Troubleshooting - Mitsubishi Electric Mr.SLIM PLA Series Technical & Service Manual

Hide thumbs Also See for Mr.SLIM PLA Series:
Table of Contents

Advertisement

TROUBLESHOOTING

9
HOW TO CHECK THE PARTS
PLA-P3AA
Parts name
Room temperature
Disconnect the connector then measure the resistance using a tester.
thermistor
(TH1)
(Surrounding temperature 10:~30:)
Pipe temperature
thermistor
(TH2)
Condenser/Evaporator
temperature thermistor
(TH5)
Vane motor
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Fan motor
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Relay connector
1
Red
1
Relay connector
White
2
2
3
Black
3
Protector
OPEN :130:
CLOSE :80i20:
Drain pump
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:)
Red
1
2
Red
Drain sensor
Measure the resistance between the terminals using a tester.
Measure the resistance after 3 minutes have passed since the power supply was intercepted.
(Surrounding temperature 0:~60:)
1
2
3
Normal
Abnormal
4.3k"~9.6k"
Open or short
Normal
Abnormal
15k"
Open or short
Motor terminal
or
Red-Black
White-Black
Normal
Abnormal
290"
Open or short
Normal
Abnormal
0.6k"~6.0k"
Open or short
Check points
(Refer to the thermistor)
Normal
PLA-P3AA
87.2"
104.1"
(Refer to the thermistor)
20
Abnormal
Open or short