Summary of Contents for LoRa Alliance MCF-LW13MIO

  • Page 1: Table Of Contents

    2023/04/19 13:39 manual_mcf-lw13mio Table of Contents MCF-LW13MIO Operating Manual ....................1. Description ..........................2. Overview ............................ 2.1 Technical data ......................... 2.2 Installation ..........................2.3 Power supply ........................... 2.4 Configuration .......................... 2.5 System leds ..........................2.6 Firmware update ........................3 I/O ..............................
  • Page 2 Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio https://www.enginko.com/support/ Printed on 2023/04/19 13:39...
  • Page 3: Mcf-Lw13Mio Operating Manual

    2023/04/19 13:39 1/19 manual_mcf-lw13mio MCF-LW13MIO Operating Manual Important safety information Read this manual before attempting to install the device! Failure to observe recommendations included in this manual may be dangerous or cause a violation of the law. The manufacturer will not be held responsible for any loss or damage resulting from not following the instructions of this operating manual.
  • Page 4: Overview

    Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio 2. Overview 2.1 Technical data CPU Cortex M0+ EEProm 32KB Flash 96KB Real time clock Encryption AES 128 bit Class C LoRaWAN® stack EU868, AS923, AU915, US915 EU868 version CE certified according to 2014/53/EU – Radio Equipment Directive (RED) Transmission band (EU version): 868 MHz Transmission Power (EU version): 14dBm max Power supply 24Vac/dc...
  • Page 5: Installation

    It is responsibility of the assembler of equipment incorporating to ensure that the overall equipment is safe. The MCF-LW13MIO must be mounted in vertical position. 2.2.1 Antenna The magnetic antenna must be positioned on a metal body. It should preferably be vertical and at least 30 cm away from other metal bodies.
  • Page 6: Power Supply

    Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio 2.3 Power supply Name Description Vss reference, power supply dc (-) Vss reference, power supply dc (-) VAC1 Power supply ac and dc (+) VAC2 Power supply ac only Valid range is 24Vac/dc ± 10% Maximum power consumption: 8W Connect the power supply to pins 11 and 12 of J3 if ac, pins 11 (+) and 10 (-) if dc.
  • Page 7: Configuration

    2023/04/19 13:39 5/19 manual_mcf-lw13mio 2.4 Configuration To deploy the sensor, use LoRaWEB online tool, to setup LoRaWAN® credentials and other preferences (only available for Windows®) : LoRaWEB Tool (iot.mcf88.cloud/LoRaWeb) Before connect the device the first time, please install LoRaBridge applications and drivers: https://iot.mcf88.cloud/LoRaWeb/#/download Validate your settings reading data after the write.
  • Page 8: System Leds

    Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio 2.5 System leds LoRaWAN® not configured Slow flashing Joining Quick flashing Sending Quick flashing Receiving Quick flashing Steady state Fixed Data error Flashing 2 seconds Connection error Flashing 1 second 2.6 Firmware update Save the new firmware file (.exe) on the PC, run the file, select the USB FW port and start the update: https://www.enginko.com/support/ Printed on 2023/04/19 13:39...
  • Page 9: Input

    2023/04/19 13:39 7/19 manual_mcf-lw13mio and waiting for the end message. 3 I/O As default, the device sends a message every time an input or an output changes. A downlink with new output status forces the device to send back an unplink with the new status. If the output status is the same of current one, the sensor will not send back any message.
  • Page 10 Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio Connector Pin Name Description Digital input 1 positive Digital input 1 negative Digital input 2 positive Digital input 2 negative Digital input 3 positive Digital input 3 negative Digital input 4 positive Digital input 4 negative Digital input 5 positive 10 I-5 Digital input 5 negative...
  • Page 11: Output

