Klein Tools NCVT1PKIT Instructions

Klein Tools NCVT1PKIT Instructions

Non-contact voltage and gfci receptacle test kit

Advertisement

Quick Links

ENGLISH
NCVT-1P (FIG. 1)
GENERAL SPECIFICATIONS
• Tester Type: Non-contact voltage detector
• Voltage Range: 50 – 1000V AC
• Frequency Range: 50 – 500Hz
• Operating Altitude: 2,000 meters (6,561 feet)
• Relative Humidity: < RH 80% non-condensing
• Operating Temperature: 32 to 104°F (0° to 40°C)
• Storage Temperature: 32 to 104°F (0° to 40°C)
• Power: 2 x 1.5V AAA batteries (included)
• Dimensions: 6" x 0.96" x 1.16" x (152 x 24 x 29 mm)
• Weight: 2.5 oz. (72 grams)
• Drop Protection: 6.6 ft. (2 m)
• Safety Rating: CAT IV 1000V
• Pollution Degree: 2
• Standards: Conforms to UL STD. 61010-1, 61010-2-030
Certi ed to CSA STD. C22.2 No. 61010-1, 61010-2-030.
Specifications subject to change.
To ensure safe operation and service of the tester, follow these instructions. Failure to observe
To ensure safe operation and service of the tester, follow these instructions. Failure to obser
To ensure safe operation and service of the tester, follow these instructions. Failure to obser
these warnings can result in severe injury or death.
these warnings can result in severe injury or death.
these warnings can result in severe injury or death.
these warnings can result in severe injury or death.
• It is important that users of this tester read, understand, and follow all warnings, cautions, safety information,
It is important that users of this tester read, understand, and follow all warnings, cautions, safety information,
It is important that users of this tester read, understand, and follow all warnings, cautions, safety information,
and instructions in this manual before operating or ser
and instructions in this manual before operating or ser
and instructions in this manual before operating or servicing this tester. Failure to follow instructions could
and instructions in this manual before operating or servicing this tester. Failure to follow instructions could
result in death or serious injury.
result in death or serious injury.
result in death or serious injury.
• Risk of electric shock and burn. Contact with live circuits could result in death or serious injury.
Risk of electric shock and burn. Contact with live circuits could result in death or serious injur
Risk of electric shock and burn. Contact with live circuits could result in death or serious injur
• Use caution with voltages above 30V AC as a shock hazard may exist.
Use caution with voltages above 30V AC as a shock hazard may exist.
Use caution with voltages above 30V AC as a shock hazard may exist.
• A blinking or steady red glow and an audible beep indicate voltage present. If no indication, voltage could
A blinking or steady red glow and an audible beep indicate voltage present. If no indication, voltage could
A blinking or steady red glow and an audible beep indicate voltage present. If no indication, voltage could
still be present.
still be present.
still be present.
still be present.
• Before and after each use, verify operation by testing a known working circuit that is within the rating of
Before and after each use, verify operation by testing a known working cir
Before and after each use, verify operation by testing a known working cir
this unit.
this unit.
It is important that users of this tester read, understand, and follow all warnings, cautions, safety information,
• Never assume neutral or ground wires are de-energized. Neutrals in multi-wire branch circuits may be
Never assume neutral or ground wires are de-energized. Neutrals in multi-wire branch cir
Never assume neutral or ground wires are de-energized. Neutrals in multi-wire branch cir
vicing this tester. Failure to follow instructions could
vicing this tester. Failure to follow instructions could
energized when disconnected and must be retested before handling.
energized when disconnected and must be retested before handling.
energized when disconnected and must be retested before handling.
energized when disconnected and must be retested before handling.
energized when disconnected and must be retested before handling.
energized when disconnected and must be retested before handling.
energized when disconnected and must be retested before handling.
result in death or serious injury.
• The tester
WILL NOT
WILL NOT
detect voltage if:
detect voltage if:
detect voltage if:
detect voltage if:
