Intelligent MDU
Input Voltage Upper Threshold - the input voltage above which an alarm is raised, sending
a trap or email if enabled.
Shed Outputs on First Input Lost - if the first power supply is removed outputs are shed for
which shedding has been enabled.
Output configuration
Name - the label for the output. Up to 7 characters may be used.
Switch Lock - allows the switch to be locked on or off. When password protection is applied
to this screen it will prevent unauthorised users from altering the status of a locked output.
Fuse Alarm - enables or disables the fuse failed alarm for this output.
Can Shed - In some systems, a secondary input (a backup generator for example) may only
be able to supply a limited load current. For this reason, when the back up supply is selected
it may be necessary to lose certain outputs. Enabling Can Shed for an output indicates it can
be shed when the main power supply is lost.
Startup Delay - the time to wait before initialising the output. (on some models only) This
allows outputs to be turned on in a sequence reducing alarms or reducing start up current
surges. Valid times are between 0 to 15 seconds.
Stop Delay - determines how long to wait before shedding or switching off the output. This is
intended to power down outputs in an orderly way, helping to prevent unnecessary alarms.
The permitted delay is 0 to 15 seconds.