SLAT Safe DC SDC-M Operating Instructions Manual

Micro-ups dc 12 v-15 v-24 v, dmr, rs, modbus / bacnet ms/tp

Advertisement

Quick Links

Safe DC SDC-M
Micro-UPS DC
SDC-M 12 V-15 V-24 V
DMR
RS
Modbus / BACnet MS/TP
EN Operating Instructions
MAN160006 | Aa | 2016.10

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Safe DC SDC-M and is the answer not in the manual?

Questions and answers

Summary of Contents for SLAT Safe DC SDC-M

  • Page 1 Safe DC SDC-M Micro-UPS DC SDC-M 12 V-15 V-24 V Modbus / BACnet MS/TP EN Operating Instructions MAN160006 | Aa | 2016.10...
  • Page 3 Autonomy duration Self-discharge Installation Positioning / Installation on support Connection Connection specifications Wiring Commissioning First configuration Subsequent configurations Operation Local report on product Remote report Alarm reports Communication Maintenance and troubleshooting SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 4: Technical Data

    Peak current 10.2 Mechanical characteristics 10.3 Environmental specifications 10.4 Standards Safety standards EMC standards 11. Warranty and Product Returns 11.1 Warranty 11.2 Product Returns Product under warranty Product not under warranty SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 5 For prolonged storage or disconnection, press the stop button back-up function. (see on Figure 4.2 in • chapter 4.4: Disconnect backup push-button) The backup is maintenance-free. Do not open it. • SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 6 MAN160006 | Aa | 2016.10 Directives and environment and public health protection The SLAT company and its product comply with directives and are committed to protecting the environment and public health. SLAT manufactures all its products in accordance with RoHS and WEEE environmental directives.
  • Page 7: General Information

    SLAT has been designing and manufacturing all its products in accordance with the ISO 14001 standard • since 2007. SLAT recycles its products at the end of their life cycle, by means of its recycling program. (For end-of- • life recycling, the backup can easily be removed by qualified professionals independent from SLAT.)
  • Page 8 Contains additional information. Non-compliance will not cause damage to equipment or personal injuries. CAUTION! Equipment and goods can be seriously damaged or people seriously injured if the precautions for use are not followed. DANGER! Non-compliance may result in serious injury or death. SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 9: Operating Principle

    Ultra-compact / Plug and Play, parallel configuration without accessories. • Performs self-diagnostic and that of its environment. • Choice of configuration in either Modbus or BACnet MS/TP via the website www.slat.com. • Lead-free, cadmium-free backup, 100% recyclable. • Service life of more than 10 years.
  • Page 10: Schematic Diagram

    Attachment to clip the box to the DIN rail or to fix it on a Clip mounting plate (depending on the clip’s position) Rail attachment Attachment to fix the box to the DIN rail. Table 4.1: Elements on the product faces SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 11: Scope Of Delivery

    MAN160006 | Aa | 2016.10 Available references The list of available product references is to be found at www.slat.com. The references are designed as follows: SDC- M 12V 2 D DMR RS ① ② ③ ④ ⑤ ⑥ ⑦ Meaning...
  • Page 12: Energy Storage

    Energy storage Available storage option SLAT products are combined with batteries or backup systems. They are used as emergency supplies in the event the mains voltage disappears. The available autonomy then depends on the capacity of the built-in backup. In the SDC-M the backup system is already built-in (Smart Backup Inside). For the DMR version of the SDC-M, one...
  • Page 13: Self-Discharge

    1h48 15 W 1h13 20 W 0h55 25 W 0h44 30 W 0h36 Table 5.2: Autonomy vs Power vs used Backup Self-discharge The self-discharge current for the SDC-M is 70 mA. SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 14: Installation

    Open the four mounting clips (red parts) by pushing them outwards with the help of a flat-head screwdriver so that they are in the position shown in Figure 6.2. Attach the product in the way indicated in Figure 6.2 using four screws. SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 15: Connection Specifications

    CAUTION! To avoid breaking the screw terminal, comply with the screw tightening torque indicated in Table 6.1. SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 16 Connect the power supply to the mains Below the three-point screw terminal (top left), the type of wire is indicated by 3 symbols: Line wire • N Neutral wire • Ground wire • SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 17 After connecting the ground wire, the neutral and line wires can be connected. Once the connections have been made, the upstream circuit-breaker can be closed. To complete the installation, the LED status must be verified to be green. SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 18: First Configuration

    (see chapter 4.7). The communication parameters can be configured via the RS485 serial connection. SLAT provides a software that allows simple configuration of these parameters. This software is available for download at www.slat.com...
  • Page 19 Press the disconnect backup push button for 10 seconds (see Figure 4.2) to return to the factory • configuration (the status LED changes temporarily its colour) and then reconfigure the product following the steps described above (chapter 7.1). SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 20: Operation

