LP1173173 Thank you for purchasing our Fiber Cooling Chiller Unit (200-230V AC) LP1173173. ・ This operation manual explains its method of operation and precautions for use. ・ Before using, read this operation manual carefully; after reading, save it in a proper place where you can easily access.
LP1173173 CAUTION For handling of thermo chiller and flow switch, refer to the attached operation manual. 1. Configuration Part Name Model No. Q’ty Thermo chiller (HRS012-A-20-MT) PZ1173142 Alarm detecting cable (20 m) AS1172750 Different diameter coupling 8-6 for SKUSDK8-6 stainless pipe...
LP1173173 2. Name and Functions of Each Section Thermo chiller Controls the water temperature. The recommended setting temperature is 27°C (no condensation). Electrical resistivity sensor Monitors the resistance value of cooling water.
LP1173173 3. Installation and Preparation This chapter explains where to install the thermo chiller and cooling water. Installation Place Follow the attached operation manual for the thermo chiller. Mounting the DI Filter Replacement Cartridge Since the DI cartridge deteriorates on contact with the air, it is packed separately.
Page 6
LP1173173 2) Mount the lower half of the DI filter with the reverse procedure to removing it. 3) Close the clamp. 4) Mount the drain plug. 5) Close the ventilation plug. 6) Start the thermo chiller with the valve of the DI filter closed.
Page 7
LP1173173 2) Connecting the tube Fiber connector Tube, Tube, (Note 4) Coupling, TPH0806W-20 TPS0604W SKUSDK8-6 (Note 1) (Note 3) (Note 2) Note 1 Tube, TPH0806W-20 Cut the tube into any length in the range of 20 m on each side of IN/OUT.
Page 8
LP1173173 When cooling plural optical fibers: ・ Up to two optical fibers can be cooled. ・ Connect optical fibers in parallel as shown below. ・ The maximum length of cooling tube should be 40 m in total. (+++++= 40 m max.) ...
Page 9
LP1173173 [Reconnection method] a. Before loosening the nut, check its SKFPK8 position. (This position is used as a Ferrule pack for recon- reference in the Step d.) necting the coupling b. Remove the nut. Check again that the front ferrule is mounted at the proper position.
Page 10
LP1173173 Wiring ・ For the AC power cable connection, follow the attached operation manual for the thermo chiller. ・ Connect the alarm detecting cable (attached AS1172750 (20 m) or optional AS1172751 (5 m)) to the Laser. Connect the EEXT. I/O (AS1172786) disconnected from the Laser to the jack side of the alarm detecting cable.
Page 11
LP1173173 Water Supply Refer to the operation manual for the thermo chiller. ⇒ When the thermo chiller is started for the first time after water supply, the water level will drop. When it is below the lower level, supply the cooling water again.
Page 12
LP1173173 Display Item Setting Contact input signal 1, C o . 1 8 OFF detection timer Contact input signal 2 SW_B C o . 1 9 Contact Contact input signal 2, form C o . 2 0...
LP1173173 4. Maintenance CAUTION Use our genuine maintenance parts. For defect caused by non-genuine maintenance parts or use of non-genuine maintenance parts, the repair is charged even if it is still within the maintenance contract period or the warranty period.
LP1173173 (1) Replacing the Replacement Cartridge of the DI Filter The replacement cartridge in the DI filter has a function to keep high purity by removing the ion generated by deteriorated cooling water. Replace it when the alarm “AL35 Electrical resistivity low” occurs in the thermo chiller.
Page 15
LP1173173 9) Open the valve on the thermo chiller’s OUTLET side. ⇒ Check for leaks. ⇒ When the cartridge is replaced, the water level of the cooling water tank will drop. In that case, supply the cooling water. CAUTION Be sure to confirm that the feed-water inlet filter (HRS-PF007) is installed before supply the water.
LP1173173 (2) Replacing the Filter Cartridge The filter cartridge in the filter housing has a function to filtrate the cooling water. Replace it within 6 months. [Item required] Filter cartridge, NFH tightening spanner, and tray to receive water Removing the Filter Cartridge 1) Close valves on both sides of the filter housing.
LP1173173 (3) Inspecting Water Leaks from the Pump Remove panels to check the pump for abnormal leaks when replacing the cooling water (every 6 months recommended). If abnormal water leaks, consult us to return the chiller and replace the mechanical seal.
LP1173173 (4) Cleaning the Dust-proof Filter Clean the dust-proof filter everyday. [Item required] Bristle brush or air blow CAUTION Refer to the operation manual for the thermo chiller. If dust is not removed after cleaning, replace the dust-proof filter. Cleaning with a bristle brush...
LP1173173 (5) Cleaning or Replacing the Union-type Small Line Filter Clean the union-type small line filter every 6 months. Replace it when dust is not removed. [Item required] Brush or air blow and spanner Disassemble the line filter to clean or replace the mesh part (element).
LP1173173 5. Alarm Code For alarm codes not described below, refer to the operation manual attached to the thermo chiller. Alarm code Contents of alarm Measures ・Confirm that the pipe is not broken or Flowrate trouble: not clogged. AL31 < 1.5 liters/min (over 30 sec.) ・Confirm that the valve is not closed too...