E.NEXT e.control.v04m - Voltage Control Relay Manual

E.NEXT e.control.v04m - Voltage Control Relay Manual

Advertisement

E.NEXT e.control.v04m - Voltage Control Relay Manual

Application

Voltage control relay e.control.v04m (hereinafter referred to as relay) monitoring in three phase circuits and to protect equipment against different types of voltage faults for example, low and high voltage, fase failure, phase sequence, asymmetry.
The relay meets requirements of IEC 60730-1.

Technical data

Table 1

Parameter name Value
Supply voltage, V 380, 400, 415 220, 230, 240
Supply terminals L1, L2, L3 L1, L2, L3, N
Frequency, Hz 50
Operating voltage range, V 266-540 154-312
Setting value, % U> 105-130
U< 75-95
Asymmetry setting, % 5-20
Trip delay, s <0,5
Hysteresis, % 2
Trip time for incorrect phase sequence and phase failure, s <0,5
Delay error, % ± 10%
Output contacts 1NO+1NC
Current rating 8A/250В АС1
Electrical live 105
Mechanical live 106
Protection degree IP20
Pollution degree 3
Altitude ≤ 2000
Operating temperature, °C -20...+55
Permissable relative humidity, % less 50 at 40°C (without condensation)
Strange temperature, °C -30...+70
Wire size, mm2 0,5-2,5
Torque, Нm 0,5
Mounting DIN-raile

The product must be operated under the following environmental conditions:

  • non-explosive;
  • does not contain corrosive gases and vapors in concentrations destroying metals and insulation;
  • not rich conductive dust and vapors;
  • lack of direct exposure to ultraviolet radiation;
  • should not be significant shock or vibration.

Transport and storage are only permitted in the original packing.

Wiring diagram and dimensions

Wiring diagram
Dimensions

Installation and operating

The relay is installed in a plastic or metal box on a standard DIN-rail width 35 mm with latches having two fixed positions.
The protection settings are set using the adjustments on the front panel of the device. During operation, the LEDs signal the operation or operation of the relay protection (see Fig.3.). The lower switch can not be set as shown in Fig.4
Installation and operating - LED Indication
Fig.3

Output indicator
<>U Over/under voltage indicator (U>: illuminate; U<: flash)
Fails Phase failure indicator
Asy Asymmetry indicator
Seq Phase sequence indicator

Installation and operating - Lower switch setting
Fig.4

Safety requirements

  1. The device should be installed, operated and maintained by qualified personnel.
  2. Don't dismantle or repair the device whether it operates normally, otherwise no responsibility is assumed by manufacturer or seller.
  3. Please refer to wiring diagram when connecting.
  4. Never use the product at the site which can be invaded by corrode gas, strong sunshine light

Warranty

Average life — 5 years, subject to the requirements of installation, operating, ambient conditions, transportation and storage.
Product Warranty period — 1 year from the date of purchase, subject to the requirements of installation, operating, ambient conditions, transportation and storage. The warranty does not apply to breakers:

  • having mechanical damage;
  • other damage caused by improper transportation, storage, assembly and installation, improper operation;
  • with the following independent, tamper and / or repair of the product.

Incorrect or impermissible use or non-compliance with these instructions invalidates our warranty provision. No modifications or alterations o the devices are permitted.

Provider address:
E.NEXT.Company Ltd.
Bulgaria, Varna, Rodopi str. 11
tel.: +359 87 7077123
e-mail: info@enext.com, www.enext.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download E.NEXT e.control.v04m - Voltage Control Relay Manual

Advertisement

Need help?

Need help?

Do you have a question about the e.control.v04m and is the answer not in the manual?

Questions and answers

Table of Contents