When the switches are set as shown on page 16
the output contacts of SPAS 348 C have the
following functions:
Contact
Relay
Function
X2/12-13
SS1
Earth fault detected only by the delayed alarm stage U
X2/3-4
TS1
CPFP (= Circuit-Breaker Failure Protection)
X2/9-11
SS2
Blocking signal to the earth-fault current relays of the feeders
X2/1-2
TS2
Circuit breaker trip signal (infeeder circuit breaker)
X2/7-8
SS3
Alarm signal, overcurrent trip
X1/15-16
TS3
Trip signal U
X2/5-6
SS4
Alarm signal, earth-fault trip
X1/11-14
TS4
Not used
> for bus section breaker or feeders most prone to faults