activity is shown directly Within a specific function, the functionality of the buttons may on the FLC-406 display. See the following details: be different; in this example, P4/P3 increases and decreases the value of the parameter shown on the first line, P2 confirms the value and returns when the function is selected.
The previous measurement screen will be restored at the end sequence. In addition the version and revision, bootloader of this operation. WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Number of samples screen return to value averaged. function selection Bypass Back to main Confirm + Decrease Increase value Bypass filter threshold, % screen return to value of full scale. function selection WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Page 12
Save user Back to main Return to Decrease (Long press) Save the instrument parameters screen function value save user parameters as a user selection parameters copy. WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Page 13
4: On every 5 min; 5: On every 10 min; 6: On every 15 min; 7: On every 30 min; 8: On every 60 min; 9: Always on (Enabled only with Bluetooth-Modbus card). WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Page 14
Back to main Return to Decrease Increase value MODBUS byte order byte-order screen function value selection 0: little endian 1: big endian 2: little endian byte swap. ■ = editable ■ = read only WIKA Operating Instructions - Battery-powered signal converter FLC-406...
(feature 33 10% or less in the previous table) can shorten the expected battery life. Expected battery life (years) according to sensor diameter and sampling rate WIKA Operating Instructions - Battery-powered signal converter FLC-406...
5. Auto diagnostics 5. Auto diagnostics During the measurement process, the FLC-406 detects automatically if error condition occurs and possibly stops the operation by reporting an alarm indication on the display. The following table describes the various conditions of alarm and converter behavior.
Main Dashboard - real live values and basic information Data LOG - Internal process log download and CSV file export Graphic - Recording of live measurements/Visualization Configuration - Parameters setting & configuration WIKA Operating Instructions - Battery-powered signal converter FLC-406...
35 or by pressing P1 and P3 together on the main display screen. Each log information scrolls automatically in 4 screens. P3 and P4 can be pressed at any time to go to the previous or next saved recording. WIKA Operating Instructions - Battery-powered signal converter FLC-406...
EEPROM memory are protected from writing attempts. and / or totalizers) 7. GSM The GSM module is an expansion of the FLC-406 electronic 7.1.5 Data transmission interval converter, which makes possible: The programmable data transmission interval is independent Remote transmission of information available in the for each mode.
NOTE Without this operation, no data on the form will change. 7.4 Phone number and email settings Up to 5 mobile numbers / email addresses can be set. WIKA Operating Instructions - Battery-powered signal converter FLC-406...
NOTE Without this operation, no data on the settings will change. 7.7 Test Press the button to test all the functions of the GSM module. Data site connection test SMS send test WIKA Operating Instructions - Battery-powered signal converter FLC-406...
8. 4-20ma output module 8. 4-20 mA output module The 4-20 mA output module is an expansion of the FLC-406 It is possible to map on this output: electronic converter, which makes it possible to transmit Instant flow rate; ■...
Bluetooth is managed with the User Interface software, FLC-406 in order to search for a possible connection request selecting Bluetooth instead of IrCOMM according to the from a PC. The periodicity of the ignition can be set from...
Page 24
Click on Imp. Default to set the device to connect at ■ startup. Click on Remove to remove it from the list. ■ The next time you start, you can connect directly to the last WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Observe the orientation of the package as shown (see the coating), grounding rings are required. Missing or incorrect image below). At this point the allowed parameters can be grounding will result in unpredictable behavior. viewed and adjusted. Compact configuration WIKA Operating Instructions - Battery-powered signal converter FLC-406...
Please compact version. note that both the sensor and the converter must be grounded using two separate wires. Avoid placing the signal and power cables close together to minimize interference. Separate configuration WIKA Operating Instructions - Battery-powered signal converter FLC-406...
(manufacturer, distributors, consumers, operators power source (FLC-406) and from the connection cables to involved in WEEE treatment). the sensor before proceeding to its removal and its disposal.
Page 28
WIKA subsidiaries worldwide can be found online at www.wika.com. Euromisure s.a.s di WIKA Italia S.r.l WIKA Alexander Wiegand SE & Co. KG Alexander-Wiegand-Strasse 30 via Borghisani 4 63911 Klingenberg • Germany 26035 Pieve San Giacomo (CR) - Italy Tel. +49 9372 132-0 Telefon (+39) 0375 6404 info@wika.de...