If further information is required by the purchaser regarding an installation, application, or maintenance activity, please contact an Insight Control representative or the installing contractor. SAVE THIS MANUAL FOR FUTURE REFERENCE...
The setpoint range is from 20-25°C with a factory default of 22.5°C. Leave the controller in “Auto” mode to work automatically off setpoint for heating or cooling based on return and supply air temperature. Insight Control TRI2 Installation Manual...
Most importantly, the room/return air sensor should always be protected from direct sources of heat such as direct sunlight and office equipment. The integrated room sensor may be replaced with an Insight Control room sensor (C-RS-10K-TL) if required. The supply air sensor should be mounted inside the supply air duct upstream from the damper.
Page 7
Supply Air Sensor The following table lists some commonly reported fault conditions and suggested corrective action. Further assistance may be obtained from Insight Control support on 1300 665 831 if needed. Symptom Suggested remedial action Motor drives the wrong way Check Actuator wiring.