Mitsubishi Electric PAC-USSEN001-FM-1 Installation Instructions Manual page 2

Flush mount room temperature sensor

Advertisement

PAC-USSEN001-FM-1
4. Troubleshooting
4. Troubleshooting
Issue
Sensor reads 1kΩ or less
Sensor or wires are shorted together or to ground
Sensor reads 13kΩ or more
Sensor or wires have been damaged and are open
Erratic readings
Loose wire connection or possibly moisture on the wires/sensor
PAC-USSEN001-FM-1
6. Thermistor Curve
6. Thermistor Calibration Table
Specifications are subject to change without notice.
Possible Cause
9
© 2018 Mitsubishi Electric US, Inc.
11
© 2018 Mitsubishi Electric US, Inc.
PAC-USSEN001-FM-1
5. Setting Indoor Units
5. Setting Indoor Units
When the Sensor is connected to the indoor unit and room temperature detection position is changed, reset
the setting of "Set temp 4-deg. Up" in the heating mode as shown below:
• K control models
DIP switch Nos 1-6 on the control PCB of the indoor unit
• M-NET control models
DIP switch Nos 3-8 on the control PCB of the indoor unit
• A control models
Refer to A-control air conditioner Service Technical Guide
Specifications are subject to change without notice.
This device is designed and intended for use in the residential,
commercial and light-industrial environment.
Please be sure to put the installer's contact address/telephone number on
this manual before handing it to the customer.
MITSUBISHI ELECTRIC US, INC.
www.mitsubishielectric-usa.com
Toll Free: 800-433-4822
MEUS DOC# CE-18001-L001, May 2018