Emergency down light

Advertisement

Quick Links

EMERGENCY DOWN LIGHT
Warning:
Please read through all following instructions before installing the unit.If any doubt about correct
installation,please consult aqualified electrician.
Technical date:
Model name
Rated voltage
Operating mode
Rated wattage
Led
Correlated Color Temperature
Luminance Flux
Emergency Luminance Flux
Battery
Charge
Discharge duration
Power factor
Operating temp range
Weight
Warranty
Remark
140
36
FRN-Z1102U
220-240V~50/60Hz
Maintained/ Non-maintained
5W
3535
5700-7200K
≥250lm
≥250lm
LiFePo4 3.2V /3000mAh
16H
3H
≥ 0.4
0℃~40℃
0.29KG
3 years
Electric shock protection class:II
External light protection class: IP20
Powercord:H03RN-F-0.5mm²
Suitable for mounting on normally flammable surface
Green LED indicator indicates battery charging mode Safety and performance in accordance with
EN55015, EN61347, EN60598-1, EN60598-2-22, AS60598.2.22 EN61000-3-2, EN61000-3-3
Suitable for indoor use, wall mounted if the external flexible cable or cord of this luminaire is dam-
aged, it shall be exclusively replaced by the manufacturer or his service agent or a similar qualified
person in order to avoid a hazard.
The battery is non-replaceable.
Illustration:
1.This luminaire is an embedded ceiling light with a hole size of ø60-ø70mm
2.The luminaire can choose whether to use the decorative panel according to the user's needs. If the
decorative panel is not needed, it can be rotated and removed without affecting the normal installa-
tion..
3.When installing the luminaire, the user can select whether the battery and the driving power supply
are fixed according to the needs (with screws and expansion)
4.This luminaire can choose whether to connect external continuous and non-continuous function
switch according to user needs. The default is continuous type.
5.This lamp has self-test function, please refer to "TESTING" requirements and steps.
Installation
The light source contained in this luminaire shall only be replaced by the manufacturer or his service
agent or a similar qualified person.
1. Opening as required: 60-70mm(see FIG2)
2. Wiring as required(see table1&FIG1)
3. Place the battery and drive power supply in appropriate positions as required, and embed the lamp
into the top surface
4. Indicator light: under the state of power supply, the battery is charged with green light, the battery is
full with green light, and the red light is flashing when the battery fails.(see table2)
5.In the emergency state, long pressing the test button can turn off the emergency function.
6. Refer to the requirements and steps of "TESTING" for specific information
Testing:
The emergency lighting must be inspected and tested regularly in accordance with local codes of
practice. Note: for safety reasons tests should be carried out during day light hours.
The testing should be doing in an dry environment and did by a qualified person.
Move the plastic diffuser, press the test button to simulate failure of mains power, the emergency light
should be on and driven by battery The minimum recommended test schedule is as follows: After
installation allow 36 hours to ensure full battery charge and then interrupt the supply: check after 3
hours that tube is still lighting.
1. Manual test: Press the test switch twice, the green and red indicator light is on, the luminaire is
transferred to the analog monthly inspection emergency function, and the main power status is
automatically restored after the emergency time is not less than 30 seconds; press the test switch
three times, the green and red indicator light flashes. The luminaire is transferred to the simulated
semi-annual inspection (180 days) emergency function to discharge termination, and the main power
state is automatically restored after the emergency time is not less than 30 minutes. (If the emergency
does not reach the emergency time or the emergency red indicator light is flashing, report the fault)
( see table 3)
2. Automatic test: The luminaire is transferred to the simulation monthly inspection emergency
function. The green and red indicator light is on, and the emergency time is not less than 30 seconds.
The main power status is automatically restored. The and red indicator light flashes. The emergency
function is terminated by the discharge, and the main power state is automatically restored after the
emergency time is not less than 30 minutes. (If the emergency does not reach the emergency time or
the emergency red indicator light is flashing, report the fault.
3. Emergency shutdown: Under normal emergency conditions, the luminaire can be turned off by
pressing the test switch for 3-5 seconds.

Advertisement

loading
Need help?

Need help?

Do you have a question about the FRN-Z1102U and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Frontier FRN-Z1102U

  • Page 1 6. Refer to the requirements and steps of "TESTING" for specific information Technical date: Testing: Model name FRN-Z1102U The emergency lighting must be inspected and tested regularly in accordance with local codes of practice. Note: for safety reasons tests should be carried out during day light hours. Rated voltage 220-240V~50/60Hz The testing should be doing in an dry environment and did by a qualified person.
  • Page 2 Table1 This marking indicates that this product should not be disposed with other household wastes throughout the EU. To prevent possible harm to the environment or human Line Illustrate health from uncontrolled waste disposal, recycle it responsibly to promotethe sustainable reuse of material resources. To return your used device, please use the Brown connect “L”...