    2023/04/19 13:39 9/19 manual_mcf-lw13mio 3.2 Output Contact mode SPDT Max. power commutable 1250VA Maximum switching voltage 250Vac~ Minimum switching load mW 500mW (10V/5mA) Min. Number of operation 100.000 Max. current If driving an inductive load in AC, a Snubber must be provided in parallel to the contacts formed by a RC resistance network = 100Ohm 2w in series with a 100nF 400Volt polyester capacitor.
  • Page 12 Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio Connector Pin Name Description NC_4 Normally closed 4 COM_4 Common output 4 NO_4 Normally open 4 NC_5 Normally closed 5 COM_5 Common output 5 NO_5 Normally open 5 NC_6 Normally closed 6 COM6 Common output 6 NO_6 Normally open 6 Connector Pin Name...
  • Page 13: Lorawan® Network

    2023/04/19 13:39 11/19 manual_mcf-lw13mio and generate and XLS file that can be downloaded by downlinks: 4 LoRaWAN® network The sensor is compliant with LoRaWAN® specification 1.0.2, regional 1.0.2b. 4.1 Activation The device supports the following activations on a LoRaWAN® network: NONE: sensor not activated OTAA: the JoinEUI and the AppKey not setted, must be written to the device;...
  • Page 14: Configuration

    Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio The device exits factory activated with NONE mode. On request devices can be shipped aleady activated. Note: in OTAA AppKey is write only, in reading the field will always be empty, even if set. Network settings: please keep “Any”...
  • Page 15: I/O Settings

    2023/04/19 13:39 13/19 manual_mcf-lw13mio 5.1 I/O settings Status of the output at power on: select the status of OUTPUT 1 at power-on (default: off). I/O reading period [min]: if different from 0, this is the interval (in minutes) between one I/O messages status and the next one. Value can be between 1 and 255 minutes (default: 0 minutes - disabled).
  • Page 16: Other Settings

    Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio Number of counter inputs: Number of inputs used as pulses counters. Value = 1 means that input 1 is a pulses counter, value = 3 means the fist 3 inputs are pulses counter . (default: 0). Counters reading period [min]: if counter enabled, this is the interval (in minutes) between one measure and the next one.
  • Page 17: Diagnostic

    2023/04/19 13:39 15/19 manual_mcf-lw13mio Normally sensor asks for a time sync at every power on (uplink starting with 01) or, if enabled, once a week. Please check chapter 2.1 DATA FRAME FORMAT. Confirmed uplinks: set for confirmed uplinks (default: confirmed uplink). Single join/day: set for to allow only one join per day (default: multiple join allowed).
  • Page 18: Configuration File

    Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio Once the passwords are setted, to gain access from LoRaWEB to the sensor, set the right values before reading from the device: To bring back the sensor to factory default and reset the passwords, a reset code must be requested to enginko (please provide the DevEUI of the sensor when you ask for that code).
  • Page 19: Multi Devices Configuration

    2023/04/19 13:39 17/19 manual_mcf-lw13mio 7.1 Multi devices configuration With LoRaWEB is possible to configure many devices in an easy way. For multi-configuration is needed at least one XML file with the parameters to set. Settings on this file will be applied to all the sensors. With an additional XLS file is possible to load different LoRa configuration parameters (Activation Type, AppKey, AppEUI, NetKey, DevAddress, Band, Private option) for each sensor, based on DevEUI.
  • Page 20: Loraweb Tool

    Last update: 2023/04/17 08:30 manual_mcf-lw13mio https://www.enginko.com/support/doku.php?id=manual_mcf-lw13mio 8 LoRaWEB Tool enginko provides, upon free registration, LoRaWEB online tool, where for each sensor it is possible to find documentation, javascript examples for parsing, downlink generator and uplink decoder: LoRaWEB Tool (iot.mcf88.cloud/LoRaWeb) 9 Payload For payload descriptions, uplinks and downlinks format and available commands please refer to this https://www.enginko.com/support/ Printed on 2023/04/19 13:39...
  • Page 21: Ordering Code

    MCF-LW13MIO-AU enginko LoRaWAN® multi I/O module AU915-928 MCF-LW13MIO-WW enginko LoRa multi I/O module 2.4GHz 11 Declaration of conformity Hereby, enginko Srl declares that MCF-LW13MIO complies with the essential requirements and other relevant provisions of Directive 2014/53/EU. 12 Contacts enginko Srl...

Table of Contents