MAKING MODERN LIVING POSSIBLE
Quick Guide
HVAC Basic Drive - DAA101

Advertisement

Table of Contents
loading

Summary of Contents for Daikin VLT DAA101

  • Page 1 MAKING MODERN LIVING POSSIBLE Quick Guide HVAC Basic Drive - DAA101...
  • Page 2: Table Of Contents

    HVAC Basic Drive - DAA101 Quick Guide Contents Contents 1 Quick Guide 1.1 Safety 1.1.1 Warnings 1.1.2 Safety Instructions 1.2 Introduction 1.2.1 Available Literature 1.2.2 Approvals 1.2.3 IT Mains 1.2.4 Avoid Unintended Start 1.2.5 Disposal Instruction 1.3 Installation 1.3.1 Before Starting Repair Work 1.3.2 Side-by-Side Installation 1.3.3 Mechanical Dimensions 1.3.4 Electrical Installation in General...
  • Page 3: Quick Guide

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1 Quick Guide Motor Thermal Protection: Motor overload protection is possible by setting Parameter 1.1 Safety 1-90 Motor thermal protection to the value Electronic Thermal Relay (ETR) trip. 1.1.1 Warnings WARNING WARNING Installation at high altitudes High Voltage Warning...
  • Page 4: Mains

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.2.3 IT Mains 1.2.5 Disposal Instruction CAUTION Equipment containing electrical components must not be disposed of together with domestic IT Mains waste. Installation on isolated mains source, i.e. IT mains. It must be separately collected with electrical Max.
  • Page 5: Side-By-Side Installation

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.3.2 Side-by-Side Installation The frequency converter can be mounted side-by-side and requires the clearance above and below for cooling. Power Clearance above/ below (mm/inch) Frame IP class 3x200-240V 3 x 380-480V 3 x 525-600V IP20 0.25-1.5kW/0.33-2Hp...
  • Page 6: Mechanical Dimensions

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.3.3 Mechanical Dimensions Power (kW/Hp) Height (mm/inch) Width (mm/inch) Depth Hole (mm) (mm/inch) Frame IP class 3x200-240V 3 x 380-480V A incl. Decoupling plate IP20 0.25-1.5 kW/ 0.37-1.5kW/ 195/7.7 273/10.7 183/7.2 75/3 56/2.2 168/6.6...
  • Page 7: Electrical Installation In General

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.3.4 Electrical Installation in General All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required, (75°C) recommended. Power (kW) Torque (Nm) Frame IP class 3 x 200-240V 3 x 380-480 Line...
  • Page 8: Connecting To Mains And Motor

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.3.5 Connecting to Mains and Motor IP20 200-240V 0.25-11kW and IP20 380-480V 0.37-22kW. The frequency converter is designed to operate all standard three-phased asynchronous motors. For maximum cross-section on wires please see section Mains Supply.
  • Page 9: Fuses

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide IP20 380-480V 30-45kW IP20 380-480V 90kW Line Relays Line Earth Motor Motor Earth Relays 1.3.6 Fuses IP20 380-480V 55-75kW Branch circuit protection In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuit and overcurrent protected according to national/international regulations.
  • Page 10: Emc-Correct Electrical Installation

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.3.7 EMC-Correct Electrical Installation Non UL compliance If UL/cUL is not to be complied with, Danfoss recommends using the fuses mentioned in the below table, which will General points to be observed to ensure EMC-correct ensure compliance with IEC 61800-5-1: electrical installation.
  • Page 11 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Panel PLC etc. Output con- tactor etc. Earthing rail Cable insula- tion stripped Min. 16 mm Equalizing cable All cable entries in one side of panel Control cables Motor cable Min. 200mm between control Mains-supply cable, mains cable...
  • Page 12: Control Terminals

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.3.8 Control Terminals Control terminals: Illustration 1.4 shows all control terminals of the frequency converter. Applying Start (term. 18), connection between IP20 200-240V 0.25-11kW and IP20 380-480V 0.37-22kW: terminal 12-27 and an analog reference (term. 53 or 54 and 55) make the frequency converter run.
  • Page 13: Electrical Overview