Risk of electric shock and burn. Contact with live circuits could result in death or serious injury.
• The wire is shielded.
The wire is shielded.
Use caution with voltages above 30V AC as a shock hazard may exist.
• The operator is not grounded or is otherwise isolated from an effective earth ground.
The operator is not grounded or is other
The operator is not grounded or is other
A blinking or steady red glow and an audible beep indicate voltage present. If no indication, voltage could
• The voltage is DC.
The voltage is DC.
The voltage is DC.
The voltage is DC.
The voltage is DC.
The voltage is DC.
The voltage is DC.
• The tester
The tester
MAY NOT
MAY NOT
detect voltage if:
detect voltage if:
detect voltage if:
detect voltage if:
Before and after each use, verify operation by testing a known working circuit that is within the rating of
• The user is not holding the tester.
The user is not holding the tester.
The user is not holding the tester.
• The user is insulated from the tester with a glove or other materials.
The user is insulated from the tester with a glove or other materials.
The user is insulated from the tester with a glove or other materials.
• The wire is partially buried or in a grounded metal conduit.
The wire is partially buried or in a grounded metal conduit.
The wire is partially buried or in a grounded metal conduit.
energized when disconnected and must be retested before handling.
• The tester is at a distance from the voltage source.
The tester is at a distance from the voltage source.
The tester is at a distance from the voltage source.
The tester
• The field created by the voltage source is blocked, dampened, or otherwise interfered with.
The field created by the voltage source is blocked, dampened, or otherwise interfered with.
The field created by the voltage source is blocked, dampened, or otherwise interfered with.
• The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
wise isolated from an effective earth ground.
wise isolated from an effective earth ground.
• The tester is outside of operation conditions (listed in Specifications section).
The tester is outside of operation conditions (listed in Specifications section).
The tester is outside of operation conditions (listed in Specifications section).
The voltage is DC.
• Operation may be affected by differences in socket design and insulation thickness and type; tester may not be
Operation may be affected by differences in socket design and insulation thickness and type; tester may not be
Operation may be affected by differences in socket design and insulation thickness and type; tester may not be
compatible with some types of standard or tamper resistant (TR) electrical outlets.
compatible with some types of standard or tamper resistant (TR) electrical outlets.
compatible with some types of standard or tamper resistant (TR) electrical outlets.
The user is not holding the tester.
• In bright light conditions, the LED visual indicators will be less visible.
In bright light conditions, the LED visual indicators will be less visible.
In bright light conditions, the LED visual indicators will be less visible.
The user is insulated from the tester with a glove or other materials.
• Do not use if "power on" LED is not illuminated.
Do not use if "power on" LED is not illuminated.
Do not use if "power on" LED is not illuminated.
Do not use if "power on" LED is not illuminated.
The wire is partially buried or in a grounded metal conduit.
• Do not use if tester appears damaged or if the tester is not operating properly. If in doubt, replace the tester.
Do not use if tester appears damaged or if the tester is not operating properly. If in doubt, replace the tester
Do not use if tester appears damaged or if the tester is not operating properly. If in doubt, replace the tester
The tester is at a distance from the voltage source.
• Do not apply more than the rated voltage as marked on the tester (1000 volts AC).
Do not apply more than the rated voltage as marked on the tester (1000 volts AC).
Do not apply more than the rated voltage as marked on the tester (1000 volts AC).
The field created by the voltage source is blocked, dampened, or otherwise interfered with.
• Do not apply to uninsulated hazardous live conductors.
Do not apply to uninsulated hazardous live conductors.
Do not apply to uninsulated hazardous live conductors.
The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
