Power Distribution Unit
(PDU)
LIS-0816 / LIS-0832
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for Lanbe LIS-0816

  • Page 1 Power Distribution Unit (PDU) LIS-0816 / LIS-0832 User Manual...
  • Page 2 User Notice All information, documentation, and specifications contained in this manual are subject to change without prior notification by the manufacturer. The manufacturer makes no representations or warranties, either expressed or implied, with respect to the contents hereof and specifically disclaims any warranties as to merchant ability or fitness for any particular purpose.
  • Page 3: Table Of Contents

    Contents About This Manual ....................1 ..................... 1 Conventions ................2 Introduction Chapter 1................3 Series Comparison Chart ......................4 Features ...................... 5 Components Hardware Setup ..............7 Chapter 2....................7 Before You Begin ......................7 Installation Basic Operation and Chapter 3.
  • Page 4: About This Manual

    About This Manual This User Manual is provided to help you get the most from your PDU system. It covers all aspects of installation, configuration and operation. An overview of the information found in the manual is provided below. Chapter 1, Introduction, introduces you to the PDU system. Its purpose, features and benefits are presented, and its front and back panel components are described.
  • Page 5: Chapter 1. Introduction

    Chapter 1 Introduction Overview The new-generation intelligent power distributor (PDU) can effectively and conveniently improve the efficiency of power management. A Smart PDU is an intelligent power distributor that contains 8 AC sockets and provides IEC sockets. These power distributors can safely, centrally and intelligently manage power (on, off, cycle) in home, garage, monitoring, shopping mall, yard, traffic, road and bridge application scenarios, and monitor power equipment using sensors.
  • Page 6: Pdu Series Comparison Chart

    Series Comparison Chart Outlets Amps Power Cord Model Monitoring Per Port Total Level LIS-0816 IEC C19-C20 UI socket LIS-0832 32A Connector UI socket Note: For complete specifications for each model, please refer to the product specification sheet.
  • Page 7: Features

    Features  Remote users can monitor PDU and loop status on web pages  Support safe shutdown function  Each device has its own power supply and socket. The user interface can be accessed even when the overload state triggers the automatic power-off switch on this device ...
  • Page 8  RTC supports timer operation in the absence of power supply  Support multi-user Settings, and multi-user different management rights Settings  Support PDU energy usage statistics, quickly understand the usage of electrical equipment through graphics  PDU Exterior The PDU provides LCD Displays to visually display the operating status of ports and hosts ...
  • Page 9: Components

    Components  LIS-0416 Front View 3 4 2 1 Rear View LIA-0816 6 7 8 9 Rear View LIA-0832 Item Description This switch is recessed and must be pushed with a Defaults Switch thin object, such as the end of a paper clip You can press this button and hold it for more ...
  • Page 10 Cascade input Cascaded RJ45 input to other devices port Cascade output Cascaded output with other devices through RJ45 port It can connect to 10M/100M Ethernet network. LAN Port Control and access PDUs External temperature and humidity sensors can be sensor connected through RJ11 ports ports When the PDU is overloaded, the protector...
  • Page 11: Chapter 2. Hardware Setup

    Chapter 2 Hardware Setup Before You Begin Important safety information regarding the placement of this switcher is listed in the appendix for safety tips, please refer to this information before operation. Before installation, ensure that the power supply of all devices to be connected is turned off.
  • Page 12 Note: It is strongly recommended that you use harness straps and cable boxes to secure cables to the front panel of the equipment. Prevent loose and poor contact in subsequent time. This Page Intentionally Left Blank...
  • Page 13: Chapter 3. Basic Operation And

    Chapter 3 Basic Operation and First Time Setup First Time Setup After the PDU is installed on the shelf, the administrator needs to set network parameters and change the default value of super Administrator log-in Settings and new users. The most convenient way is to use a browser through the network log-In.
  • Page 14 following should appear: 3. Please fill in the field data according to the information provided in the device setting instructions of Network Setting. Such as: :...
  • Page 15 Change administrator log-in To change the default user name and password of the super administrator, perform the following operations: 1. Click the User List in the User Management button at the top of the screen. A list of users is listed on the left side of the user administrator page, with their more detailed information displayed on a large block in the center.
  • Page 16 Continue to perform After you complete the network Settings and change the default administrator account and password, you can have other administrator accounts Operation permissions, including new users, are explained in the next section. This Page Intentionally Left Blank...
  • Page 17: Chapter 4. Browser Operation

    Chapter 4 Browser Operation Logging In You can connect to PDUs from any platform with a web browser installed. To access the PDU, perform the following operations: Open a browser and enter the IP address of the PDU that you want to access in the address box.
  • Page 18: Page Components

    Note: window shown above displays contents administrator&aposs page according to the type, authority, and PDU of each user Depending on the model, items may not be displayed on all users' pages. Page Components Web page components are described as follows: Item Description Option Column This option column contains the main operation...
  • Page 19 PDU operating Provides real-time information about the device, such status as power voltage, current, and power consumption.
  • Page 20: Socket Access

    Socket access Online When you log in to the PDU, the user interface will be displayed with the default socket access page and a menu. The PDU status and socket status contents are displayed on the main block. Note: Only PDUs with this function display the socket status sub-menu block.
  • Page 21: Statistics

    In the schedule task list bar, you can retrieve the desired port schedule status by time. In the add scheduled task TAB, you can add scheduled tasks based on your requirements, such as socket port, switch type, time, working day, and remarks.
  • Page 22: Setting

