Page 1
Installation and operating manual Duct smoke detector RM-O-3-D to provide the control input signal for fire dampers and smoke protection dampers General building inspectorate licence Z-78.6-125 Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)
• Installation ing on any electrical equipment. • Electrical connection • Commissioning • Maintenance • Cleaning Other applicable documentation The general building inspectorate licence no. Z-78.6-125 also applies. Download: www.troxtech- nik.com Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)
General information regarding safety Correct use Only specialist personnel are allowed to perform The RM-O-3-D duct smoke detector is used to sig- the described work on the duct smoke detector. nal to and release fire dampers and smoke Only skilled qualified electricians are allowed to protection dampers to prevent fire and smoke from work on the electrical system.
① extremely important that it is detected at an early ② stage. ③ The RM-O-3-D duct smoke detector is used to sig- ④ nal to and release fire dampers and smoke protection dampers. The duct smoke detector op- ⑤ erates on the principle of light scattering and...
2) If there is an alarm because smok e has been detected (smoke incident or maintenance), you can only reset the LED blinking duct smoke detector with the reset button after the duct smok e detector is free from smok e again. Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)
• No duct smoke Packaging detector Properly dispose of packaging material. • Data transmission to duct smoke detector has failed Alarm relay contact 250 V 2 A (release, contamination) Weight 0.7 k g Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)
Installation in FK-EU washers and wing nuts in the fire damper (no adapter required). ⑤ ① ② ④ ③ ① ② damper ③ Galvanised: A00000043410 Stainless steel: A00000043411 ④ ⑤ Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)
You can also have the duct smoke detector switch of the fan as long as the acceptable switch rating (see Seite 7) is not exceeded. Higher switch ratings require auxiliary relays. Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)
OPENS, either by means of a spring return ⑦ actuator or a pneumatic actuator. Note Fire dampers whose release mechanism includes electromagnets can be opened manually. All operating, warning and alarm functions are de- scribed on page 4. Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)
② • The sensor head has to be replaced after 8 years released. ③ • All the other parts of the RM-O-3-D duct smoke detector are not subject to wear and hence mainte- Fitting the sensor head ② ③ nance-free.