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.3.9 Electrical Overview 3 Phase power input Motor UDC- Not present on all power sizes UDC+ 50 (+10V OUT) relay2 +10Vdc 0-10Vdc- 240V AC 3A 53 (A IN) 0/4-20 mA 54 (A IN) 0-10Vdc- 0/4-20 mA 55 (COM A IN/OUT)
  • Page 14: Programming

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.4 Programming A number of information can be read from the display. 1.4.1 Programming with the Local Control Parameter number and name. Panel (LCP) Parameter value. Set-up number shows the active set-up and the edit set- NOTE up.
  • Page 15: The Start-Up Wizard For Open Loop Applications

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide At power-up At the first power-up the user is asked to choose preferred language. Once selected this screen will never be shown again in the following powerups, but language can still be changed in 0-01 Language.
  • Page 16 HVAC Basic Drive - DAA101 Quick Guide Quick Guide At power up the user is asked to choose the prefered laguage. Select Regional Settings [0] Power kW/50 Hz Setup 1 Grid Type Select language 200-240V/50Hz/Delta [1] English Setup 1 Setup 1 Asynchronous Motor Status Quick...
  • Page 17 HVAC Basic Drive - DAA101 Quick Guide Quick Guide The DAA101 Start-up Wizard for Open Loop Applications No & Name Range Default Function 0-03 Regional Settings [0] International [1] US 0-06 Grid Type 0] 200-240V/50Hz/IT-grid Size related Select operating mode for restart upon [1] 200-240V/50Hz/Delta reconnection of the drive to mains voltage after [2] 200-240V/50Hz...
  • Page 18 HVAC Basic Drive - DAA101 Quick Guide Quick Guide No & Name Range Default Function 3-03 Maximum Reference -4999-4999 The maximum reference is the lowest obtainable by summing all references 5-40 Function Relay [0] See 5-40 Function Relay Alarm Select the function to control output relay 1 Function relay 5-40 Function Relay [1] See 5-40 Function Relay...
  • Page 19 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Closed Loop Set-up Wizard 0-03 Regional Settings International Asynchronous Motor 0-01 Configuration Mode Open Loop 1-20 Motor Power 1.10 1-22 Motor Voltage 0050 1-23 Motor frequency 0050 1-24 Motor current 04.66 1-25 Motor nominal speed 1420 4-12 Motor speed low limit...
  • Page 20 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Closed Loop Set-up Wizard No & Name Range Default Function 0-03 Regional Settings [0] International [1] US 1-20 Motor power 0.09-110kW Size related Enter motor power from nameplate data 1-22 Motor Voltage 50.0 - 1000.0V Size related Enter motor voltage from nameplate data 1-23 Motor Frequency...
  • Page 21 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Motor Set-up The Quick Menu Motor Set-up guides through the needed Changes Made motor parameters. Changes Made lists all parameters changed since factory setting. Only the changed parameters in current edit-setup No &...
  • Page 22: Parameter Overview

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.5 Parameter Overview Parameter Overview 0-** Operation / Display [2] Set-up 2 0-39 Display Text 3 [15] 7.50 kW - 10.0Hp 0-0* Basic Settings *[9] Active Set-up 0-4* LCP Keypad [16] 11.00 kW - 15.00Hp 0-01 Language 0-12 Link Setups 0-40 [Hand on] Key on LCP...
  • Page 23 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Parameter Overview 1-63 Slip Compensation Time 3-1* References 0.00 - 194.00A, * 0.00 [54] Auto start Constant 3-10 Preset Reference 4-51 Warning Current High [60] Counter A (up) 0.05 - 5.00s, * 0.10 -100.00 - 100.00%, * 0.00 0.00 - 194.00A, * 194.00 [61] Counter A (down)
  • Page 24 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Parameter Overview [73] Logic rule 3 [0] Current mode [26] Bus OK [4] Enable / no warning [74] Logic rule 4 *[1] Voltage mode [35] External Interlock [5] Drive running [75] Logic rule 5 6-2* Analog Input 54 [45] Bus Control [6] Running / no warning...
  • Page 25 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Parameter Overview *[0] Digital and ctrl.word 8-52 DC Brake Select 13-00 SL Controller Mode [13] Analog in 54 [1] Digital only [0] Digital input *[0] Off [20] Alarm number [2] Controlword only [1] Bus [1] On [30] Counter A...
  • Page 26 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Parameter Overview [30] Start timer 1 [11] Automatic reset x 15 15-05 Over Volt's 16-38 SL Controller State [31] Start timer 2 [12] Automatic reset x 20 0 - 65535, * 0 0 - 255, * 0 [32] Set digital out A low [13] Infinite auto reset...
  • Page 27: Warnings And Alarms

