Introduction Thank you for purchasing Norlake Scientific equipment. This manual contains important instructions for using the LogiTemp® Plus electronic controller system. Please read it carefully. DANGER Improper or faulty hook-up of electrical components in the refrigeration units can result in severe injury or death.
Applications LogiTemp® Plus systems are designed to control SciPak™ refrigeration Systems for freezer and cooler applications. Each system contains a condensing unit, evaporator(s) with LogiTemp Plus control board(s), electric expansion valve(s), pressure transducers, temperature sensors, and reverse cycle valve. Figure 1 below shows where the LogiTemp Plus controller is mounted on the system.
LogiTemp Plus controller. • One Ethernet Port is used for connecting the edge manager (router) in the control panel to the LogiTemp Plus controller. This is used in unison with the iPad for an interface for the user to control the system.
• The room temperature sensor replaces the conventional temperature control. The temperature is set with the push buttons on the LogiTemp Plus remote display or through its web page. The default temperature must be checked during the first startup of the machine against the actual application temperature. The default must be reset to the actual application temperature if there is a discrepancy.
• A demand defrost scheme to detect the frost build-up and the criteria to start a defrost are programmed in LogiTemp® Plus. • Unlike scheduled defrost, LogiTemp Plus with demand defrost is really an energy saver. If no selection is made, the controller will automatically select demand defrost when the power is applied to the controller.
• After selecting the demand defrost, if the elapsed time since the last defrost has been a selectable time (Int) from 8 hours (480) to 72 hours (4320), Maximum Defrost Interval, LogiTemp Plus will go into defrost to ensure a proper oil return.
A reverse cycle valve is already factory-installed on the condensing unit. The valve’s primary function is to reverse the direction of the refrigerant flow during defrosting. When the LogiTemp Plus demand defrost determines that a defrost is necessary, the reverse cycle valve is activated, and the high-temperature refrigerant flow is reversed.