daviteq WS433-BL User Manual

Long range wireless bridges

Advertisement

Quick Links

USER GUIDE FOR LONG RANGE
WIRELESS BRIDGES WS433-BL
WS433-BL-MN-EN-01
This document is applied for the following products
SKU
WS433-BL
WS433-BL-RS485-M2
Item Code
WS433-BL-RS485-S2
1. Functions Change Log
HW Ver.
2.4
2. Introduction
WS433-BL is a range of Sub-Ghz wireless bridges to replace the RS485 cable or network. This wireless technology will
save time, labor cost & cable cost as well. LOS Distance is up to 6000m at baud rate 38400. Optional integrated IoT
gateway (iConnector) allows easily configure & diagnose remotely or monitoring / controls via any IoT Platform as welll.
The deployment of these wireless devices can be done in just 15 minutes!
HW Ver.
2.4
Long Range Wireless Bridge, Master, RS485, external antenna 0 dbi, M12-Female connector, 4-
pin, coding A
Long Range Wireless Bridge, Slave, RS485, external antenna 0 dbi, M12-Female connector, 4-pin,
coding A
FW Ver.
2.0
FW Ver.
Release Date
JUL-2019
DEC-2020
2.0
Functions Change

Advertisement

Table of Contents
loading

Summary of Contents for daviteq WS433-BL

  • Page 1 2. Introduction WS433-BL is a range of Sub-Ghz wireless bridges to replace the RS485 cable or network. This wireless technology will save time, labor cost & cable cost as well. LOS Distance is up to 6000m at baud rate 38400. Optional integrated IoT gateway (iConnector) allows easily configure &...
  • Page 2: Specification

    RF frequency band datasheets) ETSI EN 300 220, EN 303 204 (Europe) FCC CFR47 Part15 (US), ARIB Ready to comply STD-T108 (Japan)** Vietnam Type Approval Certification QCVN 73:2013/BTTTT, QCVN 96:2015/BTTTT (DAVITEQ B00122019) Data encryption AES-128 Ambient working temperature -40oC..+85oC Housing...
  • Page 3: Operation Principle

    5. Operation Principle 5.1 Add RS485 Wireless Bridge Slave into RS485 Wireless Bridge Master Step 1: Antenna settings for both master and slave NOTE: Use your hand to tighten the antenna on the sensor, not using tools. Step 2: 12-24VDC power supply for both slave and master via M12 connector Step 3: Bring the antenna of Wireless bridge Slave closer to the antenna of Wireless bridge Master.
  • Page 4 Step 4: When you hear a beep indicating the successful registration of Slave to Master, you are ready to use the product. WS433-BL replaces the traditional RS485 transmission line and wireless data transmission together. So after adding, the connection will be normal as traditional RS485 connection.
  • Page 5 RF transmit power: 15 dBm RF data rate: 50 kbps 5.3 LED of WS433-BL LED of WS433-BL will change state when RF data is received. For example: when we read WS433-BL Slave data from WS433-BL Master, the LED on the Slave will change.
  • Page 6 5.4 Checking connection with Modbus Tool Default offline address: The Wireless Bridge Master address is 200; The Wireless Bridge Slave address is 201; Other Modbus RTU devices have the address provided by the manufacturer. First, you need to prepare...
  • Page 7 Step 1: Connect Antenna, RS485 - configuration cable and power supply the wireless bridge;...
  • Page 8 Step 2: Open Modbus tool on PC You can download Daviteq Modbus Configuration Tool with the following link: https://filerun.daviteq.com/wl/?id=BaX6RFlaEySKSYHX2j5nYHKBgeWckrox Template File of WS433-BL Master: https://filerun.daviteq.com/wl/? id=cOS9c22bsg7PpRxNa1LAZZEVaZCuM3eq Template File of WS433-BL Slave: https://filerun.daviteq.com/wl/? id=qBnH0kCshk4cRhawWGOauDAMDqHRhT4g How to use the Modbus configuration software Unzip file and run file application "...
  • Page 9 Click “ Connect “ untill the Status displays “disconnected” to “connected“. It means the WS433-BL is being connected with computer; Next, we need to import the configuration file for WS433-BL by importing the csv file: Go to MENU: FILE / Import New / => select the template file.
  • Page 10: Mounting Bracket Installation

    6. Installation 6.1 Mounting bracket installation The mounting bracket is made from hard metallic material. Following to these steps as the below picture 6.2 IO Wiring Please wiring as shown below:...
  • Page 11: Installation Location

    Each cable includes wires which are marked labels according to types of connection. (user should not cut these labels before installation to avoid confusing) Red: PWR+(12...48VDC) Black: PWR-(OVDC) Green: White: Recommend to use 24VDC power. The signal cable from sensor should be protected by corrugated hose or the Φ16 plastic tube, keep the cable avoid high temperature areas.
  • Page 12: Troubleshooting

    No.11 Street 2G, Nam Hung Vuong Res., An Lac Ward, Binh Tan Dist., Ho Chi Minh City, Vietnam. Tel: +84-28-6268.2523/4 (ext.122) Templogger Pty Ltd Email: info@daviteq.com | www.daviteq.com Tel: 1800 LOGGER Email: contact@templogger.net Revision #17 Created Tue, Dec 15, 2020 4:25 AM by Kiệt Anh Nguyễn...

This manual is also suitable for:

Ws433-bl-rs485-m2Ws433-bl-rs485-s2

Table of Contents