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide Parameter Overview 20-01 Feedback 1 Conversion 20-94 PI Integral Time 22-46 Maximum Boost Time *[0] Disabled *[0] Linear 0.10 - 9999.00s, * 9999.00 0 - 600s, * 60 [1] Enabled Run Forward [1] Square root 20-97 Process PI Feed Forward Factor 22-47 Sleep Speed [Hz]...
  • Page 28 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Alarm/ Warning Fault Trip number Number Fault text Warning Alarm locked Cause of problem Calibration failed Contact your local Danfoss supplier. The setting of motor voltage, motor current and motor power is Unom,Inom presumably wrong.
  • Page 29: General Specifications

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.7 General Specifications 1.7.1 Mains Supply 3 x 200-240V AC Frequency converter P2K2 P3K P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K Typical shaft output (kW) 0.25 0.37 0.75 1.5 11.0 15.0 18.5...
  • Page 30: Mains Supply 3 X 380-480Vac

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.7.2 Mains Supply 3 x 380-480VAC ® MG.18.A2.02 - VLT is a registered Danfoss trademark...
  • Page 31 HVAC Basic Drive - DAA101 Quick Guide Quick Guide ® MG.18.A2.02 - VLT is a registered Danfoss trademark...
  • Page 32: Mains Supply 3 X 380-480Vac

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.7.3 Mains Supply 3 x 380-480VAC Frequency converter P22K P30K P37K P45K P55K P75K P90K Typical shaft output (kW) 22.0 30.0 37.0 45.0 55.0 75.0 90.0 Typical shaft output (hp) 30.0 40.0 50.0 60.0...
  • Page 33: Mains Supply 3 X 525-600Vac

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.7.4 Mains Supply 3 x 525-600VAC Frequency converter P2K2 P3K0 P5K5 P7K5 P11K P15K P22K P30K P45K P55K P75K P90K Typical shaft output (kW) 11.0 15.0 22.0 30.0 45.0 55.0 75.0 90.0 Typical shaft output (hp) 10.0...
  • Page 34: Emc Test Results

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide 1.7.5 EMC Test Results The following test results have been obtained using a system with a frequency converter, a screened control cable, a control box with potentiometer, as well as a motor screened cable. RFI Filter Type Conduct emission.
  • Page 35 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Protection and features • Electronic thermal motor protection against overload. • Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature. • The frequency converter is protected against short-circuits between motor terminals U, V, W. •...
  • Page 36 HVAC Basic Drive - DAA101 Quick Guide Quick Guide Analog inputs Number of analog inputs Terminal number 53, 54 Terminal 53 mode Parameter 6-19: 1 = voltage, 0 = current Terminal 54 mode Parameter 6-29: 1 = voltage, 0= current Voltage level 0 - 10V Input resistance, R...
  • Page 37: Special Conditions

    HVAC Basic Drive - DAA101 Quick Guide Quick Guide All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Surroundings Enclosure IP20 Enclosure kit available IP21, TYPE 1 Vibration test 1.0g Max.
  • Page 38 132R0078 MG18A202 Rev. 2011-03-04 *MG18A202*...