    Max voltage 60 V DC / max current 1.1 A • Signal: • “mains fault” or “backup fault” or “output overload” or “output short-circuit” or “charger fault” or “pre- alarm end of autonomy “ SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 21 • The product communicates its information on an RS485 serial connection via the Modbus or BACnet MS/TP protocol. The protocol activated by default is Modbus. It can be configured using a software SLAT makes available www.slat.com . The information and explanations on how to configure the product are described in chapter 7.
  • Page 22 10000 Number_Of_APDU_Retries Device_Address_Binding Database_Revision Max_Master 0…127, default 127 RW-E Max_Info_Frames 1…255, default 1 RW-E R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash Table 8.5: BACnet MS/TP variables SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 23 OVERRIDDEN: 0 OUT_OF_SERVICE: 0 Event_State NORMAL (0) Out_Of_Service FALSE (0) Units Milliamperes (2) R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash Table 8.7: Analog Value Object 2 SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 24 OVERRIDDEN: 0 OUT_OF_SERVICE: 0 Event_State NORMAL (0) Out_Of_Service FALSE (0) Units Milliamperes (2) R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash Table 8.9: Analog Value Object 4 SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 25 OVERRIDDEN: 0 OUT_OF_SERVICE: 0 Event_State NORMAL (0) Out_Of_Service FALSE (0) Units No units (95) R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash Table 8.11: Analog Value Object 6 SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 26 OVERRIDDEN: 0 OUT_OF_SERVICE: 0 Event_State NORMAL (0) Out_Of_Service FALSE (0) Units No units (95) R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash Table 8.13: Analog Value Object 8 SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 27 OVERRIDDEN: 0 OUT_OF_SERVICE: 0 Event_State NORMAL (0) Out_Of_Service FALSE (0) Units No units (95) R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash Table 8.15: Analog Value Object 10 SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 28: Maintenance And Troubleshooting

    DANGER! At no time should the box be opened, even for maintenance purposes. For a proper functioning of the product, it is necessary to ensure that the ventilation grilles are dust-free. SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 29: Troubleshooting

    Table 9.1: Problems, causes and solutions For additional technical assistance, contact the SLAT hotline +33 4 78 66 63 70. For an RMA request (authorization to return goods), refer to chapter 11.2 . No equipment may be returned without prior issuance of an RMA number.
  • Page 30: Electrical Characteristics

    Circuit breaker to be provided upstream Curve C or D (recommended rating 2 A) Table 10.1: Mains input electrical characteristics Current behaviour: Inrush current at start-up Figure 10.1: Oscillogram - inrush current SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 31 Medium curve Input current (20 A / DIV) Lower curve Output voltage (10 V / DIV) Time scale 200 ms / DIV Table 10.3: Description of the oscillogram - starting behaviour SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 32: Electrical Output Characteristics

    > U + 10% Short-circuit if < 6 V or I > 30 A output Table 10.4: Electrical output characteristics Figure 10.3: Output voltage vs User current SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 33: Functional Characteristics

    (voltages and load current, backup, autonomy, internal electronic temperature) The basic communication protocol is Modbus The configuration software supplied on the web site www.slat.com, makes it possible via an RS485 cable to choose the BACnet MS/TP protocol, to configure the communication parameters and to choose the functioning mode.
  • Page 34: Mechanical Characteristics

    75% load -5 … +60°C Relative humidity in storage 10 … 95% operating 20 … 95% Altitude Above 2,000 m, the temperature decreases by 5% every 1,000 m. Table 10.7: Environmental specifications SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 35: Safety Standards

    EN 61000-6-4 (March 2007) Emission standard for industrial environments (generic standard) Emissions EN 55022 (March 2007) + Emission of conducted and radiated radio- A1 (May 2008) electric interference (class B) Table 10.9: EMC standards SLAT Operating instructions ©2016 SLAT Subject to change www.slat.com...
  • Page 36: Warranty

    11.2 Product Returns Product under warranty For the maintenance of your products under warranty, SLAT offer the best solution to facilitate your repairs and minimize lead times: Contact the Customer Service department using the form available on our web site www.slat.com...
  • Page 37 Company / Complete Address / Phone / Email • Exact model of the product (indicated on the product label) / SLAT reference (indicated on the product • label, code number) / Serial No. / Quantity / Problems(s) encountered (describe the faults encountered with the product) The form to request the RMA number is also available at www.slat.com.
  • Page 38 69543 Champagne au Mont d'Or Cedex FRANCE Tel.: +33 478 66 63 60 Fax: +33 478 47 54 33 e-mail: comm@slat.fr SLAT GmbH Leitzstraße 45 70469 Stuttgart Deutschland Tel.: +49 711 899 890 08 Fax: +49 711 899 890 90 www.slat.com...