POWER
END OF
MOTOR
Q5001
VALVE
LINKAGE
Fig. 4. Mounting the motor on a Q5001 Valve Linkage.
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment circuitry.
Disconnect all power supplies before installation.
Motors with auxiliary switches can have more than one
disconnect.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
1. Ensure that the voltage and frequency stamped on the
motor correspond with the power supply characteristics.
2. When connecting several motors in parallel, ensure that
the power supply VA rating is large enough to provide
power to all motors used without overloading.
3. Fig. 10 shows that motor terminals are quick-connects
located on top of the printed circuit board.
4. To access the wiring compartment:
a. Remove the four screws from the junction box top.
b. Lift off the cover.
5. Refer to Fig. 5 through 8 for wiring.
Wire the motor as follows:
1. Remove the wiring box cover by removing the four
screws holding the cover to the motor.
2. Wire motor to system using quick-connect terminals in
wiring box.
JUNCTION
BOX
MOTOR
1/4-20 UNC
1 in. LONG
MOUNTING
BOLTS
VALVE
M18994
SERIES 72 MODUTROL IV™ MOTORS
3. Replace wiring box cover.
CONTROLLER
-
+
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQURED.
2
CONNECTING F TO – WILL DRIVE MOTOR TO FULLY OPEN.
Fig. 5. Typical system wiring.
EXTERNAL
7
MOTOR
1
L1
T1
(HOT)
T2
L2
24V
-
+
2
F
M5778
POTENTIOMETER
Based on 63-2640—08