• Detection above 50V is specified under "normal" conditions as specified below. The tester may detect at a
Detection above 50V is specified under "normal" conditions as specified below
Detection above 50V is specified under "normal" conditions as specified below
The tester is outside of operation conditions (listed in Specifications section).
different threshold at different conditions, or may not detect at all unless:
different threshold at different conditions, or may not detect at all unless:
different threshold at different conditions, or may not detect at all unless:
Operation may be affected by differences in socket design and insulation thickness and type; tester may not be
• The tip of the tester is within 0.25" of an AC voltage source radiating unimpeded.
The tip of the tester is within 0.25" of an AC voltage source radiating unimpeded.
The tip of the tester is within 0.25" of an AC voltage source radiating unimpeded.
The tip of the tester is within 0.25" of an AC voltage source radiating unimpeded.
compatible with some types of standard or tamper resistant (TR) electrical outlets.
• The user is holding the body of the tester with his or her bare hand.
The user is holding the body of the tester with his or her bare hand.
The user is holding the body of the tester with his or her bare hand.
In bright light conditions, the LED visual indicators will be less visible.
• The user is standing on or connected to earth ground.
The user is standing on or connected to earth ground.
The user is standing on or connected to earth ground.
• The air humidity is nominal (50% relative humidity).
The air humidity is nominal (50% relative humidity).
The air humidity is nominal (50% relative humidity).
Do not use if tester appears damaged or if the tester is not operating properly. If in doubt, replace the tester.
• The tester is held still.
The tester is held still.
Do not apply more than the rated voltage as marked on the tester (1000 volts AC).
• Always wear approved eye protection.
Always wear approved eye protection.
Always wear approved eye protection.
Do not apply to uninsulated hazardous live conductors.
• Comply with local and national safety requirements.
Comply with local and national safety requirements.
Comply with local and national safety requirements.
Detection above 50V is specified under "normal" conditions as specified below. The tester may detect at a
• If this product is used in a manner not specified by the manufacturer, protection provided by the product
If this product is used in a manner not specified by the manufacturer
If this product is used in a manner not specified by the manufacturer
different threshold at different conditions, or may not detect at all unless:
may be affected.
The user is holding the body of the tester with his or her bare hand.
The user is standing on or connected to earth ground.
The air humidity is nominal (50% relative humidity).
• DO NOT attempt to repair this tester. It contains no serviceable parts.
DO NOT attempt to repair this tester. It contains no serviceable parts.
DO NOT
• DO NOT expose tester to extremes in temperature or high humidity.
DO NOT expose tester to extremes in temperature or high humidity.
DO NOT
Comply with local and national safety requirements.
SYMBOLS ON TESTER
If this product is used in a manner not specified by the manufacturer, protection provided by the product
may be affected.
Risk of danger. Important information:
Risk of danger.
Risk of danger. Important information: It is important that users of this tester read,
Important information: It is important that users of this tester read,
understand, and follow all warnings, cautions, safety information, and instructions in this
understand, and follow all warnings, cautions, safety information, and instructions in this
understand, and follow all warnings, cautions, safety information, and instructions in this
manual before operating or ser
manual before operating or servicing this tester. Failure to follow instructions could result
manual before operating or ser
in death or serious injury.
in death or serious injury.
Risk of
Read
electric
instructions
shock
OPERATING INSTRUCTIONS
understand, and follow all warnings, cautions, safety information, and instructions in this
understand, and follow all warnings, cautions, safety information, and instructions in this
understand, and follow all warnings, cautions, safety information, and instructions in this
