Signtex Lighting RAENB-PEN Series Installation Instructions And Owner's Manual

Rapier accessible exit sign

Advertisement

Rapier Accessible Exit Sign
Rapier Accessible Exit Master Remote System
INSTALLATION INSTRUCTIONS AND OWNER'S MANUAL
Fig. 1
HORIZONTAL MOUNT SINGLE FACE
STANDARD DEEP J- BOX
4" x 4" x 2 1/8"
REMOTE
CLASS 2 LOW VOLTAGE WIRING 18-22 AWG
DOUBLE FACE
STANDARD DEEP J- BOX
4" x 4" x 2 1/8"
REMOTE
CLASS 2 LOW VOLTAGE WIRING 18-22 AWG

J-BOX INSTALLATION

1.
See Fig 1: Install a 4" x 4" x 2 1/8" J-box with 1 ½" extension for Master sign and Remote signs. Position J-boxes
approx ¼" below finished panel surface and set in line, 12 1/8" apart for horizontal mount, and 8 ¼" apart for
vertical mount. NOTE- Location of J- boxes must be accurate to position the two signs correctly.
2.
See Fig 2: Attach low voltage output wiring to Terminal Block mounted on Master power supply assembly (some
fixtures may be shipped with wiring in place). Maintain color codes and polarities as shown.
3.
Connect AC input wiring 120/277 VAC to power supply in Master J-box with standard wire nuts and attach Ground
wire to J-box.
IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Disconnect AC power before servicing.
2. Refer to wiring diagram for proper connections.
3. All servicing should be performed by qualified personnel.
4. Consult your local building code for approved wiring and
installation.
5. Do not use outdoors.
6. Do not use this equipment for other than intended use.
Signtex Lighting
120/277
STANDARD DEEP J- BOX
VAC INPUT
4" x 4" x 2 1/8"
STANDARD 1 1/2"
12 1/8"
EXTENSION RING
MASTER
120/277
STANDARD
VAC INPUT
DEEP J- BOX
4" x 4" x 2 1/8"
12 1/8"
STANDARD 1 1/2"
EXTENSION RING
MASTER
SAVE THESE INSTRUCTIONS
220 VFW Avenue, Grasonville, MD 21638 P (410)827- 8300 F(410)827- 8866
VERTICAL MOUNT SINGLE FACE
MASTER SIGN POWER
Fig. 2
SUPPLY ASSEMBLY
J- BOX
RED
POWER FEED TO
TERMINAL BLOCK
20 AWG
(SUPPLIED)
BLACK
POWER
SUPPLY
MODULE
7. Do not let power cords touch hot surfaces.
8. Mount and secure the fixture at a location and height
to avoid ready access and tampering by unauthorized
persons.
9. The use of accessory equipment is not recommended by
the manufacturer and may cause an unsafe condition.
Series RAENB-PEN
120/277
VAC INPUT
STANDARD DEEP
4 X 4 X 2 1/8" J-BOX
1 1/2" EXTENSION
8 1/4"
120/ 277
VAC
PUSH- WIRE
L G N
TERMINAL BLOCK
SUPPLY
TO MASTER
BROWN
RED
BACK VIEW
07.21.01
TO REMOTE
RED
BROWN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RAENB-PEN Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Signtex Lighting RAENB-PEN Series

  • Page 1 5. Do not use outdoors. the manufacturer and may cause an unsafe condition. 6. Do not use this equipment for other than intended use. SAVE THESE INSTRUCTIONS Signtex Lighting 220 VFW Avenue, Grasonville, MD 21638 P (410)827- 8300 F(410)827- 8866...
  • Page 2 Rapier Accessible Exit Sign Series RAENB-PEN Rapier Accessible Exit Master Remote System 07.21.01 Rapier Accessible Exit Master Remote System Pendant Mount 12 1/8" CLASS 2 PUSH- WIRE CONDUCTORS OUTPUT TO TERMINAL BLOCK (BY OTHERS) REMOTE LED Driver Power Supply 18-20 AWG FROM 12-24 VDC MASTER...

Table of Contents