One-Touch™ Test Mode
Test
Normal
Operation
Hold down One-Touch™ button for
less than 2 seconds.
One-
Touch™
View Mode
Note: Automatically exits after 2
minutes.
CAUTION:
Disconnect any output relays that should not be triggered before entering Active mode.
Hold down One-Touch™ button for 2
to 4 secs.
One-
Trigger each input sensor in turn and
Touch™
ensure that the LEDs indicate the
Active
correct state.
Mode
Note: The controller will operate
unconfigured and no system
communications will occur.
Hold down One-Touch™ button for
Exit One-
less than 2 seconds. One-Touch™
Touch™
Test mode will automatically be timed
Active Test
out after 1 hour, power up or power
mode
down.
Action
Configured system (expected)
View mode is intended for a configured system. See
help for more information.
The first change in state will be latched and the display for
that input will not change until test mode is exited.
– Page 5 of 22 –
Observation
GREEN system status LED flashes at
normal rate.
RED and GREEN input status LEDs off.
GREEN output status LED off.
GREEN system status LED flashes at
twice normal rate.
Unconfigured system: All RED LEDs
will flash briefly three times and test mode
is exited.
RED LED = tamper state.
GREEN LED = active state/normal
output.
GREEN LED off = non-active
state/unconfigured input.
GREEN system status LED flashes four
times faster than normal.
Green - Red
2-State
N/A
N/A
Input open
Input closed
Green - Red
3-State NO
N/A
Input open
Input closed
Input open tamper
GREEN output LED is on/off for a 5
second cycle (relays active/inactive)
>
>
GREEN flashes at normal rate again.
All other status LEDs off.
4-State
Input open
Input closed
Input open
tamper
Input
tamper
short
3-State NC
N/A
Input closed
Input open
Input
tamper
short