What The Warranty Policy Covers What The Warranty Policy Does Not Cover The Warranty Will Not Apply If; How to Make a Warranty Claim Pre-start Checklist Commissioning Checklist XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Armcor Air Solutions is not responsible for performance of equipment in applications for which the equipment was not designed or specified. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
• When a drain is exposed to freezing temperatures or subject to the formation of condensation, the drain should be insulated. IMPORTANT: ALL UNITS LOCATED IN PLANT ROOMS MUST HAVE DRAIN TRAYS UNDER THE COMPLETE UNIT. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
• Test load to see if the weight is equally distributed. Do this by lifting the unit a few centimetres off the ground level and checking stability before lifting any further or before transporting the unit. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
• Where a Heat Exchanger is incorporated in the equipment, warranty will be void if filters are not fitted. IMPORTANT: NEVER OPERATE A UNIT WITHOUT FILTERS FITTED TO THE RETURN & FRESH AIR INTAKES. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Air discharged to outdoors. Fresh Air Use a fresh air cowl or grill to introduce fresh air. Supply Air Connect to the airconditioning system or directly into the conditioned area. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Sight glass is not necessarily clear. Do not charge on stabilised. sight glass with reverse cycle systems. Compressor TX Valve Control Board All TX valves have adjustment for super heat settings. 8-11K is acceptable for r407c. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Page 10
Tighten all pipe clamps before starting. These clamps may loosen in transport. Compressor Bracket Do not remove compressor bracket, this bracket is for transport and for the operation of the compressor. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
• Check and record the available voltage and amperage of each phase. • Check and record the amperage of each motor against nameplate details. • Check and record refrigerant gas pressures (if applicable). XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Australia. • Field wiring, refrigerant pipe run between units, the condensation drainpipe, or other accessories. • Any warranty work performed by Armcor Air XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Superheat should be between 8-11°C on Cooling (R407C) If superheat is high, add refrigerant slowly using liquid into the suction line. Do not flood liquid into the suction line. XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
(where units are allowed beyond this length) Superheat setting (ºC) (refer Installation Instructions) Refrigerant Discharge Pressure on Cooling (kPa) Suction: Discharge: Refrigerant Pressure on Heating (kPa) Suction: Discharge: Refrigerant Leak Check Y / N XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Page 15
Notes ........................................................................................................................................................................................................................................................XES – ERV-PAC Packaged Swim Pool Unit Installation and Operation Manual 2021...
Page 16
Fresh Air Indoors For more information W: armcor.com.au E: sales@armcor.com.au P: (03) 8301 9200 109–111 Northcorp Blvd Broadmeadows Vic 3047...
Need help?
Do you have a question about the XES and is the answer not in the manual?
Questions and answers