    You can collect energy consumption statistics based on the specified query time range. Select a start time from the drop-down list box based on the date, month, and year. You can select energy consumption within 24 hours, the latest 7 days, 30 days, and 90 days based on the quick selection function on the time bar.
  • Page 23 If you log in to the PDU as an administrator, the account list displays information about all accounts in the PDU system. The administrator has the permission to add, delete, and edit accounts. The default administrator account can only be edited but cannot be deleted. After logging in as an administrator, you can use this function to add new accounts and select corresponding permissions.
  • Page 24 Browsing permission This section describes how to query system logs, operation logs, and statistics. You can select the corresponding options to assign the browsing permission to users. Blacklist Setting Users can add Settings based on the IP addresses that need to be restricted to prevent accounts with restricted addresses from accessing and logging in to the PDU control system.
  • Page 25 The default IP address is 192.168.0.100. You can reset the IP address and network Settings based on your IP address segment. Click SAVE to Save the new Settings. 。 Note: You can restart the PDU in two ways: 1. Press the embedded RST reset button at the front of the PDU with a needle, such as the end of a paper clip, to restart the PDU.
  • Page 26 Settings. Port delay setting function allows you to set the opening and closing delay time of the port socket. By default, the switching interval of the adjacent port is 1 second. You can also modify the interval delay time according to your needs. Note: The delay time of the port socket is intended to protect the electrical appliance from experiencing the shock of current and voltage at the moment of power-on, thus protecting the...
  • Page 27 SNMP Settings. If this function is enabled, an alarm will be sounded and E-mail message will be sent when the circuit breaker trips or the PDU/ socket threshold is set beyond the minimum or maximum setting range. PING is used to test whether the network of the port connected to the PDU is normal.
  • Page 28 Global Settings Sub-function options include: Mail Settings, System Time Settings, Electricity Meter Reset, Factory Reset, System Upgrade, Language Settings The email setting function allows you to send PDU alarms and logs to a specified email address after setting an email address. After setting the email address, you can send a test email to check whether the email address is correct.
  • Page 29 Mail logs record sent mail information. You can query, delete, or export mail logs based on the time setting. System time You can set the system time of the PDU and synchronize the time with the browser you log in to. The meter reset function can reset the accumulated electric quantity of THE PDU.
  • Page 30 restored, the system restarts. You can perform related operations, such as setting PDUs again. After system upgrade, you can query the latest version of the PDU software you use on our website, download the file and save it in the specified file directory on the PC, select the upgrade file to complete the software update of the PDU system, and restart the PDU system after the system is updated.
  • Page 31 Input Warning Setting. You can set the maximum and minimum values of the input current and voltage. When the current or voltage exceeds the threshold, the PDU automatically sends alarm logs to the specified email box address, and an alarm message is displayed on the home page, facilitating query and handling after your next log-in.
  • Page 32 Output Warning setting. You can set the upper limit and lower limit of the output current of each power output port respectively to ensure that the electrical device works within a safe current range. If the output current exceeds the set range, the system will issue an alarm. You can also set parameters in batches.
  • Page 33: About

    Note: Set the current threshold appropriately according to PDU parameters. Incorrect current setting may cause the PDU to fail to provide power output or effectively protect electrical devices and circuits when excessive current occurs. Temp & Humi Warning Setting You can set the upper and lower limits of temperature and humidity. When the upper and lower limits of temperature and humidity are exceeded, the system generates an environmental alarm.
  • Page 34: Logs

    Logs Logs are classified into two types: System Logs and User Operation Logs You can click the More Warnings button in the upper part of the main window to implement system logs. The system log list is displayed in the pop-up window. You can view the time, type, and description of system logs.
  • Page 35 User Operation Logs, You can click the log-in user drop-down list in the upper right corner of the window and choose Operation Logs to display the user Operation Logs window, which displays the log time, user, log description, and accessed IP address. This Page Intentionally Left Blank...
  • Page 36: Appendix

    Appendix Safety Instructions General This product is for indoor use only. � Read all of these instructions. Save them for future reference. � Follow all warnings and instructions marked on the device. � Do not place the device on any unstable surface (cart, stand, table, etc.). �...
  • Page 37 The device is equipped with a 3-wire grounding type plug. This is a safety � feature. If you are unable to insert the plug into the outlet, contact your electrician to replace your obsolete outlet. Do not attempt to defeat the purpose of the grounding-type plug.
  • Page 38: Rack Mounting

    for service. The device does not operate normally when the operating instructions � are followed. Only adjust those controls that are covered in the operating instructions. � Improper adjustment of other controls may result in damage that will require extensive work by a qualified technician to repair. Rack Mounting When extending the device out of the rack, ensure that the rack is �...
  • Page 39: Ip Address Determination

    IP Address Determination If you are an administrator and log in for the first time, you must connect the switcher to assign an IP address for user access. PDU device provides the means that, in each case, your computer must be on the same network segment as the switcher; When you are connected and logged in, you can assign a fixed network address to the device.
  • Page 40: Specifications

    Specifications Function LIS-0816 LIS-0832 Power Outlets Direct Power Inlet IEC C19 Aviation connector Power Outlets IEC C13 Connectors 1 x RJ-45(Female) 2 x RJ-45(Female) Cascade State of the socket LCD Displays LED lamp Powe 1 (Orange/ Green) 10/100M Switches 1 x Semi-recessed button...