Introduction

VoltDetector 12-1000 V

This contactless voltage tester is used to test alternating electric fields.
It can detect voltages in insulated cables, e.g. spot cable breaks.

Safety instructions

shock hazard
AC > 50 V
DC > 120 V

Above these voltage limits: life-threatening electric shock if touched.

  • The warranty is voided in the event of injury or damage to property caused due to non-compliance with these operating instructions. The manufacturer accepts no liability for consequential damage.
  • Operational safety is no longer guaranteed if the voltage tester has been modified in any way. Do not disassemble. Do not disassemble.
  • Test the device on a known voltage source before and after you use it.

Proper use

Voltage: 12 - 1000 V AC
Frequency: 40- 500 Hz

  • Only trained technical staff may use the voltage tester.
  • The voltage tester must not be used to verify that there is no live current.
  • You may only use a two-pole voltage tester as per EN61243-3 to verify that there is no live current.
  • You must pass on the operating instructions as well if you give voltage tester to a third party.

Operational control

Operational control

  1. Testing tip
  2. LED indicator
  3. Ready-to-use indicator
  4. Power on/off button
  5. Flashlight on/off switch
  6. End cap
  7. Torch

Preparation for using

Indication & automatic switch-off

Indication & automatic switch-off

Fitting/replacing the battery

Fitting/replacing the battery

Battery type: 2x 1.5 V AAA
Low battery: the ready-to-use indicator LED flashes

Preparing the device

Check the voltage tester is safe and intact on a regular basis (e.g.
examine for damage to the housing or deformation).
Preparing the device

Note:
All LEDs light up briefly when device is switched on.

Checking the voltage

Visual and audible testing signal
Checking the voltage

Indicator (reference only)

caution
Field force depends on:

  • connected voltage
  • Distance from power source


Indicator (reference only)

Mute mode

Mute mode

Technical specifications

Protection class IP67
Temperature range -20°C – +40°C
Relative humidity < 80% rF
Dimensions (L x W x H) 150 x 28 x 28.5 mm
Safety tested as per EN 61010-1:2010
Weight (without / with battery) 40 g / 50 g

Cleaning

  • Switch off voltage tester before cleaning.
  • Clean voltage tester with a damp cloth - do not use any scouring or solvents.
  • Dry thoroughly before using again.

Disposal

  • Dispose of the voltage tester as per the applicable statutory regulations.

  • You must dispose of empty batteries properly and separately from the product.


Dangerous voltage, risk of electric shock and impact on the voltage tester's electric safety.


Observe the indications in the operating instructions.


Uninterrupted double or reinforce insulation as per Category II EN 61140. Protection against electric shock.


Complies with European specifications.


United Kingdom Conformity Assessed


Canadian Standards Association (NRTL/C)


Complies with applicable Australian regulations.


The voltage tester meets WEEE Directive (2012/19/EU).


The voltage tester is used to measure the source in low-voltage installations (i.e. electrical measuring devices and measurements on counters, overcurrent protection devices and load management devices).

Wiha Werkzeuge GmbH
Obertalstraße 3 –7
78136 Schonach/Germany
Tel. +49 77 22 959-0
Fax +49 77 22 959-160
info.de@wiha.com
www.wiha.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Wiha SB25513 - VoltDetector 12-1.000 V Operating Instructions

Advertisement

Need help?

Need help?

Do you have a question about the SB25513 and is the answer not in the manual?

Questions and answers

Table of Contents