VB-6611S Conventional Alert Base
Installation and Operation Manual V1.00
Beijing VSAIL Fire Protection Equipment Co. Ltd.
Building 32, Huilongsen Technology Park,
No.99 14th Kechuang Street, BDA, Beijing, PRC
Feature
Used as an warning device to generate fire
alarm;
Installation and wiring same as detector
base;
Driven by detection circuit, no need for extra
power line.
Description
VB-6611S Conventional Alert Base is designed for the application inside a closed room. As an
warning device, the base will generate alarm sound when the detector detects a fire occurred.
Installed as a base, it is compatible with the range of VSAIL conventional detectors. It is usually
installed in hotel room, residential bedroom or other locations that are far away from the audible
and visual alarm.
Technical Data
Operating voltage:
Operating current:
Sound level
Tonal modification cycle
Environment
Weight
Dimension
Installation hole distance
Outline and Installation Dimension
Installation and Wiring
1) The flame resistant twisted-pair ZR-RVS-2×1.0~1.5mm
wiring.
2) Before the installation, please check whether the shell is intact without any damage, and
whether the label is complete.
3) The terminals of the alert base shall be connected as the following diagram:
Control panel terminal Zone Input+: connected with the alert base's position "1" or "2";
VSL3.928.010ASY
Standby current: 0mA
Temperature:-10℃~+55℃ Relative humidity≤95%,non-condensing
diameter of 102mm, height of 25.5mm
1
15VDC~28VDC
Action current: ≤ 4mA (12V)
>75dB at 1 meter
0.6~1.5S
67g
73mm
2
is recommended to be used for the
V1.00

Advertisement

loading

Summary of Contents for V-GREAT VB-6611S

  • Page 1 Description VB-6611S Conventional Alert Base is designed for the application inside a closed room. As an warning device, the base will generate alarm sound when the detector detects a fire occurred. Installed as a base, it is compatible with the range of VSAIL conventional detectors. It is usually installed in hotel room, residential bedroom or other locations that are far away from the audible and visual alarm.
  • Page 2 Usage and Operation Silence: Resetting the control panel can silence the alarm of the alert base. Loop capacity: Maximum 32 pieces of VB-6611S can be connected in one conventional detection zone. Attentions 1) If the alert base alarm cannot be started, inspect whether the alert base is damaged.