Riello RS 68/EV O2 BLU Installation, Use And Maintenance Instructions page 16

Forced draught gas burners
Table of Contents

Advertisement

Electrical connection of ionization probe and flame detector
It is important for signal transmission to be almost totally free
of any disturbances or loss:
• always separate the detector cables from the other cables:
– Line capacitance reduces the magnitude of the flame signal.
– Use a separate cable.
Technical data
LMV52...
Mains voltage
base control box
Mains frequency
Power absorption
Safety class
Load on 'input'
F1 unit fuse (internal)
terminals
Main fuse of perm. network (external)
Undervoltage
• Safety switch-off from operating position to
mains voltage
• Restart when mains voltage picks up
Oil pump / magnetic clutch (nominal voltage)
• Nominal current
• Power factor
Air pressure switch test valve (nominal voltage)
• Nominal current
• Power factor
Load on 'output'
Total load on the contacts:
terminals
• Mains voltage
• Total unit input current (safety circuit)
load on contacts due to:
- Fan motor contactor
- Ignition transformer
- Valve
- Oil pump / magnetic clutch
Single contact loading:
Fan motor contactor (nominal voltage)
• Nominal current
• Power factor
Alarm output (nominal voltage)
• Nominal current
• Power factor
Ignition transformer (nominal voltage)
• Nominal current
• Power factor
Fuel gas valve (nominal voltage)
• Nominal current
• Power factor
Fuel oil valve (nominal voltage)
• Nominal current
• Power factor
Cable lengths
Main line
Environmental
Operation
conditions
Climatic conditions
Mechanical conditions
Temperature range
Humidity
20155480
Technical description of the burner
16
GB
• Respect the allowed cable lengths.
• The ionisation probe is not protected against the risk of elec-
trocution. When connected to the electricity supply, the ionisa-
tion probe must be protected against any accidental contact.
• Position the ignition electrode and the ionisation probe so
that the ignition spark cannot form an arc on the probe
(risk of electric overcharge).
AC 230V -15% / +10%
50 / 60 Hz ±6 %
< 30W (normal)
I, with components in compliance with II and III, according to
DIN EN 60730-1
6.3 AT
Max. 16 AT
< AC 186 V
> AC 188 V
2A
cos  > 0.4
0.5A
cos  > 0.4
AC 230 V -15 % / +10 %
Max. 5 A
1A
cos  > 0.4
1A
cos  > 0.4
2A
cos  > 0.2
2A
cos  > 0.4
1A
cos  > 0.4
Max. 100 m (100 pF/m)
DIN EN 60721-3-3
Classe 3K3
Classe 3M3
-20...+60°C
< 95% RH
Tab. G