Summary of Contents for Austdac HBRX4D

  • Page 1 Title HUBBUS FOUR CHANNEL DIGITAL RECEIVER TYPE HBRX4D USER MANUAL Document Number 125-253-12 Issue 1 OF 27...
  • Page 2: Revision Control

    Copyright 2020 This document remains the property of Austdac Pty. Ltd. It is subject to its recall and must not be reproduced in part or whole or its contents divulged to third parties without prior written approval from Austdac Pty Ltd.
  • Page 3: Table Of Contents

    6.2.4 DIN Rail Bus ......................... 17 6.2.5 Relay Terminals (1 to 4) ....................17 7 Configuration and Parameters ....................18 7.1 Configuration Process ......................18 7.2 Parameter Summary ......................19 HubBus Four Channel Digital Receiver 3 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 4 8.2 MODBUS Registers ......................23 8.2.1 Device Identification ..................... 24 8.2.2 Information ........................24 8.2.3 HubBus Digital......................25 8.2.4 HubBus Datalink ......................25 9 Specifications ..........................26 HubBus Four Channel Digital Receiver 4 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 5: Tables

    Table 7: (2) LED ........................... 14 Table 8: (3) LED ........................... 14 Table 9: (4) LED ........................... 14 Table 10: HBRX4D Terminals ....................... 16 Table 11: Parameter – Logic Function ..................19 Table 12: Parameter – HubBus Output Address ................19 Table 13: Parameter –...
  • Page 6: Introduction

    1.2 PURPOSE This document is the user’s manual for the HubBus four channel digital receiver (HBRX4D). It provides an overview and a detailed description of the installation, use and operation of the HubBus four channel digital receiver. This document does not contain detailed information concerning the operation of the HubBus system.
  • Page 7: Warnings And Precautions

    WARNING: If the HBRX4D is used in a manner not specified by Austdac then the protection provided by the HBRX4D may be impaired. WARNING: This product may contain chemicals known to the State of California to cause cancer and birth defects or other reproductive harm.
  • Page 8: Precautions

    Mains supply fluctuations are not to exceed ±10% of the nominal supply voltage. • 2.3.1 USER ACCESS There are no user serviceable parts within the HBRX4D. The user should not open or disassemble the HBRX4D. 2.3.2 STORAGE, INSTALLATION, USE AND MAINTAINANCE REQUIREMENTS The HBRX4D should only be installed, operated and maintained by qualified personnel in accordance with the condition of safe use as outlined in the certificate.
  • Page 9: Overview

    3 Overview 3.1 GENERAL DESCRIPTION HubBus four channel receiver with digital (relay) outputs. The HBRX4D can receive from just a few (from 1) through to many digital (up to 2048) signals (ON, OFF or FAULT) from a HubBus network to control the four relay outputs directly or via complex multi-term logic functions.
  • Page 10: Operation

    In addition to this the HBRX4D has a second set of force guided contacts which are used to indicate the current state of the relay contacts. If a fault is detected and the relays are potentially in a ‘stuck’...
  • Page 11: Figure 3: Multi-Term Logic Layout And Function

    When logic resolver outputs are fed back into the HubBus channel database the designer should ensure that these feedback channels are not modified by other field devices or via the MODBUS interface. HubBus Four Channel Digital Receiver 11 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 12: Installation

    4 Installation 4.1 ENCLOSURE The HBRX4D should be mounted in a host enclosure providing protection against dust and moisture. A minimum ingress protection of IP54 is recommended. 4.2 MOUNTING The HBRX4D should be mounted on an NS 35 DIN rail.
  • Page 13: Front Panel

    HubBus Sync pulse detected. Driven by the HubBus interface. YELLOW HubBus interface board lost communication to main module. Check line power Double switch. Table 2: SYNC LED HubBus Four Channel Digital Receiver 13 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 14: Table 3: +V Led

