Fire dampers (static & dynamic)

Advertisement

Fire Dampers (Static & Dynamic)
Installation Instructions
Breakaway Connections
Manufacturer's Recommendations
All moving parts of the damper must be inspected and cycled at intervals not greater than every six months and in accordance with the
latest edition of NFPA 90A, 92A, local codes and the actuator manufacturer. In addition, fuse links shall be removed and inspected for
corrosion. Dry lubricants are recommended. When UL is referred to in this document, it represents UL/ULC.