manual before operating or servicing this tester. Failure to follow instructions could result
vicing this tester. Failure to follow instructions could result
vicing this tester. Failure to follow instructions could result
TURN UNIT ON: Press and hold the power button
single-beep sound and watch for the green LED
TURN UNIT OFF: Press and hold the power button
beep sound and watch for the "power on" green LED
SILENT MODE: The tester can be operated with only visual indication of voltage. With the
tester powered off, press and hold the power button
then release.
SYSTEM SELF-TEST: The "power on" green LED
system integrity, and operation/active mode.
CHECKING FOR THE PRESENCE OF AC VOLTAGE: Prior to use, test on known live circuit to verify
tester functionality. Place tip
of the tester near an AC voltage sour
of the tester near an AC voltage source. When 50V to 1000V voltage
1
is detected, the tester will emit a high-pitched continuous beep, and the red LED
AUTO POWER-OFF: After 4 minutes of non-use, the tester automatically powers off to
conserve battery life.
CONTINUED ON OTHER SIDE
1.800.561.8187
T
T
Clasi
Clasi
WARNINGS
ve
ve
y.
y.
cuit that is within the rating of
cuit that is within the rating of
encuentre dentro de la capacidad de esta unidad.
cuits may be
cuits may be
.
.
No aplique voltaje nominal mayor que el indicado en el probador (1000 V CA).
. The tester may detect at a
. The tester may detect at a
CAUTION
, protection provided by the product
, protection provided by the product
It is important that users of this tester read,
por el producto puede verse afectada.
CAT
For measurements performed
For measurements performed
For measurements performed
Double
at the source of low-voltage
at the source of low-voltage
at the source of low-voltage
at the source of low-voltage
IV
insulated
installation and outside lines.
for ½ second, then release. Listen for
4
to illuminate.
2
for ½ second. Listen for a double-
4
to turn off.
2
installation and outside lines.
until the green LED
illuminates,
4
2
visually confirms battery sufficiency,
2
will illuminate.
2
ce. When 50V to 1000V voltage
probador cer
probador cer
probador cer
www.
NON-CONTACT VOLTAGE AND GFCI RECEPTACLE TEST KIT
INSTRUCTIONS
FIG. 1 - NCVT-1P
2 baterías AAA de 1,5 V (incluidas)
ENGLISH
1
1.
Tip
2
2
2.
LEDs
3.
Tester body
4.
Power button
5.
Battery cap
6.
Locking tab
7.
2x AAA batteries (included)
NOTE: There are no user-
4
serviceable parts inside
serviceable parts inside
serviceable parts inside
tester.
3
6
7
2 m
5
se encenderá.
.com
NCVT1PKIT
T
T
T
T
2 piles alcalines AAA de 1,5 V (comprises)
graves, voire la mort.
cuito activo que se
cuito activo que se
de fonctionnement se trouvant à proximité de l'unité.
.
.
Le testeur
.
.
Évitez d'appliquer une tension supérieure à la tension nominale indiquée sur le testeur (1000 V c.a.).
sont différentes, à moins que :
cionada
cionada
N'exposez PAS
CAT IV
1000V
le bouton de mise en marche
et maintenez-le enfoncé jusqu'à ce que la DEL verte
5000573
A
A
1390617 Rev. 07/22 B
près d'une source de tension c.a. Dès la détection d'une tension de 50 à 1000 V, le testeur produira un
près d'une sour
près d'une sour
ce de tension c.a. Dès la détection d'une tension de 50 à 1000 V, le testeur produira un
aigu et continu, puis la DEL rouge
information@itm.com
0 °C à 40 °C (32 °F à 104 °F)
out contact avec un circuit sous tension peut provoquer des blessure
out contact avec un circuit sous tension peut provoquer des blessure
cuit dont vous connaissez
cuit dont vous connaissez
, lorsque les cond
, lorsque les cond
. Il ne contient aucune pièce pouvant être réparée.
. Il ne contient aucune pièce pouvant être réparée.
.
appuy
appuy
appuy
appuy
, le testeur produira un
, le testeur produira un
, le testeur produira un
, le testeur produira un
s'allumera.

Advertisement

loading
Need help?

Need help?

Do you have a question about the NCVT1PKIT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Klein Tools NCVT1PKIT

  • Page 1 ENGLISH NCVT1PKIT NCVT-1P (FIG. 1) GENERAL SPECIFICATIONS • Tester Type: Non-contact voltage detector NON-CONTACT VOLTAGE AND GFCI RECEPTACLE TEST KIT • Voltage Range: 50 – 1000V AC INSTRUCTIONS • Frequency Range: 50 – 500Hz • Operating Altitude: 2,000 meters (6,561 feet) •...
  • Page 2 The Klein Tools RT205 is a receptacle tester designed to detect the most common wiring fréquents dans les prises standard.