CONTENTS Three-Phase Meter Configuration Guide ......1 Preface ....................1 Symbol interpretation ..........2 Introduction ............... 3 Meter installation ............3 Setting Feed-in limitation of the inverters ..5 Check the installation results ........8 Communication ............... 8 Display function ............14 Troubleshooting ............
Three-Phase Meter Preface Table of adapted inverters Product Type Model SOFAR 3-12KTL*-G3 SOFAR 15-24KTL*-G3 Three-phase inverters SOFAR 25-50KTL*-G3 (PV) SOFAR 60-80KTL*-G3 SOFAR 100-136KTL HYD 5-20KTL-3PH Three-phase inverters (Energy Storage) ME 5-20KTL-3PH Scope of application This product manual describes the installation, electrical connection, debugging, maintenance and troubleshooting of Three-Phase Meter.
Three-Phase Meter 2. Introduction This scheme is a 1-to-1 communication mode, and one set of electricity meter cannot correspond to multiple grid-connected inverters. Reference Nominal Type Appearance Frequency Adapted CT Model Voltage Current HY94C5-200, 1.5(6)A 200A, 2KV, -30~75℃, Φ24 Three-Phase DTSU666 3x230V/400V 50Hz/60Hz...
Page 6
Three-Phase Meter 3.2 AC current Conductor Cross-sectional Area Range ≤16 mm2 3.3 RS485 cable The meter communication is in RS485 communication mode, and the port rate can be set to 1200,2400,4800, and 9600 (default). The device communication address defaults to 01(please see instrument factory number or crystal display screen).
Three-Phase Meter Only Meter CT is installed between the load and the grid, CT with arrow with the arrow in the figure (arrow points to the grid). CT without an arrow, the direction of the arrow represents the direction of P1 (inverter) to P2 (power grid). ①...
Page 8
Three-Phase Meter Parameter setting (long ---Long press ↓ to enter press ↓ to enter the menu) 1. Set the system time 2. Clear up the power generation capacity 3. Clear the event record 4. Import the safety gauge parameters 5. Switch on machine control Some settings require a password 6.
Page 9
Three-Phase Meter Advanced setting ---Press the OK key to enter (back to the menu) 1. Set the system time 2. Clear up the power generation capacity 3. Clear the event record 4. Set up safety regulations for countries 5. Switch on machine control 6.
Three-Phase Meter 1. If you only need to monitor the power, you don't need the Feed-in limitation function: 20. Set Feed-in Limitation→Disable 2. If you need to connect the meter to realize the Feed-in limitation function: 17. Set Feed-in limitation→Enable 20.
Page 14
Three-Phase Meter Combined Phase Power Factor PFt=0.500 A Phase Power Factor Pfa =1.000 B Phase Power Factor PFb =0.500 C Phase Power Factor PFc =-0.500 ·Protocol: DL/T645-2007 display 4 and 5,Protocol: Modbus-RTU display 6 and 7. ·The above interface is used to show the meaning of the display content. Due to the different functions of the instrument, the display symbols will increase or decrease.
Page 15
Three-Phase Meter 6.1 Programming operation Key description: "SET" key means "OK", or "Cursor shift" (when entering the number), "ESC" key means "exit", "key" "means" add ", because only the key can only" add ", not" subtract ", when you add the number to the maximum value, the number will start from 0. Enter a password (default: 701).
Three-Phase Meter 7. Communication Communication protocol: complied with the requirement of Modbus communication protocol. The following table is the common Modbus protocol address table. NOTE Modbus-RTU protocol read command is 03H, write command is 10H. 7.1 Modbus protocol address table Data Data Instructions of...
Page 17
Three-Phase Meter Data Instructions of Data R / W Parameter Parameter length type parameters property address code Word Backlight time 16bit with 000BH B.LCD control(s) signal Single-precision floating point size 16bit with Endian end mode (0: 000CH signal ABCD;1: CDAB;2: BADC;3: DCBA;) Protocol switching 16bit with...
Page 18
Three-Phase Meter Single- precision 200CH floating point Three phase Single- current data, precision 200EH Unit A(×0.001A) floating point Single- precision 2010H floating point Combined active Single- power, Unit precision 2012H W(×0.1W) floating point Single- A phase active precision power, Unit 2014H floating point W(×0.1W)
Page 19
Three-Phase Meter Data Instructions of Data R / W Parameter Parameter length type parameters property address code Word A phase power factor (positive number: Single- Inductive, negative precision number: 202CH floating point capacitive) (Invalid for three phase three phase) (×0.001) B phase power factor (positive number:...
Page 20
Three-Phase Meter Single- (current)Total reactive energy of precision 1046H Q3Eq the third quadrant floating point (current)Total Single- reactive energy of precision 1050H Q4Eq the fourth floating point quadrant NOTE When the ratio of the voltage transformer is 1, the data of read voltage transformer ratio register UrAt is 10.
Page 21
Three-Phase Meter Return frame:01 03 04 45 9C 38 00 3C D1 (01 is table address,03 is read command,04 is read register return data number, 459C3800 is floating data,3CD1 is CRC16 check code)Ia measurement=0x459C3800(single precision floating point)×current ratio×0.001=4999(decimalist)×20×0.001=99.98A. Read current positive active total energy ImpEp (101EH): Read command frame:01 03 10 1E 00 02 A0 CD (hexadecimal,01 is table address,03 is read command,101E is current positive total active energy address, 0002 is single-precision floating point data length,A0CD is CRC16 check code).
Three-Phase Meter 8. Troubleshooting Problems Reason Troubleshooting 1. If the wiring is incorrect, please follow the correct wiring instruction (see wiring diagram). 1. The meter wiring is 2. If the power supply voltage is incorrect. No display abnormal, please supply power 2.
Three-Phase Meter 9. Interface description There are two interfaces respectively. 9.1 Type 1 (two screen buttons) Definition Function Remarks RS485A RS485 Differential signal + RS485A RS485 Differential signal + Wired monitoring or Inverter cascade RS485B RS485 Differential signal- monitoring RS485B RS485 Differential signal- Meter RS485 Differential Electricity Meter, RS485A...