Advertisement
The RT-825 temperature controller is designed for direct control of heating devices powered by 230 V with maximum current no higher than 16 A.
The controller can operate in one of four operating modes:
When the room temperature falls below 2°C from the temperature set in the controller, the heating device switches on ( symbol on the display). When the room temperature is higher than the set temperature, the heating device will be disconnected. If the controller operates in "0" mode, with two external and internal temperature sensors (parameter F3) and the temperature in the room exceeds the value set in parameter F5, the heating device will be disconnected. On the other hand, if the temperature falls below the value set in parameter F6 (antifreeze mode), the heating device will be switched on, whether the controller is on or off.
The "timer" function operates in a cyclic mode starting from switching on the controller for the set time (parameter F1), and then the controller will be switched off for the set time (parameter F2) etc. on all days of the week. The activation time of the controller starts when the number of hours is accepted with the ON/OFF key. When the "timer" function is activated, the temperature control is maintained depending on the settings.
ON/OFF button
Long press of the button switches the controller on or off (about 2 seconds).
UP/DOWN button
Short press of the button during normal operation decreases or increases the value of set temperature by one degree.
MENU button
Short press of the button switches the device to the programming mode.
Press the MENU button to enter the programming mode. In the programming mode you can set 8 parameters. Use the UP/DOWN buttons to choose one of the parameters. Press ON/OFF button to edit a parameter. Change the value of the parameter in the parameter edit mode using the UP/DOWN buttons. Confirm setting with the ON/OFF button.
Every day in the controller program is divided into four parts marked with icons:
morning
forenoon (leaving the house)
afternoon, evening (coming back)
night
It is necessary to set the start time for each of these periods (the hour of the end of the given period is the starting time of the next). The start times for each time of the day should be set separately for business days, Saturdays and Sundays. Temperature value is programmed for each time of day.
The following weekly program of the controller operation is set:
Time of day | Time of day start | Value of the set temperature | |
MON-FRI | SAT, SUN | ||
![]() | 06:00 | 25 | 25 |
![]() | 08:00 | 10 | 10 |
![]() | 16:00 | 25 | 25 |
![]() | 22:00 | 15 | 15 |
Setting up a weekly operation program:
Keep the UP button pressed for a controller to reset itself and disconnect heating device.
Press the ON/OFF button to return to operation.
To protect the controller from unauthorized access, press the UP/DOWN button for a longer time. Activation of the protection is signaled by a padlock symbol on the display. Unlocking is done in the same way.
Longer press of the DOWN button changes the controller mode of operation from automatic to manual and vice versa (day time icon goes off). Manual operation - room temperature control is based on the current setting. Use the UP/DOWN buttons to change the temperature. Automatic operation - the temperature is maintained on the basis of the pre-programmed cycles of the controller.
If the controller is set to operate with two temperature sensors by short press of the ON/OFF button, the readout source changes from the internal sensor to the external.
Controller operation errors indication
Er1 - damage to internal temperature probe
Er2 - damage of external temperature probe
Er3 - damage to internal and external probe
Take special care when installing the controller. Incorrect connection may result in electric shock and/or damage to the controller and the powered device.
1/4 - output for heater connection
2 - L power supply of the controller
3 - N power supply of the controller
5/6 - output for temperature probe connection
Do not install a device that is damaged or incomplete.
Do not install the device in rooms with high humidity, such as bathrooms.
power supply | 230 V AC |
current load heating circuit | <16 A |
temperature adjustment range | 5÷55°C |
histeresis | 2°C |
setting accuracy | 1°C |
measurement accuracy | ±0,1°C |
power consumption | 1 W |
working temperature | 0÷65°C |
terminal | 2.5mm² screw terminals |
dimensions | |
front | 86×86 mm; D= 22 mm |
back | Ø 0; D= 6 27.5 mm |
mounting | in Ø60 flush mounted |
ingress protection | IP20 |
external temperature sensor | NTC |
sensor dimensions | Ø7 ; h=25 mm |
sensor isolation | PC muff |
wire | PC 2×0,34 mm²; l= 3 m |
F&F Filipowski sp. j.
Konstantynowska 79/81 95-200 Pabianice
phone/fax: (+48 42) 215 23 83 / 227 09 71 POLAND
http://www.fif.com.pl
e-mail: biuro@fif.com.pl
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the RT-825 that isn't answered in the manual? Leave your question here.