VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual Catalogue Chapter I General Feature ............................1 Chapter II Technical Data ............................1 Chapter III Structure and Wiring ..........................1 Chapter IV Installation ...............................4 Chapter V System setup ..............................4 Chapter VI Use and Operation............................9 Chapter VII Fault Analysis and Elimination ......................
8 logic zones with one sounder beacon VI-6737 and one output interface VI-6727 or VI-6721 of each. VI-6811 is considered as an economic solution for small projects such as residential house, restaurant, hotel, bank office, telecom stations, etc.
Page 4
O - - C o n tr o l I n te r f a c e Figure 3.3 VI-6811 is equiped with LED screen and indicator. The functions are shown below: ◇ Main Power (Green): The indicator is illuminating in green when the panel is operating well with main power supply.
Page 5
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual Figure 3.4 3.5 Wiring Terminals: Figure 3.5 3.5.1 The Sounder Output terminals are available for one circuit of conventional sounder, such as VC-6734 Conventional Sounder Strobe. In order for the line-fault, a 2k resistor is required at the end of line.
3.6 Loop wiring VI-6811 has one single detection loop, which is capable for both Class A and Class B wiring. But for A circuit wiring, it is highly recommended to install Isolate Interfaces at the first and last device as shown below. Please do ensure the loop polarity is correct during wiring.
Chapter V System setup With regard to VI-6811 panel, we need go through several major settings, including device address and type, system time, printer, relay output, sounder mode, etc. If needed, enter the relevant menu and directly set them. Enter the system setup menu and enter the relevant password.
Page 8
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual System Clock Initial fire Time Devices Fire Fault Time Figure 5.2 (3) Meaning of display position in Figure 5.2: System clock: Current time of the system. Initial fire: In case of one or more fire events, the address number of initial fire will be displayed in this position, (in case of no fire, “——”...
Page 9
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual “Search” key: With the cursor in the detector address selection bit, press “Search” key and add 1 (add the number to reach 9, and then automatically reset to 0); with the cursor in the type selection bit, press “Search” key...
Page 10
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual Step 3: Set address #24 as last point Press “Shift” button to move cursor to the tens digit of the second number, and then press “Search” Operation: button to add one number until “2” appears. Then move cursor to the position of single digit and press “Search”...
Page 11
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual Step5: Confirm and check Operation: Move cursor to the arrow right after the symbol of device type, press “Search” until “#” appears to save the above settings. DETECTOR SETUP MENU ON:01-24 S# OFF:00←...
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual There is one conventional sounder circuit on the panel. The Sounder Output on the Main Board can be used to connect with conventional sounder (reminder: EOL resistor 2K). And this setting can change the mode of sounder output.
Page 13
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual System time First fire First fire time Number of online detectors 09:54:36 09: 54 0 2 / 01 04/01 Fire alarm/total number Fault/total number Figure 6.2 In the above figure: 02 means the detector with 02 address alarms for the first time, “04/01” in the bottom row means that address #04 device is faulty.
Page 14
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual System time First fire First fire time Number of online detectors Fire alarm/total number Fault/total number Figure 6.4 6.7 Fault of open-circuit If there is open-circuit occurred in the detection loop, fault message will be reported to the panel within 60s.
VI-6811 Intelligent Fire Alarm Panel Installation and Operation Manual No display on LCD Screen or 1. The connection of the display board is 1.Insert the plug tightly black screen loose. 2.Insert the CPU board tightly 2. CPU board is loose or is in wrong 3.Contact the manufacturer.
Page 16
Any quality problem may choose any of the following ways to contact us, we will wholeheartedly for your service. Company name:Tianjin VSAIL Intelligent Fire Technology Co.,Ltd Company address:No.401, Building 6, No.1 Xinxing Roard, Wuqing Development Zone, Tianjin, 301700, China Website:www.vsailglobal.com...