CO2 eSENSE SE-0010 Installation Manual

Co2 transmitter and alarm

Advertisement

Quick Links

eSENSE
CO
Transmitter and Alarm
2
Installation & Manual
SE-0010, SE-0012, SE-0013, SE-0014
Rev. 22 November 2015
© 2015, CO2Meter.com. All Rights Reserved.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the eSENSE SE-0010 and is the answer not in the manual?

Questions and answers

Summary of Contents for CO2 eSENSE SE-0010

  • Page 1 eSENSE Transmitter and Alarm Installation & Manual SE-0010, SE-0012, SE-0013, SE-0014 Rev. 22 November 2015 © 2015, CO2Meter.com. All Rights Reserved.
  • Page 2: Table Of Contents

    Table of Contents General ............................3   Opening the Housing ........................3   Recommended Mounting Height from Floor ................4   Dimensions ..........................4   Electrical Connections ........................ 4   Buzzer & Jumper Settings ......................6   LED Display Configuration ....................... 7  ...
  • Page 3: General

    General The eSense alarm is designed to measure carbon dioxide (CO ) in rooms. It displays the measured CO value in ppm (parts-per-million) on the LCD. LEDs give an overview of the value. On alarm models, an acoustic alarm sounds when the CO goes above the set value.
  • Page 4: Recommended Mounting Height From Floor

    The locking hooks will then be released. Recommended Mounting Height from Floor - 18-36 inches for OSHA, CO2 storage applications, fermentation IAQ level applications - 48-60 inches for LEED, Indoor Air Quality applications - As required for custom indoor horticultural cultivation applications...
  • Page 5 Terminal Function Electrical data Remarks Power (+) 24 VAC/DC+ (+-20%), 2W Power ground (-) 24 VAC/DC- System voltage reference OUT1 Analog Output 1 (+) 0-10 VDC 0-2,000 ppm CO default 0-9,999 ppm CO OSHA 0-2,000 ppm CO LEED OUT2 Acoustic Alarm Buzzer Push button silences the acoustic SE-0010, 0013,0014...
  • Page 6: Buzzer & Jumper Settings

    Buzzer & Jumper Settings Models SE-0010, SE-0013, SE-0014 Analog Output 2 Voltage & Buzzer Only Model SE-0012 only. Analog Output 2 options: 0-10V Jumper Settings 4-20mA Jumper Settings Figure 4. The upper part of the eSense PCB seen from the back with the jumper in voltage (default) or current position.
  • Page 7: Led Display Configuration

    Theory of Operation The CO2 sensor inside this meter uses NDIR (non-dispersive infrared) technology to sense, as a function of transmitted light, the concentration of CO2 in the air. It has been factory calibrated to operate within the specified range and precision.
  • Page 8: Manual Calibration

    Manual Calibration There are 2 methods of manual calibration: 1. Fresh Air (400ppm CO2) Calibration: if Din3 is shorted for a minimum time of 8 seconds, the internal calibration code bCAL (background calibration) is executed. The sensor must be operating in a fresh air environment (400 ppm CO ).
  • Page 9: Emc Directives

    Addtional Notes The sensor accuracy is defined at continuous operation (at least 3 weeks after installation). Electronic products should be disposed of via a suitable recycling center. EMC Directives This product is in accordance with the EMC 2004/108/EC, 92/31/EEG including amendments by the CE-marking Directive 93/68/EEC.
  • Page 10: Liability

    Please use the original packaging (if available) when returning the meter to CO2Meter. Include the provided RMA number on the outside of the box, preferably on the shipping label. Secure the meter inside the package properly to prevent any damage during transit. Ship your meter to the address listed on your RMA paperwork.