ELEKTRODENSTEUERUNG ES2001
SAFETY INSTRUCTIONS
- Installation, commissioning and maintenance may only be performed by
qualified personnel!
- nly connect the unit to the voltage specified in the technical data or on the type
plate (observe polarity for DC)!
- The device must be disconnected from all sources of power during installation
and maintenance work.
- The device may only be operated under the conditions specified in the operating
instructions.
TECHNICAL DATA
Power supply
Connected load
Relay output
Measuring circuit
Measuring function
Hysteresis
Response sensitivity
Working principle
Delay
Ambient temperature
Dimension
Housing
Cable
Electrical connections
Signalling
EC Conformity: The instrument meets the legal requirements of the current European Directives.
OPERATING RANGE
The capacitive resistance of long cables reduces the sensitivity of the detection.
A standard 3-wire PVC cable has a capacitance of 100 pF/m
The range therefore depends on the liquid resistance and on the cable length between the electrode and the relay ES2001.
This results in an operating range according to the diagram below:
22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL
Tel
+33 (0)1 30 25 83 20
Fax
+33 (0)1 34 10 16 05
INSTRUCTION MANUAL
230, 115, 48, 24 V ±10% AC 50/60 Hz; 24, 12 V DC
≤ 2 VA
2 changeover contacts, potential-free
AC: Max. 250 V, 5 A, 500 VA
DC: Max. 125 V, 1 A, 40 W
Galvanically isolated, AC voltage < 6 V / < 2 mA
MIN-MAX control
MIN control or MAX control
About 20% of the set sensitivity value
2 adjustable ranges
1 to 70 kΩ & 5 to 150 kΩ
Open / Closed curent lopp
ON/OFF delay adjustable: 0.5 to 3 s
Adjustment through potentiometer
-15 ... +45 °C
22.5 x 75 x 100 mm
IP40, mounting DIN rail 35x7.5 mm (EN 50 022); Option: IP55 wall-mount cabinet 88x150x130mm
min. Wire cross-section 0.5mm², shielded cable
IP20, screw terminals, cable cross-section max 2.5 mm²
1x LED: ''Operating''
1x LED: ''Status of relay''
Operating range
INTERNATIONAL
Web
www.bamo.eu
E-mail
export@bamo.fr
Outside the operating range
Cable length [ m ]
INSTRUCTION MANUAL
ELEKTRODENSTEUERUNG ES2001
06-06-2023
LEV
530-01
M-530.01-EN-AB
/1

Advertisement

loading

Summary of Contents for Bamo ES2001

  • Page 1 A standard 3-wire PVC cable has a capacitance of 100 pF/m The range therefore depends on the liquid resistance and on the cable length between the electrode and the relay ES2001. This results in an operating range according to the diagram below:...
  • Page 2 Output relay status is changed MAINTENANCE When used as intended, the device is maintenance-free. INSTRUCTION MANUAL INTERNATIONAL ELEKTRODENSTEUERUNG ES2001 22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL 530-01 +33 (0)1 30 25 83 20 www.bamo.eu 06-06-2023 M-530.01-EN-AB...
  • Page 3 Relay of the drain pump activates when MAX electrode immerses; ...drops off when MIN electrode becomes free INSTRUCTION MANUAL INTERNATIONAL ELEKTRODENSTEUERUNG ES2001 22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL 530-01 +33 (0)1 30 25 83 20 www.bamo.eu...
  • Page 4 ---> Connect relay K1 to terminal 12 TESTING THE RELAY: - Disconnect the electrodes from the relay ES2001 - Short circuit E0 and E2 → the relay is activated (alarm function) - Short circuit in the order E0, E2 and E1 → Enable E2 then E1 (control function)