    Relay 3 fault detected Table 8: (3) LED 5.1.1.9 Colour Flash Rate Description YELLOW Solid Relay 4 energised YELLOW Fast Relay 4 fault detected Table 9: (4) LED HubBus Four Channel Digital Receiver 14 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 15: Inner

    Power source selection: A. HubBus line powered B. External power supply This switch is not applicable or functional on the HBRX4D as it must be powered from an external power supply. It is not capable of being line powered. 5.2.2 Config Port Four pin TTL level configuration port.
  • Page 16: Terminals

    6 Terminals 6.1 TYPE The PCB terminal connector is a Phoenix Contact style with 5.08mm pitch. Austdac supplies the module with either a 90˚ free hanging push-in spring terminal plug. Figure 6: Terminal Plug 6.2 LAYOUT Table 10: HBRX4D Terminals 6.2.1 Power...
  • Page 17: Hubbus

    Earth points. 6.2.3 MODBUS This is an RS485 MODBUS port at 19,200bps used for configuration. The HBRX4D is considered a slave device on the MODBUS network and therefore must be interrogated by a master device. Refer to the configuration section of this manual for instructions on setting network addresses etc.
  • Page 18: Configuration And Parameters

    Handheld Programmer User Manual” (125-198-12) for further information. 7.1 CONFIGURATION PROCESS This unit may be used in a safety function. Only the Austdac Handheld programmer, type HHP1-H, may be used to configure the HubBus safety devices. Configuration of safety devices follow the below process: 1.
  • Page 19: Parameter Summary

    NAND Table 11: Parameter – Logic Function 7.2.1.2 Relay (Logic) Status HubBus Output Address Feedback or returned value from the logic resolver to be transmitted by the HBRX4D and/or used as input to other logic functions. Value Limit (channels) Minimum...
  • Page 20: Latch Reset Address

    The logic resolver may equate (have input defined for) up to 2048 channels. Each channel input may have one of 4 states defined as the input term. HubBus Four Channel Digital Receiver 20 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 21: Examples

    Modbus address parameter, care must be taken not to have multiple devices with the same address on the bus. Value Limit (seconds) Minimum Maximum Step Default Table 17: Parameter – Modbus Address HubBus Four Channel Digital Receiver 21 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 22: Rs485 Enable

    It enables the Modbus RS485 port on the terminal connector and DIN rail bus. Value Meaning Enabled Port enabled Disabled Port disabled Default Disabled Table 18: Parameter – RS485 Enable HubBus Four Channel Digital Receiver 22 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 23: Modbus

    Code 4 / Read Input Registers: 64 words o Code 15 / Write Multiple Coils: 256 bits o Code 16 / Write Multiple Registers: 64 words Modbus Address: Message delay: 10ms HubBus Four Channel Digital Receiver 23 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 24: Device Identification

    “HBRX4D” Module 1028 N/A, returns “” Identifier Austdac Serial 1032 Austdac format serial number in the following format: “YYMMnnnn” F/W Ver. 1036 Firmware version of the main microcontroller, most Main significant byte is the major and the least significant byte is the minor version number.
  • Page 25: Hubbus Digital

    Combined 3v3 and 3v6 diagnostic Table 20: Modbus Registers – Information Data Displayed value = (DATA / HIGH) * SCALE 8.2.3 HubBus Digital 8.2.4 HubBus Datalink HubBus Four Channel Digital Receiver 25 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 26: Specifications

    EN50205 type B Contacts 2 x CO with force guided contacts (2 set for safety diagnostics) Contact material Ag-Cu-Ni + 0.2μm AU Terminals NO - COM - NC HubBus Four Channel Digital Receiver 26 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...
  • Page 27: Table 21: Specifications

    2A @ 24VDC Maximum switching power 2000W(VA) Contact resistance ≤100mΩ / 28V / 100mA Insulation Double or reinforced @ 250VAC, Tested at 4000V/50Hz/1min Table 21: Specifications HubBus Four Channel Digital Receiver 27 OF 27 125-253-12 HBRX4D USER MANUAL Issue: 01...